Although there is no simpler way to reduce the amount of energy consumed by lighting systems than to manually turn lights off whenever not needed, this is not done as often as it could be. In response to that problem, the Code requires several automatic switches that either work on time schedule or sense the presence of occupants.
Automatic Control Strategies
Several different approaches can be used to control electric lighting. The control hardware and design practices are discussed below:
Scheduling Control: Use a time scheduling device to control lighting systems according to predetermined schedules.
Occupancy Sensing: Control lights in response to the presence or absence of people in the space.
Daylighting: Switch or dim electric lights in response to the presence or absence of daylight illumination in the space.
Lumen Maintenance: Gradually adjust electric light levels over time to correspond with the depreciation of light output from aging lamps.
Scheduling Controls
Programmable timing, also known as automatic time scheduling, is the oldest form of automatic lighting control. Time scheduling manages the on and off times of a building’s lighting systems.
Scheduling systems function by turning off all or some of the lights when a building space is
unoccupied. In the most basic time-scheduling scheme, a time switch switches lighting circuits on or off based on programmable schedules. For example, exterior lighting is usually switched on to correspond to sundown and is switched off again at daybreak. By contrast, time scheduling of interior lighting systems is based, for the most part, on occupancy schedules. In some cases, time switches are used to energize additional lighting control systems, such as daylighting controls, which are held off during unoccupied periods. Time-scheduling systems employ the following components:
A central processor is usually capable of controlling several output channels, each of which may be assigned to one or more lighting circuits.
Relays are series-wired to lighting control zones and are controlled by the central processor.
Overrides are required to accommodate individuals who use the space during scheduled off hours. Individuals can activate manual switches or use telephone overrides to regain temporary control of the lights in a given space.
Occupancy Sensors
Occupant-sensing devices are an alternative to scheduling controls and an acceptable means of meeting the requirement for automatic shutoff.
Occupancy sensors are automatic scheduling devices that detect motion and turn lights on and off accordingly. Most devices can be calibrated for sensitivity and for the length-of-time delay between the last detected occupancy and extinguishing of the lights. The most energyefficient occupancy sensors, known as “manualon, automatic-off,” require that the user manually switch on the lights when entering a controlled zone (the “lights off” function is still automatic).
Occupancy sensor systems typically consist of a motion detector, a control unit, and a relay. Usually, two or more of the components are integrated into one package. Most systems also require a power supply in the form of a transformer, which steps down the building voltage to 24V. The detector collects information, then sends it to the controller, where it is processed. Output from the controller activates the relay, which in turn switches the light circuit.
There are two major types of occupancy controls.
• Wallbox units are designed to fit into a standard wall switch box and operate on the building voltage (i.e., a separate power supply is not required). Their main limitation is their relatively short range. Consequently, they tend to be used in small offices and meeting rooms.
Wall and Ceiling units typically contain an integrated sensor/controller unit wired (Class 2) to a switch pack containing the relay and power supply. They are far more popular than wallbox units and have very few application limitations.
The designer is free to arrange occupant sensing controls in any manner that makes sense for the building design. In office spaces, each room or space might have an occupant sensor. Of course, the smaller the area controlled, the greater the energy savings will be. In open office areas, several occupant sensors may be connected so that the lights remain on if any one of the sensors detects occupants. However, in order to satisfy the Code requirement, it is necessary that all the general lighting be controlled by one or more occupant sensors.
As per the Code,
(a) 90% of interior lighting fittings in building or space of building larger than 300 m2shall be equipped with automatic control device.
(b) Additionally, occupancy sensors shall be provided in
(i) All building types greater than 20,000 m2 BUA, in
a. All habitable spaces less than 30 m2, enclosed by walls or ceiling height partitions.
b. All storage or utility spaces more than 15 m2in all building types with BUA greater than 20,000 m2.
c. Public toilets more than 25 m2, controlling at least 80 % of lighting fitted in the toilet. The lighting fixtures, not controlled by automatic lighting shutoff, shall be uniformly spread in the area.
(ii) In corridors of all Hospitality greater than 20,000 m2 BUA, controlling minimum 70% and maximum 80% of lighting fitted in the public corridor. The lighting fixtures, not controlled by automatic lighting shut off, shall be uniformly spread in the area.
(iii) In all Business and all conference or meeting rooms.
(c) Automatic control device shall function on either:
(i) A scheduled basis at specific programmed times. An independent program schedule shall be provided for areas of no more than 2,500 m2 and not more than one floor, or,
(ii) Occupancy sensors that shall turn off the lighting fixtures within 15 minutes of an occupant leaving the space. Light fixtures controlled by occupancy
sensors shall have a wall-mounted, manual switch capable of turning off lights when the space is occupied.
Exception to §6.2.1.1: Lighting systems designed for emergency and firefighting purposes.