This defines the minimum set of capabilities for WBP method simulation programs. These have been broadly defined to allow all complying programs to be considered for approval by the Authority Having Jurisdiction, while eliminating programs that would not be able to adequately account for the energy performance of building features important under the Code. These minimum capabilities are:
Approved Simulation Program: The simulation program should be subjected to the International Energy Agency BESTEST (Building Energy Simulation Test and
Diagnostic Method) or the ANSI/ ASHRAE Standard 140-2004, Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs.
Minimum Hours per Year: Programs must be able to model energy flows on an hourly basis for the entire year (8,760 hours).
Hourly Variations: Building loads and system operations vary hour-by-hour, and their interactions have a great influence on building energy performance. Approved programs must have the capability to model hourly variations – and to establish separately designed schedules of operation for each day of the week and for holidays – for occupancy, lighting power, miscellaneous equipment power, thermostat set points, and HVAC system operation.
Thermal Mass Effects: A building’s ability to absorb and hold heat varies with the type of construction and with the system and ventilation characteristics. This affects the timing and magnitude of loads handled by the HVAC system. Simulation programs must be able to model these thermal mass effects.
Number of Thermal Zones: There are multiple thermal zones in all but the simplest buildings, and they experience different load patterns. Approved programs must be able to model at least 10 thermal zones; many simulation programs can handle far greater number of zones.
Part-Load Performance: Mechanical equipment seldom experiences full-load operating conditions, so the performance of this equipment under part-load conditions is important. Approved programs must incorporate part-load performance curves in their calculations.
Correction Curves: The efficiency of the mechanical equipment varies depending on temperature and humidity conditions. Approved programs must incorporate
efficiency correction curves for mechanical heating and cooling equipment.
Economizers: Economizer cooling is an important efficiency measure under the Standard. Approved programs must have the capability to model both airside and waterside economizers with integrated control.
Design Load Calculations: Approved programs must be capable of performing design load calculations to determine required HVAC equipment capacities and air and water flow rates for both the Proposed Design and the Standard Design. This is to ensure that the systems in both design simulations are properly sized, which avoids the problem of differing part-load performance characteristics between the two designs.