A dedicated access staircase for firemen should be provided in each underground station. This access should be arranged so as to provide uninterrupted access from ground level to station concourse and platform levels. If continuous access is not feasible, smoke sealed lobbies should be provided at concourse or other intermediate
levels and such lobbies should be protected with fire doors of adequate rating. Firemen staircases should be maintained under positive pressure at all times.
H-5.4.12 Emergency and escape lighting and illumination of means of all exits should comply with the various provisions under 3.5.6 and H-9.