Industry by definition includes manufacturing, processing, service sectors under which IT sector is also considered as Industry. However, for the purpose of this section industry basically include any building or part of building or structure, in which products or materials of all kinds and properties are stored, fabricated, assembled, manufactured or processes. For example, assembly plants, laboratories, dry cleaning plants, pumping stations, refineries, dairies, saw mills, chemical plants, workshops, distilleries, steel plants, etc.
Industrial installations are of various types. Single industrial site may comprise electrical loads of varying types and requirements. Classification of Industries is based on three criteria as given in 4.1 to 4.3.
4.1 Classification Based on Fire Safety
4.1.1 Industrial buildings are classified into Group G from the fire safety point of view in SP 7. Buildings under Group G are further subdivided as follows:
a) Subdivision G-1 — Buildings used for low hazard industries — Includes any building in which the contents are of such low combustibility and the industrial processes or operations conducted therein are of such a nature that there are no possibilities for any self-propagating fire to occur and the only consequent danger to life and property may arise from panic, fumes or smoke, or fire from some external source.
b) Subdivision G-2 — Buildings used for moderate hazard industries — Includes any building in which the contents or industrial processes of operations conducted therein are liable to give rise to a fire which will burn with moderate rapidity and give off a considerable volume of smoke but from which neither toxic fumes nor explosions are to be feared in the event of fire.
c) Subdivision G-3 — Buildings used for high hazard industries — Includes any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with extreme rapidity or from which poisonous fumes or explosions are to be feared in the event of fire.
NOTE — SP 7 includes Group J buildings for such location where storage, handling, manufacture or processing of highly combustible or explosive materials or products are being carried out. Such installations including such high hazard locations in Group G classification shall comply with the special rules of Part 7 of the Code.
SP 30 : 2023
4.1.2 Typical list of industries for different class of fire hazard are given in Annex B.
4.2 Classification Based on Power Consumption
Industrial buildings may also be classified depending on the quantum of electric power requirements for its services as given in Table 1.
Loads within the industrial site could be divided depending on their nature and size. For guidance, the classification given in Table 2 shall be referred to.
4.3 Classification Based on Pollution
For the propose of evaluating creepage distances and clearances, the following four degrees of pollution in the micro-environment are established:
a) Pollution degree 1 — No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
b) Pollution degree 2 — only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected.
c) Pollution degree 3 — Conductive pollution occurs, or dry non-conductive pollution occurs which becomes conductive due to condensation — which is to be expected.
d) Pollution degree 4 — Continuous conductivity occurs due to conductive dust, rain or other wet conditions.
1 Clearances and creepage distances according to the different pollution degrees are given in Tables 13 and 15 of IS/IEC 60947-1. Unless otherwise stated by the relevant product standard, equipment for industrial applications is generally for use in pollution degree 3 environment. However, other pollution degrees may be considered to apply depending upon applications or the micro-environment.
a) The pollution degree of the micro-environment for the equipment may be influenced by installation in an enclosure. Means may be provided to reduce pollution at the insulation under consideration by effective use of enclosures, encapsulation or hermetic sealing. Such means to reduce pollution may not be effective when the equipment is subject to condensation or if, in normal operation, it generates pollutants itself.
b) Pollution will become conductive in the presence of humidity. Pollution caused by contaminated water, soot, metal or carbon dust is inherently conductive. Small clearances can be bridged completely by solid particles, dust and water and therefore minimum clearances are specified where pollution may be present in the micro-environment.
Table 1 Classification Based on Power Consumption
(Clause 4.2)
| Sl No. | Description¹⁾ | Average Power Requirement | Examples |
| (1) | (2) | (3) | (4) |
| i) | Light industries | Up to 50 kVA | Hosiery, tailoring and jewellery |
| ii) | Average industries | Above 50 kVA up to 2 000 kVA | Machinery, engine fitting, motor cars, aircraft, light pressings, furniture, pottery, glass, tobacco, electrical manufacturing and textile (see Note) |
| iii) | Heavy industries | Above 2 000 kVA | Heavy electrical equipment, rolling mills, structural steel works, tube making, foundries, locomotives, ship-building and repairing, chemical factories, factories for metal extraction from ores, etc. |