The prescriptive requirement of the Code regulates both interior and exterior lighting power.
Interior Lighting Power
The prescriptive lighting requirements limit the installed electric wattage for interior building lighting. Interior lighting includes all permanently installed general and task lighting shown on the plans. Interior lighting, for a building or a separately metered or permitted portion of a building, shall not exceed allowed power limits.
The installed interior lighting power for a building or a separately metered or permitted portion of a building shall be calculated in accordance with §6.3.4 and shall not exceed the interior lighting power allowance determined in accordance with either §6.3.2 or §6.3.3Error! Reference source not found.. Tradeoffs of interior lighting power allowance among portions of the building for which a different method of calculation has been used are not permitted.
As with the other sections of the Code, however, these lighting power requirements are minimum requirements. Designers working on specific projects may often be able to design more efficient lighting systems.
There are many exceptions to the lighting power requirement, generally for specialized lighting. These are listed in ECBC §6.3.1.
For interior lighting power requirements, the installed lighting power used by luminaires, including lamps, ballasts, current regulators, and central devices (except as specifically exempted in 7.1) can be calculated using the Building Area Method or the Space Function Method. These are explained in detail in the further sections.