5.3 Selection and Erection of Equipment
Equipment shall be so selected that they suit the environmental conditions of use and shall be installed in such a way that their normal functioning is not affected by the external influences enumerated in 4.
5.3.1 It is recommended to protect final sub-circuits by residual current devices, the rated operating residual current not exceeding 30 mA and as low as practicable but avoiding nuisance tripping.
In agricultural or horticultural premises, electrical equipment shall have a minimum degree of protection of IP 44, when used under normal conditions. Where equipment of IP 44 rating is not available, it shall be placed in an enclosure complying with IP 44.
Socket-outlets shall be installed in a position where they are unlikely to come into contact with combustible material. Where there are conditions of external influences >AD4, >AE3 and/or >AG1, socket outlets shall be provided with the appropriate protection.
Protection may also be provided by the use of additional enclosures or by installation in building recesses.
These requirements do not apply to residential locations, offices, shops and locations with similar external influences belonging to agricultural and horticultural premises where, for socket-outlets IEC 60884-1 applies.
Where corrosive substances are present for example, in dairies, byres, the electrical equipment shall be adequately protected.
5.3.2 Selection and Erection of Electrical Equipment
Earthing arrangements, protective conductors and protective bonding conductors
5.3.3 Protective Bonding Conductors (Equipotential Bonding Conductors)
5.3.4 Protective Bonding Conductors for Supplementary Bonding
Protective (equipotential) bonding conductors shall be protected against mechanical damage and corrosion, and shall be selected to avoid electrolytic effects.
For example, the following may be used:
a) hot-dip galvanized steel strip with a dimension of at least 30 mm × 3 mm,
b) hot-dip galvanized round steel with at least 8 mm diameter,
c) copper conductor having a minimum cross-sectional area of 4 mm2, and
d) copper coated steel conductor with at least 6 mm diameter.
Other suitable materials may be used.
5.3.5 Selection and Erection of Electrical Equipment – Other Equipment
5.3.5.1 Socket-outlets
Socket-outlets of agricultural and horticultural premises shall comply with:
a) IS/IEC 60309-1,
b) IS/IEC 60309-2 when interchangeability is required, or
c) relevant national standards provided the rated current does not exceed 20 A.
5.3.6 Safety Services
5.3.6.1 Automatic life support for high density livestock rearing
For high density livestock rearing, systems operating for the life support of livestock shall be taken into account as follows:
a) Where the supply of food, water, air and/or lighting to livestock is not ensured in the event of power supply failure, a secure source of supply shall be provided, such as an alternative or back-up supply (see also 5.5.2 of IS 732). For the supply of ventilation and lighting units separate final circuits shall be provided. Such circuits shall only supply electrical equipment necessary for the operation of the ventilation and lighting.
b) Discrimination of the main circuits supplying the ventilation shall be ensured in case of any overcurrent and/or short-circuit to earth.
c) Where electrically powered ventilation is necessary in an installation one of the following shall be provided:
- A stand-by electrical source ensuring sufficient supply for ventilation equipment; or
NOTE — For the functional efficiency, a notice should be placed adjacent to the stand-by electrical source, indicating that it should be tested periodically according to the manufacturer’s instruction.
- Temperature and supply voltage monitoring. This can be achieved by one or more monitoring devices. The device(s) shall release a visible or audible signal that can be readily observed by the user and shall operate independently from the normal supply.
NOTES
1 Consideration should be given to legal requirements for the keeping of livestock.
2 The reliability of the installation for ventilation will be increased if, for this purpose, separate supply circuits are erected downstream from the main distribution board.
5.3.7 Luminaires and Lighting Installations
Luminaires shall comply with the IEC 60598 or IS 10322 series and be selected regarding their degree of protection and surface temperature according to the conditions of the surrounding areas and the places of installation (for example, IP 54, suitable temperature marking for mounting on combustible material).
In areas where a fire risk and a danger from a combustible coating of dust exist, only luminaires marked in accordance with IEC 60598-2-24, luminaires with limited surface temperature, shall be used.
Luminaires marked shall only be installed if the luminaire containing the lamps are in compliance with the degree of protection IP 54.
Luminaires shall be mounted at places where a sufficiently large distance from combustible materials is ensured taking into account the storage of goods and other dangerous work processes.
NOTE S f ty di t gi i th f t ‘ i t ti f ti g. F th , f i d 4.3.2 f IS 732. — a e s ances are ven n e manu ac urer s ns ruc ons or moun n ur ermore re erence s ma e o
The switched conditions (on or off) of luminaires installed in hay or straw storage places or similar locations, shall either be recognizable at the location of the switch or indicated there by a visible signal.