The simulation software shall be a computerbased program for the analysis of energy consumption in buildings and be approved by the authority having jurisdiction. The simulation
program shall, at a minimum, have the ability to model the following:
a) Energy flows on an hourly basis for all 8,760 hours of the year,
b) Hourly variations in occupancy, lighting power, miscellaneous equipment power, thermostat set points, and HVAC system operation, defined separately for each day of the week and holidays,
c) Thermal mass effects,
d) Ten or more thermal zones,
e) Part-load and temperature dependent performance of heating and cooling equipment,
f) Air-side and water-side economizers with integrated control.
In addition to the above, the simulation tool shall be able to produce hourly reports of energy use by energy source and shall have the capability to performing design load calculations to determine required HVAC equipment capacities, air, and water flow rates in accordance with §Error! Reference source not found. for both the proposed and Standard building designs
The simulation program shall be tested according to ASHRAE Standard 140 Method of Test for the Evaluation of Building Energy Analysis Computer Programs (ANSI approved) and the results shall be furnished by the software provider.
WBP Method uses the output of a simulation program to demonstrate that the Proposed Design complies with the ECBC. In order to make sure that these calculations are sufficiently accurate for the purposes of the Code, a series of requirements have been set. The most basic requirement is that the simulation program be a computer-based program designed to analyze energy consumption in buildings, and that it has the capability to model the features of the
Proposed Design. A building energy simulation model comprises of a detailed description of the building geometry and materials of construction.