Exterior lighting could be installed on the sire outside the building, integrated in landscape design, integrated in façade or could be used for highlighting special design feature as well. Energy efficiency can be achieved by improving the lamp efficacy, reducing the connected wattage and having good controls.
As per the Code,
(a) Lighting for all exterior applications not exempted in §6.3.5 shall be controlled by a photo sensor or astronomical time switch that is capable of automatically turning off the exterior lighting when daylight is available or the lighting is not required.
(b) Lighting for all exterior applications, of Schools and Business with built up area
greater than 20,000 m2, shall have lamp efficacy not less than 80 lumens per watt, 90 lumens per watt, and 100 lumens per watt, for ECBC, ECBC+, and SuperECBC Buildings respectively, unless the luminaire is controlled by a motion sensor or exempt under §6.1.
(c) Façade lighting and façade non-emergency signage of Shopping Complexes shall have separate time switches.
Exemption to §6.2.1.4: Exterior emergency lighting.