Swimming pools and fountains can be classified based on the extent of activity involved and the locations they are situated in. They generally utilise electricity for their functioning. The combination of water and electricity can create dangerous and unintended paths of electrical current. Depending on the amount of current, the duration of exposure, and the current path through the body, electrical exposures can result in a broad range of injuries, from minor tingling to severe burns or death.
This section shall cover the requirements for construction and installation of electrical wiring, and other equipment that could be used in swimming pools and fountains.
For the purpose of this part of NEC Part 3 Section 3, the requirements of IS 732 : 2019 and shall apply. This Part 3/Sec 3 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3/Sec 3 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The particular requirements of this section of NEC apply to electrical installations of:
a) basins of swimming pools and paddling pools and their surrounding zones;
b) areas in natural waters, lakes in gravel pits and coastal and similar areas, specially intended to be occupied by persons for swimming, paddling and similar purposes, and their surrounding zones. Such areas in natural waters, lakes in gravel pits and coastal and similar areas, are considered as swimming pools;
c) basins of fountains and their surrounding zones.
NOTE — In these areas, in normal use, the effect of an electric shock is increased by a reduction in body resistance and contact of the body with earth potential.
For swimming pools for medical use, special requirements may apply.
This standard does not cover the use of mobile equipment, e.g. pool cleaning equipment.
2 REFERENCES
IS/IEC No.
Title
IEC 60364-7-702 : 2010 Low-voltage electrical installations — Requirements for special installations or locations — Swimming pools and fountains
IEC 60335-2-41 Household and similar electrical appliances — Safety — Part 2-41: Particular requirements for pumps
732 : 2019 Code of practice for electrical wiring installations
IS/IEC 60529 : 1989 Degrees of protection provided by enclosures (IP Code)
16205 (Part 1) : 2017 Conduit systems for cable management: Part 1 General requirements
IS/IEC No.
IEC 60245 (all parts) Rubber insulated cables — Rated voltages up to and including 450/750 V
IEC 60598-2-18 Luminaires — Part 2: Particular requirements — Section 18: Luminaires for swimming pools and similar applications
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
3.1 Fountain — Arrangement, typically for decorative purposes, where water issues from a source and fills a basin of some kind.
3.2 Basin of Fountain — Part of the fountain which collects discharged water.
3.3 Swimming Pool — Water basin designed for purposes such as swimming, diving, etc and not for personal cleaning activity.
3.4 Paddling Pool — Water basin with low water level, e.g. for playing or wading.
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.5 Assessment of general characteristics
4.1.5.5.101 General
Add the following:
The requirements of this part are based on the dimensions of three zones, zone 0, zone 1 and zone 2 as described in 4.1.5.5.102 to 4.1.5.5.104 (see Fig. A-1 to A-4).
For electrical equipment in parts of walls, floors or ceilings limiting the zones specified in 4.1.5.5.102 to 4.1.5.5.104 but being part of the surface of that wall, floor or ceiling, the same requirements that apply for the zone limited by the surface shall be fulfilled unless specific requirements exist (see 5.5).
The width of zone 1 or zone 2 may be reduced by fixed partitions having a minimum height of 2.5 m.
The requirements for swimming pools also apply to paddling pools.
For basins of fountains which are intended to be occupied by persons, the specifications, and requirements for zone 0 and zone 1 for swimming pools apply.
NOTES
1 Fixed partitions are fixed separating walls, walls including windows and doors. The zones are also limited by ceilings, slopes of roofs and floors. Fixed partitions that are lower than 2.5 m are only limiting if they end at a ceiling or slope of a roof.
2 When a fixed partition is erected inside a zone, its effects on the zone are illustrated in Fig. A-3.
3 For the installation of a prefabricated swimming pool, the requirements of this standard are applicable.
4 Annex A provides some examples of the zones.
4.1.5.5.102 Description of zone 0
This zone comprises
a) the interior of basins, including any recesses in their walls or floors,
b) the interior of basins for foot cleaning, and
c) the interior of waterjets or waterfalls, and the space below them (see Fig. A-4).
NOTE — If the zone cannot be precisely determined under waterjets or waterfalls, it is recommended to take the vertical plane from the rim of the basin as the horizontal limitation of the zone and the maximum height of the water jet or waterfall as the limitation of height.
4.1.5.5.103 Description of zone 1
This zone is limited by
a) the zone 0 boundaries,
b) a vertical plane 2 m from the rim of the basin,
NATIONAL ELECTRICAL CODE OF INDIA
c) the floor or surface expected to be occupied by persons, and
SP 30 : 2023
d) the horizontal plane 2.5 m above the floor or the surface expected to be occupied by persons.
NOTE — Inaccessible equipment installed in an enclosure below the surface of a floor or wall or above a ceiling is not considered to be within zone 1 (see 5.5.5.101.3).
Where the swimming pool contains diving structures, starting blocks, chutes or other components expected to be occupied or accessible by persons, zone 1 also comprises the zone limited by
a) a vertical plane situated 1.5 m around the diving boards, springboards, starting blocks, chutes and other components such as accessible sculptures and decorative basins,
b) the horizontal plane 2.5 m above the highest surface expected to be occupied by persons.
4.1.5.5.104 Description of zone 2
This zone is limited by:
a) the vertical plane external to zone 1 and a parallel plane 1.5 m from the former,
b) the floor or surface expected to be occupied by persons, and
c) the horizontal plane 2.5 m above the floor or surface expected to be occupied by persons.
There is no zone 2 for fountains.
NOTE — Inaccessible equipment installed in an enclosure below the surface of a floor or wall or above a ceiling is not considered to be within zone 2 (see 5.5.5.101.3).