Power distribution systems is the network of wires/cables that distribute power to all the enduses in a building from the point of supply. For a given load, energy losses depend on the size and material of the wires, length of wires and the overall circuit design.
Usually, the distribution voltage of 230V is fixed in buildings. Thus, sizing of the wires/cable depend on the load and current. Building loads are determined during the design stage. It is important to get accurate data as far as possible to design the size of the cable and avoid oversizing.
Based on the types of the load distribution lines must be segregated. For example, distribution line for HVAC must not be used for supplying the lighting loads. This disaggregation of cables will reduce the load in each distribution line minimize the losses.
Distribution losses due to heat generated by friction in the cables. The longer the wires, more is the heat loss. Thicker the wire, more is the heat loss. Further material of the cable itself offers
some friction depending on how good a conductor it is. An engineer or contractor can demonstrate real savings as well as the advantages of lower heat generated and increased flexibility of the installation with a properly sized distribution system. In addition, when less heat is generated, the result is reduced energy requirements for fans and air conditioning systems.
The power cabling shall be sized so that the distribution losses do not exceed
(a) 3% of the total power usage in ECBC Buildings
(b) 2% of the total power usage in ECBC+ Buildings
(c) 1% of total power usage in SuperECBC Buildings
Record of design calculation for the losses shall be maintained. Load calculation shall be calculated up to the panel level.