Along with controls for individual lights or sets of fixtures, master controls are required for each space which can shut off all the lights within the space. For example, the last person leaving the office is much more likely to use a master switch than to go through the office turning off every switch. Similarly, a cleaning crew can easily use master switches to turn lights off at the end of a working day.
Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the space. Each control device shall be activated either manually by an occupant or automatically by sensing an occupant. Each control device shall
(a) control a maximum of 250 m2for a space less than or equal to 1,000 m2, and a maximum of 1,000 m2 for a space greater than 1,000 m2.
(b) have the capability to override the shutoff control required in § 6.2.1.1 for no more than 2 hours, and
(c) be readily accessible and located so the occupants can see the control.
A summary of the Code requirement is given below.
| ECBC requirements: Space Area and Lighting Controls | ||
| S.No. | Space Area | Coverage Area for each control device |
| 1 | Up to 1000 m2 | 250 m2 max. |
| 2 | More than 1000 m2 | 1000 m2 max. |
An exception to § 6.2.1.2 (c) is provided for control devices that need to be remotely installed for reasons of safety or security. However, a remotely located device must have a pilot light indicator as part of or next to the control device and it must be clearly labeled to identify the controlled lighting device.