b) in any position where access to it may be impeded by livestock.
5.2.2 Where an installation serves more than one building, it shall be possible to isolate and control the buildings individually.
5.2.3 Means of access to all live parts of switchgear and other fixed live parts where different nominal voltages exist shall be marked to indicate the voltages present.
5.2.4 Cables
5.2.4.1 All cables shall be placed out of reach of livestock and clear of all vehicular movement.
5.2.4.2 Where additional protection against mechanical damage to cables is required, it shall, wherever possible, be provided by the use of non-metallic materials.
5.2.4.3 Where long runs of cable must be placed along the sides of buildings, they shall wherever possible be placed on the outside of the buildings, and as high as practicable.
5.2.4.4 Where conductors or cables are carried overhead supported by buildings or by poles, the minimum height above ground shall be 6 m.
5.2.4.5 Cable couplers shall not be used in agricultural premises.
In locations accessible to, and enclosing, livestock wiring systems shall be erected so that they are inaccessible to livestock or suitably protected against mechanical damage.
Overhead lines shall be insulated.
In areas of agricultural premises, where vehicles and mobile agricultural machines are operated, the following methods of installation shall be applied:
a) Cables to be buried in the ground at a depth of at least 0.6 m with added mechanical protection;
NOTE — Where conduits are used as additional protection, they should provide a degree of protection against compression of 450 N and a normal degree of protection against impact according to IS 16205 (Part 24).
SP 30 : 2023
b) Cables in arable or cultivated ground to be buried at a depth of at least 1 m; and
c) Self-supporting suspension cables to be installed at a height of at least 6 m.
NOTE — Cables buried in the ground is the preferred method of installation.
5.2.4.6 Wiring systems supplying main distribution boards at the origin of the electrical installation, if not protected by RCDs, shall be protected against mechanical damage, for example, buried in the soil or installed in separated enclosed cable trunking or ducting systems.
This requirement shall also apply to residences and other locations belonging to agricultural or horticultural premises.
5.2.4.7 Special attention shall be given to the presence of different kinds of fauna, for example, mice and rats.
5.2.4.8 Conduits, ducts and trunking systems
For locations where livestock is kept, external influences shall be classified AF4, and conduits shall have protection against corrosion of at least Class 2 (medium) for indoor use and Class 4 (high protection) outdoor according to IS 16205 (Part 21).
For locations where the wiring system may be exposed to impact and mechanical shock due to vehicles and mobile agricultural machines etc., the external influences shall be classified AG3:
a) conduits shall have a degree of protection against compression of at least Class 4 (heavy) according to IS 16205 (Part 21);
b) cable trunking and ducting system shall provide a heavy degree of protection against impact according to IS 14927 (Part 2).