6.1 Where a single protective device protects several conductors in parallel, there shall be no branch circuits or devices for isolation or switching in the parallel conductors. This sub-clause does not preclude the use of final ring circuits.
6.2 If parallel conductors shares equal currents the value of Iz is the sum of the Iz of the various conductors.
6.3 In case of unequal current sharing between parallel conductors overload protection for each conductor shall be considered individually.
NOTE — Currents in parallel conductors are considered to be unequal if the difference between any currents is more than 10 percent of the design current for each conductor.
6.4 For short circuit protection, if operation of a single protective device is not effective, then for two conductors in parallel, a short-circuit protective device shall be provided at the supply end of each parallel conductor or For more than two conductors in parallel, short-circuit protective devices shall be provided at the supply and load ends of each parallel conductor.
6.5 For busbar trunking systems complying with IS/IEC 61439-6 and powertrack complying with the IS 17345 (Part 1), one of the following requirements in Table 2 shall apply:
Table 2 Protection for Busbar Trunking or Powertrack System
(Clause 6.5)
| Busbar Trunking or Powertrack System | Condition | Protective Device |
|---|---|---|
| The rated short-time withstand current (ICW) | > | prospective short-circuit current (rms) |
| The rated peak withstand current | > | Prospective short-circuit current (peak) |
| The maximum time for the ICW | > | Maximum operating time of the protective device |
| The rated conditional short-circuit current | > | Prospective short-circuit current |