Daylight controls enable daylight harvesting. This is a technique using which the artificial lighting is controlled by switching off or dimming in response to the available daylight levels. Thus, daylight controls reduce lighting energy use while providing visual comfort.
Depending the size of the fenestrations and specifications such as the VLT, the daylit area can extend upto two times the head height of the fenestration. Luminaires located in this area should be controlled by the daylight sensor.
A daylight sensor is basically a photosensor that can detect lux levels and converts it to analog voltage that controls the ballast of the luminaire. Dimmable luminaires allow continuous adjustment of light level in proportion to the available natural light. Dimming the light reduces the electric power demand contributing to energy savings.
In the other approach, the luminaire is switched off when the daylight level reaches a predefined level as detected by the photosensor. Another variant of this on-off switching is the step switching or the “bi-level switching”. In this method, multiple lamps in a single luminaire can be switched on or off independent of each other.
For example, the luminaire output can be stepped down one level and reduced to 50% before turning it off completely.
As per the Code,
(a) Luminaires, installed within day lighting extent from the window as calculated in § 4.2.3, shall be equipped with either a manual control device to shut off luminaires, installed within day lit area, during potential daylit time of a day or automatic control device that:
Has a delay of minimum 5 minutes, or,
II. Can dim or step down to 50% of total power.
(b) Overrides to the daylight controls shall not be allowed.
(c) For SuperECBC Buildings, Lighting Power Density adjustment factor of 20% shall be allowed to all spaces with more than 70% of their area under daylight controls.