There are three main categories of arcs in PV installations:
a) Series arc resulting from faulty connection or series break in d.c. wiring;
b) Parallel arc resulting from short circuit between adjacent d.c. wiring at different potentials; and
c) Arc to earth resulting from failure of insulation.
In order to prevent arcing, every device without on-load breaking capacity (for example, MC4 connectors, d.c. fuse holders, SPD holders etc.) that could be used to open a d.c. circuit shall be secured against inadvertent or unauthorized operation.
Arc fault protection is recommended to protect d.c. side of PV system from failure in connectivity of any component in d.c. PV circuit, circuit conductor or interconnection. d.c. arcing generated in absence of arc fault protection poses potential risk of a fire incidence.
Arc fault protection is recommended in PV systems in buildings operating at system voltage between any two conductors on d.c. side > 100 V d.c. The purpose of arc fault protection equipment is to accurately detect and discriminate arcs in PV arrays and interrupt the arcs.
8.12 Rapid Shutdown Protection
d.c. PV circuits are live with d.c. voltages up to 1 000 Vd.c. (open circuit voltage) even when disconnected from PCE/inverter and are significant electric shock hazards in an emergency situation.
745
Rapid shutdown protection that disconnects PV array outputs recommended for PV arrays installed on rooftops to reduce electric shock hazards for fire fighters and other emergency workers.