Current transformer (CT) is used to measure current and Potential transformer (PT) is used to measure voltage. These instrument transformers as they are called are used primarily for measuring losses.
All measurement of losses shall be carried out by using calibrated digital meters of class 0.5 or better accuracy and certified by the
manufacturer. All transformers of capacity of 500 kVA and above would be equipped with additional metering class current transformers (CTs) and potential transformers (PTs) additional to requirements of Utilities so that periodic loss monitoring study may be carried out.