The provisions of IS/IEC 62305 (Part 1, Part 2, Part 3 and Part 4) shall apply. General principles of LPS shall comply with IS/IEC 62305-1.
If the physical characteristics of the building change significantly due to the installation of the PV array, it is recommended that the need for a lightning protection system be assessed in accordance with IS/IEC 62305-2 and, if required, it shall be installed in compliance with IS/IEC 62305-3. If LPS is already installed on the building, the PV system shall be integrated into the LPS as appropriate in accordance with IS/IEC 62305-3. The lightning protection of electrical and electronic equipment installed in PV system shall comply with IS/IEC 62305-4. Air termination not confirming as per protection angle/mesh/rolling sphere methods in IS/IEC 62305-3 shall be disregarded.
Large PV systems shall have a dedicated lightning protection system designed according to IS/IEC 62305. The existing lightning protection of a building shall be used, provided it adequately protects the PV installation and is assured of functioning throughout the life of the PV system.
LPS shall be tested according to IEC 62561-1 for minimum LPL III.In all instances where LPS is required or no LPS is required for PV array installed on a building rooftop or in case of a free-standing array, overvoltage protection shall be required to protect the array and the inverter and all parts of the installation.