Motor Efficiency is the ratio of the useful mechanical power output to the total electric power input to the motor. Like all electromechanical equipment, motors consume some “extra” energy in order to make the conversion. Efficiency reflects how much total energy a motor uses in relation to the rated power delivered to the shaft.
A motor’s nameplate rating is based on output horsepower, which is fixed for continuous operation at full load. The amount of input power needed to produce rated horsepower will vary from motor to motor, with more efficient motors requiring less input wattage than lessefficient models to produce the same output. Electrical energy input is measured in watts, while output is given in horsepower. Output power for motors may also be stated in watts or kilowatts.
1 horsepower = 746 watts
The International Electrotechnical Commission (IEC) has developed the International Efficiency (IE) classes for motors. This is an international standard that stipulates the energy efficiency of low voltage AC motors. IS (Indian Standard) uses same standards to classify the motor efficiency. The IE classes are shown in Table 7 A.
| Class type | Class number |
|---|---|
| Standard efficiency | IE1 |
| High efficiency | IE2 |
| Premium efficiency | IE3 |
| Super premium efficiency | IE4 |
Higher the class number, the higher the motor efficiency. As per the Code,
Motors shall comply with the following:
(a) Three phase induction motors shall conform to Indian Standard (IS) 12615 and shall fulfil the following efficiency requirements:
I. ECBC Buildings shall have motors of IE 2 (high efficiency) class or a higher class
II. ECBC+ Buildings shall have IE 3 (premium efficiency) class motors or higher class
III. SuperECBC Buildings shall have IE 4 (super premium efficiency) class motors
(b) All permanently wired polyphase motors of 0.375 kW or more serving the building and expected to operate more than 1,500 hours per year and all permanently wired polyphase motors of 50kW or more serving the building and expected to operate more than 500 hour per year, shall have a minimum acceptable nominal full load motor efficiency not less than levels specified in the latest version of IS 12615. (Refer to
(c) Table 7 B through Table 7 E)
(d) Motors of horsepower differing from those listed in the table shall have efficiency greater than that of the next listed kW motor.
| Rated Output | Frame Designation | Full Load Speed Min | Full Load Current Max | Breakaway Torque in Terms of Full Load Torque Min | Breakaway Current in Terms of Full Current, Equal or Below | Nominal Efficiency | ||
| For eff 2 | For eff 1 | For eff2 | For eff 1 | |||||
| kW | Rev/min | Amp | Percent | Percent | Percent | Percent | Percent | |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| 0.37 | 71 | 2790 | 1.2 | 170 | 600 | 650 | 66 | 70.2 |
| 0.55 | 71 | 2760 | 1.6 | 170 | 600 | 650 | 70 | 74 |
| 0.75 | 80 | 2780 | 2 | 170 | 600 | 650 | 73 | 77 |
| 1.1 | 80 | 2790 | 2.8 | 170 | 600 | 650 | 76.2 | 82.8 |
| 1.5 | 90S | 2800 | 3.7 | 170 | 600 | 650 | 78.5 | 84.1 |
| 2.2 | 90L | 2810 | 5 | 170 | 650 | 700 | 81 | 85.6 |
| 3.7 | 100L | 2820 | 8 | 160 | 650 | 700 | 84 | 87.5 |
| 5.5 | 132S | 2830 | 11 | 160 | 650 | 700 | 85.7 | 88.6 |
| 7.5 | 132S | 2840 | 15 | 160 | 650 | 700 | 87 | 89.5 |
| 9.3 | 160M | 2840 | 18.5 | 160 | 650 | 700 | 87.7 | 90 |
| 11 | 160M | 2860 | 21.5 | 160 | 650 | 700 | 88.4 | 90.5 |
| 15 | 160M | 2870 | ||||||
Source: IS 12615: 2004, Energy-Efficient Induction Motors --- Three-Phase Squirrel Cage (First Revision)
| Rated Output | Frame Designation | Full Load Speed Min | Full Load Current Max | Breakaway Torque in Terms of Full Load Torque Min | Breakaway Current in Terms of Full Current, Equal or Below | Nominal Efficiency | ||
| For eff 2 | For eff 1 | For eff 2 | For eff 1 | |||||
| kW | Rev/min | Amp | Percent | Percent | Percent | Percent | Percent | |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| 0.37 | 71 | 2790 | 1.2 | 170 | 600 | 650 | 66 | 70.2 |
| 0.55 | 71 | 2760 | 1.6 | 170 | 600 | 650 | 70 | 74 |
| 0.37 | 71 | 1330 | 1.4 | 170 | 550 | 600 | 66 | 73 |
| 0.55 | 80 | 1340 | 1.7 | 170 | 550 | 600 | 70 | 78 |
| 0.75 | 80 | 1360 | 2.2 | 170 | 550 | 600 | 73 | 82.5 |
| 1.1 | 90S | 1370 | 2.9 | 170 | 550 | 600 | 76.2 | 83.8 |
| 1.5 | 90L | 1380 | 3.8 | 170 | 550 | 600 | 78.5 | 85 |
| 2.2 | 100L | 1390 | 5.1 | 170 | 600 | 700 | 81 | 86.4 |
| 3.7 | 112M | 1410 | 8.1 | 160 | 600 | 700 | 84 | 88.3 |
| 5.5 | 132S | 1420 | 11.4 | 160 | 600 | 700 | 85.7 | 89.2 |
| 7.5 | 132M | 1430 | 15.4 | 160 | 600 | 700 | 87 | 90.1 |
| 9.3 | 160M | |||||||
Source: IS 12615: 2004, Energy-Efficient Induction Motors --- Three-Phase Squirrel Cage (First Revision)
| Rated Output | Frame Designation | Full Load Speed Min | Full Load Current Max | Breakaway Torque in Terms of Full Load Torque Min | Breakaway Current in Terms of Full Current, Equal or Below | Nominal Efficiency | ||
| For eff 2 | For eff 1 | For eff 2 | For eff 1 | |||||
| kW | Rev/min | Amp | Percent | Percent | Percent | Percent | Percent | |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| 0.37 | 80 | 870 | 1.4 | 160 | 550 | 600 | 65 | 69.4 |
| 0.55 | 80 | 870 | 1.9 | 160 | 550 | 600 | 68 | 72 |
| 0.75 | 90S | 890 | 2.3 | 160 | 550 | 600 | 71 | 74.6 |
| 1.1 | 90L | 900 | 3.2 | 160 | 550 | 600 | 74 | 77.3 |
| 1.5 | 100L | 900 | 4 | 160 | 550 | 600 | 76 | 79.6 |
| 2.2 | 112M | 910 | 5.5 | 150 | 600 | 700 | 79 | 82.2 |
| 3.7 | 132S | 920 | 8.8 | 150 | 600 | 700 | 82.5 | 85.1 |
| 5.5 | 132M | 920 | 12.7 | 150 | 600 | 700 | 84.5 | 86.8 |
| 7.5 | 160M | 930 | 16.7 | 150 | 600 | 700 | 86 | 88.1 |
| 9.3 | 160L | 930 | 20.5 | 140 | 600 | 700 | 87 | 89.3 |
| 11 | 160L | 935 | 23.0. | 140 | 600 | 700 | 87.5 | 89.7 |
| 15 | 180L | |||||||
Source: IS 12615: 2004, Energy-Efficient Induction Motors --- Three-Phase Squirrel Cage (First Revision)
| Rated Output | Frame Designation | Full Load Speed Min | Full Load Current Max | Breakaway Torque in Terms of Full Load Torque Min | Breakaway Current in Terms of Full Current, Equal or Below | Nominal Efficiency | ||
| For eff 2 | For eff 1 | For eff 2 | For eff 1 | |||||
| kW | Rev/min | Amp | Percent | Percent | Percent | Percent | Percent | |
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) | (9) |
| 0.37 | 90S | 640 | 1.5 | 150 | 550 | 600 | 62 | 66.8 |
| 0.55 | 90L | 640 | 2.1 | 150 | 550 | 600 | 67 | 71.1 |
| 0.75 | 100L | 650 | 2.7 | 150 | 550 | 600 | 70 | 73.8 |
| 1.1 | 100L | 660 | 3.5 | 150 | 550 | 600 | 72 | 76.2 |
| 1.5 | 112M | 670 | 4.5 | 150 | 550 | 600 | 74 | 77.9 |
| 2.2 | I32S | 680 | 6.1 | 140 | 600 | 700 | 77 | 80.5 |
| 3.7 | 160M | 690 | 9.8 | 140 | 600 | 700 | 80 | 83 |
| 5.5 | 160M | 690 | 14.2 | 140 | 600 | 700 | 82.5 | 85.1 |
| 7.5 | 160L | 695 | 19 | 140 | 600 | 700 | 84 | 86.4 |
| 9.3 | 180L | 700 | 23 | 140 | 600 | 700 | 85 | 87.3 |
| 11 | 180L | 700 | 26 | 140 | 600 | 700 | 86 | 88.1 |
| 15 | 200L | 705 | ||||||
Source: IS 12615: 2004, Energy-Efficient Induction Motors --- Three-Phase Squirrel Cage (First Revision)