There may also be cases where the simulation program lacks modeling capabilities needed to fully model a component or system of the
Proposed Design. If this means that a reasonable calculation of the proposed building cannot be made, then the best solution is to seek a different program that has the needed capabilities.
One alternative is to ignore the system in the model, provided this does not affect the modeling of energy consumption measures, described in the previous section. A second alternative is to apply engineering judgment and to model the component or system using a thermodynamically similar model that is within the capabilities of the program being used. This requires a thorough understanding of the algorithms of the simulation program and the thermodynamic characteristics of the component being modeled, but in many cases, it can be accomplished without compromising accuracy. It makes little sense, though, to use an alternate program for a component if it means losing the interactive capabilities of the hourly modeling tool. Consequently, this is generally not recommended.
A third alternative is to simply model the system or component as if it were the base case system defined for the Standard Design. Of course, this alternative is only allowable when the system or component meets the prescriptive requirements of the ECBC. Also, this alternative is not preferred, as the intent is to model the actual Proposed Design. The general rule, therefore, is if a simulation program can’t model a component, then the component must not be given any energy saving benefits.
Climate Data
The simulation program shall use hourly values of climatic data, such as temperature and humidity, from representative climatic data for the city in which the Proposed Design is to be located. For cities or urban regions with several climate data entries, and for locations where weather data are not available, the designer shall
select available weather data that best represent the climate at the construction site.
Compliance Calculations
The Proposed Design and Standard Design shall be calculated using the following:
a) Same simulation program,
b) Same weather data, and
c) Identical building operation assumptions (thermostat set points, schedules, equipment and occupant loads, etc.) unless an exception is allowed by this Code or the authority having jurisdiction for a given category.