When motors are oversized and operate for extended periods at significantly less than full load, there are three significant operational penalties – reduced efficiency, reduced slip (important if the load is a cube-law type), and reduced power factor.
Depending on the motor, efficiency will typically peak at somewhere between 75% load and full load. The larger the motor and the higher its peak efficiency, the more likely it will have a relatively flat efficiency curve between 50% load and full load, with a hump at 75% load some 0.3 to 1% points higher than at full load. Efficiency drops
precipitously below 50% load, with the average 100-hp energy efficient motor losing over two points between 50 and 25% load and the average 100-hp standard efficiency induction motor dropping some 5.5 points over the same range. Smaller motors lose even more, particularly at lower efficiencies.
A general rule-of-thumb is that a one percentage point increase in efficiency is equivalent to about a one-third-point increase in slip – a decrease in slip can therefore quickly negate even a significant energy efficiency improvement.
As per the Code,
(e) Motor horsepower ratings shall not exceed 20% of the calculated maximum load being served.
(f) Motor nameplates shall list the nominal fullload motor efficiencies and the full-load power factor.