Fenestration areas and performance are strong drivers of energy use in buildings. Therefore, the ECBC places great emphasis in how these values are calculated and applied for compliance.
ECBC §4.3.3 and §4.3.4 sets the prescriptive upper limits on vertical fenestration area and skylight area. If the fenestration areas for the Proposed Design are less than these limits, the Standard Design shall have the same areas and orientations as the Proposed Design.
If the fenestration areas in the Proposed Design exceed these limits, then the corresponding areas in the Standard Design must be adjusted down to these limits and corresponding increases made to opaque areas so that the gross wall area is no longer the same for the Proposed Design and the Standard Design.
The prescriptive envelope requirements of the Code do not provide an exception for streetlevel, street-side vertical fenestration (e.g., store display windows). Thus, such fenestration must be modeled identically for the Proposed Design and the Standard Design simulation runs so that the representation of these types of fenestration is energy neutral.
U-Factors
The U-factor for the Standard Design is set to the minimum required for the climate, as specified in ECBC Table 4-10. The minimum U-factor is a function of the percentage of glazing (WWR) in a wall or roof, as described above.
Solar Heat Gain Coefficient
The solar heat gain coefficient value for the fenestration applied in the Standard Design is set to the maximum required for the climate and for
each orientation, as specified in ECBC Table 4-10. The maximum SHGC is a function of the glazing percentage of wall or roof, which is based on the Proposed Design as described above.
If the vertical fenestration to be used is unrated, then the SHGC values in ECBC Table 10-1 must be used.
Shading of Fenestration
Glazing installed in the Standard Design must be modeled as being flush with its wall or roof surface, and without any external shading devices. This ruling allows the Proposed Design to use to its advantage shading from window recesses, overhangs, side fins, or other permanent shading devices that reduce solar gains on the glazing.
Interior shading devices, if not automatic, should not be modeled in the Proposed Design. In Standard Design, no shading should be modeled.
Exceptions for Envelope
Any simulation program necessarily relies on a somewhat simplified description of the building envelope. It is usually time-consuming and difficult to explicitly detail every minor variation in the envelope design, and if good engineering judgment is applied, these simplifications won’t result in a significant decline in accuracy. Three exceptions, where more substantial simplifications may be made, are: