Explosive gas atmosphere is the atmosphere where mixture with air, under atmospheric conditions, of flammable substances in the form of gas or vapour, which, after ignition, permits self-sustaining flame propagation. Area in which an explosive gas atmosphere is present, or may be expected to be present, in quantities, such as to require special precautions for the construction, installation and use of equipment is referred as a hazardous area and has to be treated in a special manner from the point of the design of electrical installation.
Many liquids, gases and vapours which in industry are generated, processed, handled and stored are combustible. When ignited, these may burn readily and with considerable explosive force when mixed with air in the appropriate proportions. With regard to electrical installations, essential ignition sources include arcs, sparks or hot surfaces, produced either in normal operation or under specified fault conditions.
This Part 7 of the Code is intended to provide guidelines for electrical installations and equipment in locations where a hazardous atmosphere is likely to be present, with a view to maximizing electrical safety. The scope of this Part therefore includes installations in hazardous areas such a petroleum refineries and petrochemical and chemical industries. The requirements laid down herein are in addition to those specified in Part 4 of this Code.
It is recognized that when electrical equipment is to be installed in or near a hazardous area, it is frequently possible, by taking care in the layout of the installation, to locate much of the equipment in less hazardous or non-hazardous areas and thus reduce the amount of special equipment required.
NOTE — Hazardous areas can be limited in extent by construction measures, that is, walls or dams. Ventilation or application of protective gas will reduce the probability of the presence of explosive gas atmosphere so that areas of greater hazard can be transformed to areas of lesser hazard or to non-hazardous areas.
This Part includes generalized statements and recommendations on matters on which there are diverse opinions. It is, therefore, important that sound engineering judgment should be exercised while applying these guidelines.