Motor failures are frequently caused by bearing failures and are often accompanied by the breakdown of the coils of insulated wire inside the motor (the stator windings) and other problems. When a motor fails, the owner is faced with deciding whether to rebuild it or replace it. Rebuilding, commonly called rewinding, usually entails a lower initial cost compared to a replacement motor, especially for larger motors. Rewinding can preserve and, in rare cases, slightly improve motor efficiency if skilfully done. However, the rewinding process provides many avenues by which the motor efficiency can be degraded, greatly increasing operating cost energy consumption.
To ensure the highest quality in repaired motors, the consistent use of test equipment and documentation procedures must be an integral part of the repair process, so that the efficiency of the motor and the quality of its components can be verified before the motor is put back into service.
A critical task in most motor rebuilds is to remove the old windings without altering the adjacent laminated steel cores, and then to wrap new insulated wire around the old cores.
The old windings are commonly embedded in thick coats of varnish (used to glue the windings inside the core slots) which prevent their easy removal. Heat, chemicals, or mechanical force are commonly used to loosen and pull out old windings; excessive use of any of these can cause damage to the cores. Improper machining, replacement bearings, wire diameter, and
winding technique can all compound, resulting in a rebuilt motor with poor performance and lower efficiency.
Although it is technically possible to rebuild a motor to its original specifications, survey results of actual rewind practices show that this is seldom the case. On the average, rewound motors are less efficient than they were before rewinding. The magnitude of this problem can vary widely from one rewind shop to another, and can only be properly identified when efficiency measurements are taken before and after rewinding.
(g) Motor users should insist on proper rewinding practices for any rewound motors. If the proper rewinding practices cannot be assured, the damaged motor should be replaced with a new, efficient one rather than suffer the significant efficiency penalty associated with typical rewind practices. Rewinding practices from BEE guideline for energy efficient motors shall be followed.
(h) Certificates shall be obtained and kept on record indicating the motor efficiency. Whenever a motor is rewound, appropriate measures shall be taken so that the core characteristics of the motor is not lost due to thermal and mechanical stress during removal of damaged parts. After rewinding, a new efficiency test shall be performed and a similar record shall be maintained.
Diesel Generator (DG)sets:
DG sets are used for power backup in buildings. Additionally, it could also be used to generate power for peak load application. Using diesel as the fuel, the generator converts mechanical energy into electrical energy. DG sets can be located inside the building or outside.
The DG set as a system consists of the diesel engine, AC alternator, control system and switchgear, foundation and corresponding civil works, exhaust facilities and fuel storage. Some of the disadvantages of the DG set are noise, vibration and pollution due to the exhaust.