5.1 Cases where omission of devices for overcurrent protection shall be considered for safety reasons or for circuits supplying current-using equipment where unexpected disconnection of the circuit could cause danger or damage. Examples as under:
a) exciter circuits of rotating machines;
b) supply circuits of lifting magnets;
c) secondary circuits of current transformers;
d) circuits which supply fire extinguishing devices;
e) circuits supplying safety services (burglar alarm, gas alarms, etc.); and
f) Certain measuring circuits, signalling, telecommunication, control and similar.
NOTE —In such cases, consideration should be given to the provision of an overload alarm.
5.2 Omission of protective device shall be permitted at the origin of an installation where the distributor provides an overcurrent device and agrees that it affords protection between the origin and the main distribution point of the installation where further overcurrent protection is provided.
5.3 For considering omission of short circuit protection as per 4.7.2 and 4.7.3 the wiring installation shall be in such a way to reduce the risk of short-circuit to a minimum and wiring is not placed close to combustible material.
5.4 For conductor not likely to carry overload current, overload protection shall be omitted provided that this conductor is protected against short-circuit.
179
5.5 In IT systems without a neutral conductor, the overload protective device may be omitted in one of the phase conductors if a RCD is installed in each circuit.
5.6 Alternative position or omission of devices for protection against overload are not applicable to IT systems unless each circuit not protected against overload is protected by RCD for each circuit or by permanently supervised systems only use of insulation monitoring which either disconnect the circuit for the first fault or gives a signal indicating a fault.