All fenestration with U-factors, SHGC, or visible light transmittance determined, certified, and labeled in accordance ISO 15099 shall be assigned those values.
Unrated Vertical Fenestration.
Unlabeled vertical fenestration, both operable and fixed, shall be assigned the U-factors, SHGCs, and visible light transmittances in Table 10-1.
| Frame Type | Glazing Type | U-Factor(W/m<sup>2</sup>.K) |
|---|---|---|
| All frame types | Single Glazing | 7.1 |
| Wood, vinyl, or fiberglass frame or metal | Double Glazing | 3.4 |
| frame with thermal break | ||
| Metal and other frame type | Double Glazing | 5.1 |
Unrated Sloped Glazing and Skylights
Unrated sloped glazing and skylights, both operable and fixed, shall be assigned the SHGCs and visible light transmittances in Table 10-1. To determine the default U-factor for unrated sloped glazing and skylights without a curb, multiply the values in Table 10-1 by 1.2. To determine the default U-factor for unrated skylights on a curb, multiply the values in Table 10-1 by 1.6.
Typical Roof Constructions
For calculating the overall U-factor of a typical roof construction, the U-factors from the typical wall construction type and effective U-factor for insulation shall be combined according to the following equation:
where
UTotalRoof Total U-factor of the roof with insulation
UTypical Roof U-factor of the roof
UTypical Insulation U-factor of the effective insulation