Many special lighting applications must be controlled separately, including display lighting in retail stores, case lighting, hotel/motel guest rooms, task lighting, non-visual lighting applications, and demonstration lighting.
As per the Code,
The following lighting applications shall be equipped with a control device to control such lighting independently of general lighting:
(a) Display/ Accent Lighting Display or accent lighting greater than 300 m2 area shall have a separate control device.
Lighting used to highlight artwork or merchandise in retail stores, art galleries, lobbies, and other spaces must have a separate lighting control. This additional control can save considerable energy since the hours required for display lighting are generally fewer than the hours that the space is occupied.
In a retail store, for instance, employees typically arrive one to two hours before the store opens in order to prepare the store, and often employees need to stay for an hour or two after the store closes. Without a separate control for display lighting, the display lighting would have to be
operated for two to four hours each day when it isn’t needed. Controls for display lighting can be situated in remote locations, but it is advisable that they have indicator lights and be clearly marked to indicate which lighting is controlled.
(b) Hotel Guest Room Lighting. Guest rooms and guest suites in a hotel shall have a master control device at the main room entry that controls all permanently installed luminaires and switched receptacles.
A master lighting control is required at the entry door of hotel and motel guest rooms to control all permanently installed luminaires and switched receptacles. The control is usually a three-way device wired in combination with local controls. In multiple-room suites, a single master control must be located at the main entrance. This master lighting control allows guests or the housekeeping staff to turn off all permanently installed luminaires when they are exiting the room.
(c) Task Lighting. Supplemental task lighting including permanently installed under shelf or under cabinet lighting shall have a control device integral to the luminaires or be controlled by a wall-mounted control device provided the control device complies with §6.2.1.2.
All supplemental task lighting in a space shall have a separate control. Desk lamps will inherently meet this requirement, but the requirement also applies to permanently installed under-shelf or under-cabinet lighting. Such lighting can have a switch integral to the luminaires or be controlled by a wall-mounted control device, provided the control device is accessible and the controlled lighting can be observed when the switch is toggled
(d) Nonvisual Lighting. Lighting for nonvisual applications, such as plant
growth and food-warming, shall be equipped with a separate control device.
Lighting needed for non-visual purposes, such as plant growth or food warming, must have a separate control. This is because such lighting is likely to be needed at different times than the general lighting.
(e) Demonstration Lighting. Lighting equipment that is for sale or for demonstrations in lighting education shall be equipped with a separate control device accessible only to authorized personnel.
Lighting on display in retail lighting stores and lighting that is being demonstrated in classrooms and lighting education facilities must have a separate control. Again, the justification is that such lighting is operated on a separate schedule from the general lighting
Exit Signs
Internally-illuminated exit signs shall not exceed 5 Watts per face.
Electrically powered exit signs normally use incandescent bulbs. Most LED and some CFL exit signs can meet ECBC requirement. Due to their low power consumption, LED exit signs can be purchased with built-in backup power supplies (i.e., batteries). With an estimated service life of 10 years or more, LEDs require significantly fewer lamp replacements than exit signs equipped with either incandescent lamps or CFLs.