UPS provides backup power when utility power fails, either long enough for critical equipment to shut down properly so that no data is lost, or long enough to keep required loads operational until a generator comes online. Along with backup power, it conditions incoming power so that quality power reaches to the load. It is commonly used to dedicatedly serve critical loads such as computers, servers, routers and other IT loads.
These losses in the system occur due to internal circuitry of the UPS system. Generally, UPS has efficiency equal or greater than 90%. For some UPS, it could reach up to 97%. As per the Code,
In all buildings, UPS shall meet or exceed the energy efficiency requirements listed in Table 7-4. Any Standards and Labeling program by BEE
shall take precedence over requirements listed in this section.
| UPS Size | Energy Efficiency Requirements at 100% Load |
|---|---|
| kVA< 20 | 90.2% |
| 20<=kVA <= 100 | 91.9% |
| kVA > 100 | 93.8% |