Notice the large difference between voltamperes and Watts V x I = 230 x 17 = 3910 VA P (power) = 1657 Watts
This difference is an important consideration for circuit design and sizing different circuit components.
A load with a power factor of 1.0 results in the most efficient loading of the supply. A load with a power factor of, say, 0.8, results in much higher losses in the supply system and a higher bill for the consumer.
In commercial buildings, majority of the loads are inductive such as induction motor, a power transformer, a ballast in a luminaire, a welding set or so on. Hence, the resulting reactive power tend to reduce the power factor. Consequently, a power factor correction is required which is discussed in §7.2.5.
Energy in electric circuits
Energy is the power used over a certain time. Since the units of power is Watts and time is hours, the units of energy is Watt-hour or kilowatt-hour (kWh).
1 kWh is commonly referred to as 1 unit. If you observe the electricity bill, the total number of units is tabulated which is the total kWh of energy used by the facility.
Example 7-D
Find the daily energy consumption of the equipment listed if they are used for the length of time shown.
Split AC (3500 W) – 5 hrs Coffee maker (500 W) – 6 hrs Computer (75 W) – 12 hrs Microwave (1000 W) – 2hrs
Split AC 3500 W = 3.5 kW x 5 = 17.5 kWh
Computer
75 W = 0.075 kW x 12 = 0.9 kWh
Microwave 1000 W = 1 kW x 2 = 2 kWh
Total daily energy consumption = 23.4 kWh
Types of electrical circuits
There are two types of circuit arrangements – series and parallel. While the concept remains same for both AC and DC, circuit calculations are different.