| Equip. ID | Brand Name | Model No. | Capacity kW | Testing Standards | OSA CFM or Economizer? | COP | IPLV | Location |
|---|---|---|---|---|---|---|---|---|
| Heating Equipment Schedule | Heating Equipment Schedule | Heating Equipment Schedule | Heating Equipment Schedule | Heating Equipment Schedule | Heating Equipment Schedule | Heating Equipment Schedule | Heating Equipment Schedule | Heating Equipment Schedule |
| Equip. ID | Brand Name | Model No. | Capacity kW | Testing Standards | OSA CFM or Economizer? | Input kW | Output kW | Efficiency |
Fan Equipment Schedule
| Equipment ID | Brand Name | Model No. | Testing Standards | SP | Efficiency | Flow Control | Location of Service | |
Energy Conservation Building Code 2017 Compliance Forms
Comfort System & Controls Checklist
| Project Address | Date | |||||||||||
| The following information is necessary to check a building permit application for compliance with the mechanical requirements in the Energy Conservation Building Code. | ||||||||||||
| Applicability | Code Section | Component | Information Required | Location on Plans | Building Department Notes | |||||||
| s e Y | o N | A/N | ||||||||||
| Comfort Systems and Control | ||||||||||||
| Mandatory Provisions (Section 5.2) | ||||||||||||
| 5.2.1 | Ventilation | Indicate all habitable spaces are ventilated with outdoor air in accordance with § 5.2.1 and guidelines specified in NBC | ||||||||||
| 5.2.2 | Minimum Space Conditioning Equipment Efficiencies | Provide equipment schedule with type, capacity, efficiency | ||||||||||
| 5.2.3 | Controls | |||||||||||
| 5.2.3.1 | Timeclock | Indicate thermostat with night setback, 3 different day types per week, and 2-hour manual override, capable of retaining programming and time setting during loss of power for a period of at least 10 hours | ||||||||||
| 5.2.3.2 | Temperature Controls | Indicate temperature control with 3°C deadband minimum if the system provides both heating and cooling. | ||||||||||
| Indicate thermostats are interlocked to prevent simultaneous heating and cooling, where separate heating and cooling systems are there | ||||||||||||
| Indicate separate thermostat control for space types mentioned in § 5.2.3.2.(c) | ||||||||||||
| 5.2.2.3 | Occupancy Controls | Indicate occupancy controls for space types mentioned in § 5.2.3.3 | ||||||||||
| 5.2.2.4 | Fan Controls | Indicate two-speed motor, pony motor, or variable speed drive to control the fans and controls shall be capable to reduce the fan speed to at least two third of installed fan power | ||||||||||
| 5.2.2.5 | Dampers | |||||||||||
| 5.2.5 | Additional controls for SuperECBC Building | Indicate that the mechanical systems comply with § 5.2.4 and § 5.2.5 | |||||
| 5.2.5.1 | Variable Air Volume Fan Control | Indicate Fans in VAV systems shall have controls or devices to limit fan motor demand as per § 5.2.5.1 | |||||
| 5.2.6 | Piping & ductwork | Indicate sealing, caulking, gasketing, and weatherstripping | |||||
| 5.2.6.1 | Piping insulation | Indicate R-value of insulation | |||||
| 5.2.6.2 | Ductwork and Plenum insulation | Indicate R-value of insulation | |||||
| 5.2.7 | System Balancing | Show written balance report for HVAC systems serving zones with a total conditioned area exceeding 500 m2 | |||||
| 5.2.8 | Condensers | Indicate location of condenser and source of water used for condenser | |||||
| 5.2.9 | Service Hot Water Heating | ||||||
| 5.2.9.1 | Solar Water Heating | Indicate all Hotels and hospitals have solar water heating equipment installed for hot water design capacity as per §5.2.9.1 | |||||
| 5.2.9.2 | Heating Equipment Efficiency | Indicate service water heating equipment shall meet the performance and efficiency as per § 5.2.9.2 | |||||
| 5.2.9.3 | Supplementary Water Heating System | Indicate supplementary heating system is designed in consideration with § 5.2.9.3 | |||||
| 5.2.9.4 | Piping Insulation | Indicate the Piping insulation is compliant with § 5.2.6.1. | |||||
| 5.2.9.5 | Heat Traps | Indicate vertical pipe risers serving water heaters and storage tanks are as per § 5.2.9.5 | |||||
| 5.2.9.6 | Swimming Pools | Indicate the heated pools are provided with a vapor retardent pool cover on the water surface and temperature control and minimum insulation value as per § 5.2.9.6 | |||||
| Prescriptive Compliance Option (Section 5.3) | Prescriptive Compliance Option (Section 5.3) | Prescriptive Compliance Option (Section 5.3) | Prescriptive Compliance Option (Section 5.3) | Prescriptive Compliance Option (Section 5.3) | Prescriptive Compliance Option (Section 5.3) | Prescriptive Compliance Option (Section 5.3) | Prescriptive Compliance Option (Section 5.3) |
| 5.3.1 | Fans | Indicate fan type, motor efficiency and mechanical efficiency | Indicate fan type, motor efficiency and mechanical efficiency | Indicate fan type, motor efficiency and mechanical efficiency | |||
| 5.3.2 | Pumps | Indicate pump type (Primary, secondary, and condenser), its total installed capacity and efficiency | Indicate pump type (Primary, secondary, and condenser), its total installed capacity and efficiency | Indicate pump type (Primary, secondary, and condenser), its total installed capacity and efficiency | |||
| 5.3.3 | Cooling Towers | Indicate cooling tower type and installed capacity | |||||
| 5.3.4 | Air-Economizer(ECBC/ECBC+/SuperECBC) | Indicate air economizer is capable of modulating outside-air and return-air dampers to supply 50% of design supply air quantity as outside-air for respective building type. | Indicate air economizer is capable of modulating outside-air and return-air dampers to supply 50% of design supply air quantity as outside-air for respective building type. | Indicate air economizer is capable of modulating outside-air and return-air dampers to supply 50% of design supply air quantity as outside-air for respective building type. | |||
| 5.3.4 | Water-economizer(ECBC/ECBC+/SuperECBC) | Indicate water economizer is capable of providing 50% of the expected system cooling load at outside air temperatures of 10°C dry-bulb/7.2°C wet-bulb and below, if the designed building is a respective building type. | Indicate water economizer is capable of providing 50% of the expected system cooling load at outside air temperatures of 10°C dry-bulb/7.2°C wet-bulb and below, if the designed building is a respective building type. | Indicate water economizer is capable of providing 50% of the expected system cooling load at outside air temperatures of 10°C dry-bulb/7.2°C wet-bulb and below, if the designed building is a respective building type. | |||
| 5.3.4.3 | Partial Cooling | Indicate where required by § 5.3.4 economizers shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the cooling load. |