4.1 PV Module
Crystalline silicon PV modules design qualification and type approval shall comply with IS 14286 (Part 1/Sec 1). IS 14286 outlines procedures for sampling, marking and testing of mono-and multi-crystalline silicon PV modules and test schedules of visual inspection, maximum power determination, insulation test, measurement of temperature coefficients, environmental tests etc.
Thin film PV modules design qualification and type approval shall comply with IS 14286 (Part 1/Sec 1), IS 14286 (Part 1/Sec 2), IS 14286 (Part 1/Sec 3) and IS 14286 (Part 1/Sec 4) outlines procedures for sampling, marking and testing of thin-film PV modules, such as amorphous silicon, cadmium telluride (CdTe), copper indium gallium selenide (CIGS), micro-morph and other thin film technologies.
Concentrator photovoltaic (CPV) modules and assemblies design qualification and type approval shall comply with IS 16228.
All PV modules safety qualification shall comply with IS/IEC 61730-1 requirements for construction and IS/IEC 61730-2 requirements for testing in order to provide safe electrical and mechanical operation during their expected lifetime.
Crystalline silicon PV modules shall comply with IS 17210 (Part 1)/IEC 62804-1 PID testing requirements for system voltage > 600 Vd.c.
PV modules shall comply with IS/IEC 61701 salt mist corrosion testing requirements as applicable based on site environmental conditions (recommended in coastal areas).
PV modules irradiance and temperature performance measurement and power rating shall comply with IS 16170/IEC 61853-1.
PV modules shall comply with IS 16664/IEC 62716 Ammonia (NH ) corrosion testing requirements as applicable based on site environmental conditions (dairies, toilets, mines etc.).
PV module package units shall comply with IEC 62759-1 requirements of transportation and shipping.
PV modules shall be tested for dust and sand exposure based on IS 9000 (Part 12)/IEC 60068-2-668 for high dust/sand geographical sites.
PV modules shall contain following clear indelible marking laminated inside the glass as per IS/IEC 61730-1.
a) Name, monogram or symbol of manufacturer;
b) Model number;
c) Unique serial number;
d) Nominal wattage ± 2 percent;
e) Year and country of origin; and
f) Brand name if applicable.
PV module may be RFID embedded inside module laminate and is recommended. RFID consists of following information.
a) Name of the manufacturer of PV module;
b) Name of the manufacturer of solar cells;
c) Month and year of the manufacture (separately for solar cells and module);
d) Country of origin (separately for solar cells and module);
e) I-V curve for the module;
f) Name of the test lab issuing IEC certificate;
g) Date and year of obtaining IEC PV module qualification certificates;
h) Peak wattage (Wp), Imp, Vmp and FF for the module;
j) Unique Serial No and Model No of the module; and
k) Other relevant information on traceability of solar cells and module as per ISO 9000 series.
4.1.1 PV Module Class
Class A (safety class II) modules shall be used for general applications where PV system voltage exceeds DVC-A limit of 50Vd.c. Class C (safety class III) modules shall be used for low voltage applications where PV system voltage is within DVC-A limit of 50V d.c. Class B modules shall not be used (Refer IS/IEC 61730-1).
Where the protective measure used on the d.c. side is double or reinforced insulation, PV modules shall be selected according to class II or equivalent insulation. Where the protective measure used on the d.c. side is extra low voltage by means of SELV or PELV, PV modules shall be selected according to class III or class II or equivalent insulation.
4.1.2 Junction Box
Junction Box combines all PV cell strings, and is attached at back surface of PV module and is hermetically sealed. It provides PV modules positive and negative conductor outputs 1.2 m long, 4 sq. mm copper cables as per IS 17293 recommended termination on male and female connectors respectively.
PV module junction box shall comply with IS/IEC 60529. Junction box material shall be thermo-plastic. Junction box shall have min. rating of IP65.
SP 30 : 2023
4.1.3 Bypass Diode
Bypass diodes are used to prevent PV modules from being reverse biased and consequent hot spot heating. These are normally installed in the junction box or embedded in PV module encapsulation.
Bypass diodes installed external to PV module or Junction Box shall comply with following requirements:
a) Voltage rating min. 2 × VOC MOD of the protected module;
b) Current rating of min. 1.4 × ISC MOD of the protected module;
c) Installed according to module manufacturer’s recommendations;
d) Installed such that no live parts are exposed; and
e) Protected from degradation due to environmental factors.
4.1.4 Blocking Diode
Blocking diodes are used to prevent reverse current in sections of a PV sub-array or array.
It is recommended not to use blocking diodes as a replacement of overcurrent protection in PV systems without batteries.
In systems with batteries, blocking diodes are recommended as one of the possible solutions to avoid reverse current leakage from the batteries into the array at night. The best practice recommendation is to incorporate blocking diode integral with charge controller.
Blocking diode shall comply with following requirements.
a) Voltage rating of minimum 2 × PV array maximum voltage determined in 5.8.1;
b) Current rating of minimum 1.4 times the short circuit current at STC of the protection circuit (string, sub-array or array);
c) Installed such that no live parts are exposed; and
d) Protected from degradation due to environmental factors.