Heavy duty batteries may be 12 V/24 V of required Ah rating depending on the capacity of Gen-set, connectivity to control circuitry, model of respective manufacturer. Batteries shall be suitable to operate under respective ambient temperature. Connections shall be made with the class 5 copper cables of 35/50/70 mm2 or as per required size and type to restrict voltage drop within 8 percent of nominal battery voltage during cranking. Generally, 1.25 m length is considered. But depending on length to restrict voltage drop size may be increased. Ensure polarity before making connections. Use adequate lugs. Protocols in respect of initial and routine charging shall be followed. For AMF applications static battery charger working on mains supply may be necessary to keep batteries charged at all the times, to respond mains failure instantly. Location of batteries shall be at cool place and on stands.