Part 3Low-voltage Electrical Installations — Requirements for Special Installations or Locations
This Part 3 of the code covers the requirements for electrical installations for special purposes and at special locations. It can also be classified as electrical installations in non-industrial buildings. The requirements for electrical installations in industrial buildings has been detailed in Part 4 of the code. While a majority of installations could be categorically classified as non- industrial, an industrial complex would necessarily incorporate sub-units such as offices, residential quarters and support services which are either housed or fall in the category of non-industrial buildings. The requirement stipulated in Part 3 and Part 4 of this Code would therefore require judicious application.
With the current trend in power utilization, it would also be extremely difficult to classify electrical installations based on power requirement or the voltage of supply, as large buildings for non-industrial purposes consume sufficient power to consider them at par with the consumption of light industrial establishments. It is therefore necessary to consider for initial assessment of the installation the guidelines given in Part 1/Sec 8 this Code, which are better defined than the earlier terminology used for classifying installations. Also, this part specifies the requirements for installations in certain special purposes like supplies for electrical vehicles and furniture that require special attention for safety and ease of usability.
Part 3 of this Code, therefore covers requirements for several types of special applications and non-industrial occupations. In case of typical occupancies that strictly fall into any of these, recourse shall be made to the general guidelines stipulated in Part 1.
This Part consists of the following Sections:
Section 1 Domestic dwellings
Section 2 Locations containing a bath or shower
Section 3 Swimming pools and fountains
Section 4 Rooms and cabins containing sauna heaters
Section 5 Construction and demolition site installations
Section 6 Conducting locations with restricted movement
Section 7 Caravan parks, camping parks and similar locations
Section 14 Electrical installations in caravans and motor caravans
Section 15 Supplies for electric vehicles
Section 16 Operating or maintenance gangways
Section 17 Temporary electrical installations for structures, amusement devices and booths at fairgrounds, amusement parks and circuses
Section 18 Heating cables and embedded heating systems
Section 19 Office building, shopping and commercial centres and institutions
Section 20 Hotels
Section 21 Sports buildings
Section 22 Specific requirements for electrical installations in multistoried buildings
Domestic Dwellings
This section will give guidelines particularly in respect of Electrical Installations in Domestic Dwellings. The portion in this section shall be read with Part 1 Section 9 Wiring Installations. The recommendations given here under are to call for specific attention primarily to provide safe electrical environment from the point of view of users having no age band, who are uninstructed, with whom one cannot expect to have any technical knowledge and capability to identify possible electrical threats/hazards. Another point to consider is designing layouts, selecting fittings in respect of lighting, ventilation, power outlets to suite needs of such users at home; not for any particular period of day like office hours but for round the clock, which will provide comfort, ease of operation and convenience.
2References
2.1 Statutory Provisions
Section 53 of Electricity Act, 2003 dealing with ‘Protecting Public from Dangers of Electricity’.
Central Electricity Authority (Measures related to Safety and Electric Supply) Regulations, 2010, with further amendments.
2.2 Standards
IS No.
4648 : 1968 Electrical layouts in residential buildings
3646 (Part 2) : 1966 Code of practice for interior illumination
15707 : 2006 Testing evaluation installation and maintenance of a.c. electricity meters
8061 : 1976 Code of practice for design, installation and maintenance of service lines up to and including 650 V
SP 7 : 2016 National Building Code
SP 72 : 2010 National Lighting Code
3Terminology
For the purpose of this section, the definitions given in Part 1/Sec 2 and Part1/Sec 9 of this Code shall apply.
4 GENERAL AND COMMON ASPECTS OF ARCHITECTURAL DESIGN, PLANNING AND CIVIL CONSTRUCTION WORK FROM THE PERSPECTIVE OF ELECTRICAL INSTALLATIONS AND CHARACTERISTICS
4.1 Civil and Architectural Aspects
The objective of this section is to highlight needs of required base of infrastructure, related to architectural and civil planning and coordination. To consider electrical needs, appointment of electrical consultant/contractor is necessary from planning stage, so that question of incorrigible mistakes will not arise. The important points to be considered are given below;
a) Routes and service entry points;
b) Electrical meter rooms;
SP 30 : 2023
c) Shafts/ducts;
d) Interior design;
e) Aesthetics and electrical safety;
f) Ceiling fans
g) Exhaust fans;
h) Fire rating;
j) Wall thickness;
k) Water leakages/seepages;
m) Bathrooms/washrooms; and
n) Earthing.
For details 4 of Part 1/Sec 9, shall be referred.
4.2 Environment
The following environmental factors shall apply to electrical installations in domestic dwellings:
Environment
Characteristics
Remarks
(1)
(2)
(3)
Presence of water
Probability of presence of water is negligible
-
Presence of foreign solid bodies
The quantity or nature of dust or foreign solid bodies is not significant
-
Presence of corrosive or polluting substances
The quantity and nature of corrosive or polluting substances is not significant
Applicable for most of the locations except for dwellings situated by sea or in industrial zone in which case categorization AF2 applies (see Part 1/Sec 8)
Mechanical stresses
Impact and vibration of low severity
Household and similar conditions
Seismic effect and lighting
Depends on the location of the building
4.3 Utilization
The following aspects utilization shall apply:
Utilization
Characteristics
Remarks
(1)
(2)
(3)
Capability of persons
Uninstructed persons
Applies to all domestic installations
Contact of persons
Persons in normally situations
Conditions of evacuation during emergency
Low density occupation, easy conditions of evacuation
Buildings of normal or low height used for one or two family dwellings
Low density occupation, difficult conditions of evacuation
Apartment houses including high-rise flats
Nature of processed of stored material
No significant risks
5Electrical Design, Installation
5.1 General
Electrical design, layouts and installation shall be done keeping following points in mind on the basis of priority.
a) Safety;
b) Functionality;
c) Ease of operation; and
d) Aesthetics.
While designing layouts sustainability under respective environment, situation from the point of view of domestic installations is important, e.g. distance/clearing to be maintained between heat generating appliances in kitchen. Another point is requirements of user and perspective of architect in respect of electrical fixtures and appliances. Electrical consultant or contractor has to provide wiring installation to suit these requirements within the framework of codes and safety norms, hence role of electrical contractor/consultant begins from initial planning stage.
5.2Electrical Contractor, Consultant
5.2.1 Appointment
To avoid conflicts between electrical and civil work, aesthetics and electrical safety norms, ascertain related provisions of spaces, constructional requirements, avoid last time corrective measures/adjustments (which sometimes may turn out to be impossible to correct), appointment of chartered electrical safety engineer/licensed electrical contractor is necessary from initial stage. Under the circumstances of any conflict between civil and electrical work, it shall be seen that the problem gets resolved under mutual agreement without compromising safety.
5.2.2 Flawless Design
User/occupant being uninstructed person and not expected to have technical knowledge, is not allowed by law to interfere with electrical installation. Under urgency and in absence/unavailability of electrician user shall not attempt to resolve problem. This situation may arise due to frequent trouble arising out of defective installation. Therefore, it is important point to have sufficient experience specific to such type of installations to the electrical designer/consultant, so that the electrical installation will be safe and trouble free.
5.3 Wiring Systems
Wiring systems have been given under 5.3 of Part 1/Sec 9. Broadly wiring may either be surface type or concealed. Point to note here is in surface wiring it is easy to make and accommodate after thought changes. In case of concealed type wiring since the subsequent changes are difficult, involve breakages, likely to contradict predetermined values of load on circuits; prior decision or anticipations in respect of interior layout is very important.
5.4Material and Selection
Material shall conform IS specifications and certified accordingly. Selected material shall be sustainable under the situation and possible external influences as mentioned under 5.4 of Part 1/Sec 9.
5.4.1 Cables
It is recommended to use FRLSH/HFFR grade copper cables for internal wiring installation. Size of wires shall be selected correlating to current carrying capacity as per situation (see 5.5 of Part 1/Sec 9) and shall not be less than that recommended under Table 1. The current carrying capacity shall be net after considering all de-rating factors, for example, maximum allowable voltage drop (see 5.7 of Part 1/Sec 9).
NOTES
1 It shall be noted that there is vast difference in current carrying capacity of conductor of same size, depending situation, reference method of installation (see 5.5.2 of Part 1/Sec 9); which may reduce the capacity to 50 percent. So size shall be carefully selected.
2 Class 1/2 conductor shall preferably be used for fixed wirings.
5.4.2 Wire Enclosures - conduits/Trunking
For surface type wiring, conduits or trunking (also known as casing and capping) may be used. However, trunking shall not be used where it is likely to be get concealed including areas above false ceiling. For concealed wiring selection of metal/non-metal PVC conduits shall be made depending on situation. PVC trunking or conduits shall be FR grade and conduits shall have High Mechanical Strength (HMS) or at least Medium Mechanical Strength
(MMS). Metal conduits shall be selected where mechanical damages are likely to occur, for example, places may to get infected with rodents like voids/areas above false ceiling. Size shall be so selected that after drawing of wires 50 percent area will remain free. (for details see clause 5.9 from Part 1/Sec 9).
5.4.3 Accessories and Boxes
There is wide scope to select accessories to suite aesthetic needs. But selection shall be done considering sustainability under respective environment and class of user. Delicate, press-fit type accessories may not survive under rough use. Boxes may be metallic or non-metallic for metal conduits preference shall be given to metal boxes. Non-metal boxes shall be FR grade. Plug sockets if positioned below 1.2 m from floor level, shall be shuttered type only.
5.4.4 Fittings/Fixtures/Appliances
Lighting fixtures shall be capable to give desired lumen output, suite functional requirements and human comfort in respect of CCT, CRI and glair index. Preference shall be given to BEE star rated fittings. Heat dissipation factor shall also be considered with respect to location/base on which fitting is to be installed.
5.5Installation
5.5.1 Wire Enclosures and Routing
Routing of conduits/trunking shall be near and parallel to the edges of wall. Considering single phase distribution, separate enclosure shall be used for each phase (in case of three phase supply). Also, other wire enclosures of extra low voltage systems, for example, telephone, data, sound system, CCTV, control cables of automation, shall be separate with adequate spacing in between. In kitchens, from the point of view of safety, routes shall not conflict with gas pipelines/heat generating devices.
NOTE — For concealed type wiring work must be planned and coordinated with the activities of civil work.
5.5.2 Switch-boards
Followings points shall be noted in respect of switch-boards for general lighting, switch-boards for power outlets, and special purpose switch-boards.
NOTE — Locations of switch-boards have been recommended in general, however additional safety and accessibility must be considered from the point of view of children and disabled persons.
5.5.2.1 Switch boards-lighting
Location of general light and fan switch boards shall be positioned close to door frame and on opposite side of hinged edge of door, so that a person while entering can have immediate access to switch board. If a room has two doors; lighting control shall be provided on switch boards located near both doors. For the purpose use of two way switches may be made. General height shall be reachable and 1.2 m above ground level.
NOTE — It is recommended to provide a onboard 6A plug socket outlet on every lighting switchboard which insures availability of neutral and earth, which is required when additional board/extension is needed in future, which is possible if within limit of allowable loadcpoints on that circuit.
5.5.2.2 Switch boards – power outlets
Plug outlet boards for shall be located as near as possible from the position/proposed/anticipated location of appliance to avoid mess of loose hanging/suspended cords. If position of switch-board is above top of table/platform; it shall be 150 mm above the surface of table/platform top. Plug outlets if required at lower level shall be 200 mm above finished floor level and such plug sockets must be shuttered type. For wall mounted a.c. units suitable height may be above lintel level.
5.5.2.3 Switch boards – specific to utility area
Following additional points may be considered in respect of switchboard installation depending use of room/area.
a) Hall/living room — Additional switchboard may be provided adjacent to and accessible from sitting location for particular light/fan/plug outlet/charging point.
b) Kitchen — Location of power outlets shall be above working platform adjacent to the actual/anticipated position of appliance and shall not be behind the appliance. Special care shall be taken in respect of heat generating devices to maintain safe distance.
c) Bedrooms — Switchboards with two way controls for light fan shall be provided adjacent to bed location but not behind head position and shall be accessible from both ends of double bed. There shall be points for night
lamp/path light, reading lights and plug outlet for mobile phone/laptop charging. A switchboard shall also be provided near dressing mirror for light and plug outlets portable appliances like hair dryer.
d) Passages/staircase — Location shall be at entry/start point. Switchboards with two way control may be provided at both ends depending on distance/convenience.
e) Terrace/balcony — If sitting arrangement is considered plug outlets shall be provided adjacent to sitting area. Considering location of festive lamps/decoration, provisions of plug outlets at suitable location but safe from weather effects shall be made.
f) Wet areas - bathrooms/toilets — Boards shall be located away from area where there are chances of splashing of water. Preference shall be given to provide a switchboard immediate outside the door so that switch can be operated before entering and at the time of leaving, considering difficultly in locating switchboard in dark. Switchboard for mirror light above washbasin and plug outlet for appliance like electric razor shall be adjacent to mirror.
5.5.3 Distribution
Proper distribution is the basis of safe and trouble free electrical installation. Following guidelines will help to design the distribution.
5.5.3.1 Circuits for lighting load
Lighting load comprising lights, fans, 6A plug on boards shall be separated from power load. There shall be an independent lighting circuit for:
a) Each room, access of which is controlled by door (attached balcony/terrace may be included within the circuit of room);
b) Common areas, for example, passages, verandah;
c) Toilets; and
d) External lighting.
NOTE — Maximum points on any lighting circuit shall not exceed 24 or load shall not exceed 1 000 W. Provision of separate circuit shall be done if the load exceeds. Refer 5.6 for consideration of load.
5.5.3.2 Circuits for power load
There shall be independent circuit for:
a) Air-conditioner;
b) Water heater;
c) Oven/cooking range having load 2k W or above;
d) Washing machine/dishwasher having load 2k W or above; and
e) EV charging.
Maximum points of 16A shall not exceed 2 or load shall not exceed 3000 W on each circuit. Provision of separate circuit shall be done if the load exceeds.
5.5.3.3 Circuits for Inverter/UPS used as standby electrical supply
There shall be a separate circuit(s) comprising phase and neutral for the points to be provided on the supply from Inverter/UPS. Depending on load provision of separate DB may be necessary. Colour coding of such wires shall be brown/grey to identify the circuits easily. Neutral of such circuits shall not be looped anywhere with the points/circuits having no backup of inverter/UPS supply.
5.5.3.4 Cables-size
In domestic dwellings there are more occasions requiring additions and alterations in existing wiring installation due to purchases of new gadgets, changes in interior layouts. This may involve extra loading on the cables. Anticipating this aspect, it is desirable to consider one size higher for cables. For guidance, following table may be referred for considering minimum cross section of conductor.
SP 30 : 2023
Table 1Recommended Minimum Nominal Cross-sectional Areas of Conductor (Clause 5.4.1)
Use
Size (2 + E) copper
Point wiring for light/fan/bell/independent plug 6A
1.5 mm<sup>2</sup>
Branch circuit (DB to switch board) limited to total 10 points/800W
5.5.4 Point Wiring-lighting
5.5.4.1 Recommended values of illumination
Table 2 gives recommended values of illumination level. For further details refer SP 72 National Lighting Code.
5.5.4.2 Recommended points
Table 3 below shows recommended points on the basis of minimum functional requirement related to use and utility of the area. Actual requirement may vary to higher side.
Table 2Recommended Levels of Illumination for Different Parts of Domestic Dwellings (Clause 5.5.4.1)
Sl No.
Location
Illumination Level lux
(1)
(2)
(3)
i)
Entrances, hallways
100
ii)
Living room
300
iii)
Dining room
150
iv)
Bedroom: a) General b) Dressing tables, bed heads
300200
v)
Games or recreation room
100
vi)
Table games
300
vii)
Kitchen
200
viii)
Kitchen sink
300
ix)
Laundry
200
x)
Bathroom
100
xi)
Bathroom mirror
300
xii)
Sewing
700
xiii)
Workshop
200
xiv)
Stairs
100
xv)
Garage
70
xvi)
Study
300
413
Table 3Minimum Recommended Points as per Functional Requirement (Clause 5.5.4.2)
Portion of Dwelling Unit
Light Point Per 10-12 m<sup>2</sup> or Part
Fan/ex Fan Point Per 10-12 m<sup>2</sup> or Part
Bell Point Cable TV Telephone
Hall/Living room
2
1
1 1*
kitchen/dining
2
1 + 1
Bed room
4
5.5.5 Points – power Outlets 6A/16A/25A
With the increasing use of domestic gadgets sufficient number of power points shall be provided considering future requirement. This provision at initial stage helps proper sizing of cables and protections, which at later stage often raise problems of undesirable overloading to which existing wiring installation is not designed.
Table 4Recommended Power Outlets Depending on Anticipated Use of Appliance (Clause 5.5.5)
Portion of Dwelling Unit
6A Power Outlet Per 10-12 m² Or Part
6/16A Power Outlet Per 10-12 m² or Part
20/25 A Power Outlet
Hall/Living room
6a
1b
kitchen/dining
2c
4d
Bed room
6e
1f
1g
bath/toilet
1h
1i
passage/verandah
1j
balcony/terrace
1j
Entrance
1j
servant room/garage
2j
1j
Dry balcony or available space
1k
a TV, set top box, music system/DVD, mobile charging, movable/portable gadgets
b General purpose, vacuum cleaner, room heater
c Water purifier, general purpose- small mixer
d Fridge, microwave/OTG, induction, mixer/grinder
e Two bedside tables, TV, Set top box, computer, printer
f General purpose- room heater
g A.C.
h General purpose-shaver/drier
i Water heater
j Festive lighting/general purpose
5.6Load Consideration
For electrical design consideration of total connected load and diversity is important. Load can either be decided as custom requirement or anticipated/assessed general requirement.
5.6.1 For custom requirements tables 5 and 6 may be used to consider load depending on point of utility.
Table 5 Determination of Load of Lighting Points(Clause 5.6.1)
Connected Device on the Outlet of Point Wiring
Load Consideration
Light point*
50 W
Fan point
75 W
Power outlet 6A
100 W
NOTES
1* Light point may be utilized for a conventional incandescent lamp/tube light with ballast or single/group of LED lighting fixtures.
2 Fan shall include all types/sweeps/exhaust.
3 If actual rating of appliance is known, it may be taken into consideration subject to envisaged changes.
Table 6Determination of Load on Power Points (Clause 5.6.1)
Commonly Connected Devices on the Outlet of Power Point
Load Consideration in W
Bathroom
Storage type water heater
2000
Instant hot water geyser
3000
Dry balcony
Washing Machine
2000
Dish washer
1500
Kitchen
Electric Hot Plate
2000
Induction hot plate
2000
Electric oven
2000
Microwave
2000
Mixer/grinder
500
Fridge
500
Toaster/kettle
800
Air fryer
1500
Kitchen exhaust hood
350
Other
A.C 1TR/1.5 TR/2 TR
1250/1500/2000
Room heater
1000
Computer
150
TV
100
Iron
800
5.6.2 When there is no custom requirement, load may be considered on the basis of watts per m2 of carpet area. For design purpose load for domestic dwellings may be considered as 75W/m2.
NOTE — Sometimes Supply Company may set parameters to consider load per unit area, while sanctioning. Under the circumstances higher value shall be considered.
5.7 Earthing
5.7.1 Important extracts of Mandatory Provisions under CEA Regulations :
Regulation 16
‘the supplier shall be provide and maintain on the consumer’s premises for the consumer’s use, a suitable earthed terminal in accessible position at or near the point of commencement of supply’.
Further proviso states:
‘provided that in case of installation of voltages exceeding 250 V the consumer shall, in addition to the afore mentioned earthing arrangement, provide his own earthing system with an independent electrode.’
Regulation 41
(x) no person shall make connection with earth by the aid of, nor shall he keep it.in contact with, any watermains not belonging to him except with the consent of the owner thereof and of the Electrical Inspector.
(xiv) all metal casing or metallic coverings containing or protecting any electric supply line or apparatus shall be connected with earth and shall be so joined and connected across all junction and other openings as to make good mechanical and electrical connection throughout their whole length:
Provided that conditions mentioned in this regulation shall not apply, where the supply voltage does not exceed 250 V and the apparatus consists of wall tubes or brackets, electroliers, switches, ceiling fans or other fittings, other than ,portable hand lamps and portable and transportable apparatus, unless provided with earth terminal and to class-II apparatus and appliances.
Provided further that where the supply voltage is not exceeding 250 V and, where the installations are either new or renovated, all plug sockets shall be of the three pin type, and the third pin shall be permanently and efficiently earthed.
415
Without prejudice to the above mandatory provision Owner shall get it verified periodically from the electrical agency that:
a) Connections with water or any other metallic line shall not be opted as earth connection.
b) All electrical appliances, fittings provided with earth terminal/3 pin plug are properly connected with earth.
c) Earthing is in good condition. And, wherever consumer has his/her own earth electrode it shall properly maintained and tested at least once in a year during summer value of which shall not exceed 2 ohms.
d) Under the multiple neutral earthing system, if suppliers neutral is earthed in consumer’s premises, consumer’s earth electrode shall maintain distance of at least 3 m. In case of multiple consumers, Earth Bus shall be of adequate capacity to which individual consumer’s earth conductor is connected. Such connections must be done with properly crimped lug duly tightened with nut bolt. Since copper conductor is recommended for wiring installations in domestic dwellings, preference may be given to copper earth electrode and bus to avoid contact related issues between different metals. Under unavoidable conditions bimetallic lug shall be used.
5.8 Fans, Light fittings, Appliances
5.8.1 Fans
Provision of ceiling, exhaust and other fans shall be done in accordance with 9.2 of Part 1/Sec 9 of this code.
5.8.2 Lighting Fixtures
Provision of lighting fixtures shall be done in accordance with 9.1 of Part 1/Sec 9 of this code. Recommended illumination level may also be referred from IS 4648.
5.8.3 Fixed and Portable Appliances
For appliances other than class II, proper connectivity to earth shall be checked. Connections shall be through shielded cord only. Heat generating appliances/parts shall be safely located and shall be provided with suitable thermostat.
5.9Service Connections, Meters
Safety issues and maintenance of electrical service line, meter, switchgears, etc; at the point of supply/in meter room are the matters of individual as well as joint concerns of owner of dwelling and supplier of electricity. Following points shall be noted in this regard.
5.9.1 Electrical Meter Rooms
Meter rooms shall be separate. It shall be planned to have sufficient head room and clear space in front of meters, control switches (at least 1m). Space on wall shall be sufficient to accommodate required number of meters at such height that readings can be taken without aid of any tackle. Also the switchgears shall be at least 0.5 m above floor level and within such height to have an easy access for operation. The meter room shall be well ventilated, protected from external influences like sun, rain, water seepages, entry of rodents. Location of meter room shall be suitably adjacent or nearest to cable duct/shaft/vertical route of mains.
5.9.2 Supplier’s Obligations
Regulation 13 and 14 of CEA Regulations gives mandate in respect of responsibilities of supplier and consumer as below:
‘13(1) The supplier shall ensure that all electric supply lines, wires, fittings and apparatus belonging to him or under his control, which are on a consumer’s premises, are in a safe-condition and in all respects fit for supplying electricity and the supplier shall take precautions to avoid danger arising on such premises from such supply lines, wires, fittings and apparatus’.
‘13(2) Service lines placed by the supplier on the premises of a consumer which are underground or which are accessible shall be so insulated and protected by the supplier as to be secured under all ordinary conditions against electrical, mechanical, chemical or other injury to the insulation,
14, Switchgear on consumer’s premises.- (1) The supplier shall provide a suitable switchgear in each conductor of every service line other than an earthed or earthed\ neutral conductor or the earthed external conductor of a concentric cable within a\ consumer’s premises, in an accessible position and such switchgear shall be contained within an adequately enclosed fire-proof receptacle:
Provided that where more than one consumer is supplied through a common service line, each such consumer shall be provided with an independent· switchgear at the point of rigid junction to the common service,
5.9.3 Owner’s Obligations
‘13(3) The consumer shall, as far as circumstances permit, take precautions for the safe custody of the equipment on his premises belonging to the supplier’. ‘The consumer shall also ensure that the installation under his control is maintained in a safe condition’.
6Testing and Handing Over
Before handing over installation to the owner for use, Electrical Contractor shall carryout tests and perform visual checks as per the guidelines given under 10 of Part 1/Sec 9. Handing over to the owner shall be done with proper documentation as given below.
6.1 Documents shall be Handed Over to Owner
Owner shall be provided with documents as listed below. These documents shall be kept for record and will be of importance when work of additions/alteration/modifications involves in future.
6.1.1 Electrical service connection details relating to sanctioned/connected load.
6.1.2 Copy of test report of the electrical installation given by electrical contractor.
6.1.3 Single line diagram of electrical installation.
6.1.4 Instructions/trouble shooting chart in respect with the use, limit of maximum load, operation, safety of Electrical Installation and precautions to be taken while making changes in existing installation.
6.1.5 Emergency contacts in respect with any possible problem with Electrical Installation.
SP 30 : 2023
6.1.6 Wiring details of the house showing the conduits, wires in each conduit with circuit identification, pull boxes, junction boxes, switchboxes, fittings, earthing wire routing, etc at their proper locations should also be handed over to facilitate easy tracing of wires in case required.
6.2 Documents to be Handed over to Society/Association/Building Committee of Owners
Following documents related with common electrical installation(s) shall be handed over.
6.2.1 Load sanctioned letter of electric supply company.
6.2.2 Electrical service connection details in respect of common energy meters sanctioned/connected load, security deposit paid.
6.2.3 Single line diagram from the tapping point of service cable to the point of supply (incoming terminal of consumers switch/MCB installed near energy meter.
6.2.4 Copy of test report of the electrical installation given by electrical contractor in respect of electrical installation connected on common meters.
6.2.5 Copies of the approvals/permissions/licenses received from the respective authority; instructions, liabilities and responsibilities;
INFORMATIVE NOTE — Under the set of documents, owner/stakeholders of domestic dwelling(s) are also required to possess following NOCs, permissions, licenses, instructions, liabilities, etc; which respective agency shall handover; some of which do not come under the scope of this section.
a) Generating set/s (CEA Reg. 32);
b) High-rise building (CEA Reg. 36);
c) HT installation (CEA Reg. 43); if installation is owned by consumer/s;
d) Lift/s (Rule 5, Mah. Lift Rules);
e) Warranties/Guarantees and initial AMCs of Lift/s, Generating set, UPS and batteries and also in respect of installation handed over to Supply Company etc. as per applicable;
f) Instructions in respect of maintenance and operation of water pump, Lift and handling emergency. Telephone numbers of emergency services;
g) List of liabilities, responsibilities to be undertaken:
Maintaining electrical installation (related to common facilities like lights, water pump, fire-fighting equipment), in good condition so as to cause no danger.
Renewing AMCs in respect of generating set, lifts after defect liability period. Due dates shall be given.
Safeguarding electrical installation belonging to supply company in the premises, for example, equipment in meter room.
Communicating electrical inspector within 24 h in respect of any electrical accident.
Any electrical related work to be got done only through license/permit holder person.
7Maintenance
Proper maintenance is a key to safety, trouble free use, operation and longevity. Even though installation is working smoothly, periodical testing/inspection from the authorized person/Chartered Electrical Safety Engineer is recommended. Periodicity of which shall preferably shall not be more than three years. In respect of portable appliances PAT (Portable Appliance Test) shall be performed (see 10.2.2 under Part 1 Section 9). RCD shall be tested every month with the push button provided on it, for confirmation of proper functioning.
Section 2 Locations Containing a Bath or Shower
The combination of water and electricity can create dangerous and unintended paths of electrical current. Depending on the amount of current, the duration of exposure, and the current path through the body, electrical exposures can result in a broad range of injuries, from minor tingling to severe burns or death.
This section shall cover the requirements for construction and installation of electrical wiring, and other equipment that could be used in locations containing a bath or shower.
For the purpose of this part of NEC Part 3/Sec 2, the requirements of IS 732 : 2019 and shall apply. This Part 3/Sec 2 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3/Sec 2 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The particular requirements of this section (Part 3/Sec 2) of NEC apply to electrical installations in indoor or outdoor locations where a bath tub and/or a shower is intended to be permanently placed in a specific location.
The extent of the location containing a bath tub and/or a shower is limited by:
a) the lowest finished floor level;
b) a horizontal plane 3 m above the lowest finished floor level;
c) a vertical circumscribing virtual surface at a distance of 4 m from the fixed water outlet for the bath tub or shower; and
d) the volume within the walls, floor and ceiling that border the location containing a bath or shower, measured to a depth of 6 cm.
NOTES
1 Where the shower head and flexible hose are detachable, the fixed water outlet is taken to be at the supply end of the flexible hose.
The requirements of this document also apply to fixed electrical installations in mobile applications, for example caravans, mobile homes, shower containers. This document does not apply to emergency facilities, for example emergency showers used in industrial areas or laboratories.
2 For locations containing a bath or shower for medical treatment, special requirements can be necessary.
3 For prefabricated bath and/or shower units, see also IEC 60335-2-105.
2 REFERENCES
IS/IEC Standard Title
732 : 2019 Code of practice for electrical wiring installations
IEC 60335-2-105 Household and similar electrical appliances — Safety — Part 2-105: Particular requirements for multifunctional shower cabinets
IEC 61558-2-5 Safety of transformers, reactors, power supply units and combinations thereof — Part 2-5: Particular requirements and test for transformer for shavers, power supply units for shavers and shaver supply units
302 (all parts) Safety of household and similar electrical appliances
SP 30 : 2023
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.—
3.1 Location — Particular place or position
EXAMPLE — A dedicated room, an area of a room (for example, area in a loft), an outdoor area.
3.2 Bath Tub — Basin for the total or substantial immersion of the human body in water, which is intended to be drained after every use.
3.3 Shower — Defined place intended for personal cleaning activity under a spray of water without intentional retention of the water.
3.4 Fixed Partition — Solid barrier or enclosure, including any integrated doors, with some portion attached to the building structure that will deflect water directed against its surface.
NOTES
1 Integrated doors are considered to be closed.
2 A curtain is not a fixed partition.
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.5 Assessment of general characteristics
4.1.5.5.101 General
When applying this document, the zones specified in 4.1.5.5.102, 4.1.5.5.103, and 4.1.5.5.104 shall be taken into account. For fixed prefabricated bath or shower units, the zones are applied to the situation when the bath or shower basin is in its intended configuration.
Fixed partitions including horizontal or inclined ceilings, walls with or without windows, doors, floors, may limit the extent of locations containing a bath or shower as well as their zones. Where the dimensions of fixed partitions are smaller than the dimensions of the relevant zones, for example partitions having a height lower than 225 cm, the minimum distance in horizontal and vertical direction shall be taken into account (see Fig. 2 to Fig. 9).
Shower curtains or equivalent flexible material shall not be used for limiting the zones.
Where a shower is located in zone 1 of a bath tub, the zones for a bath tub apply.
Where for showers there is more than one fixed water outlet, the limit of the zones to be considered are those given by the combination of the zones.
4.1.5.5.102 Description of zone 0
Zone 0 is limited:
a) by the interior of a bath tub, see Fig. 2 to Fig. 4;
b) for showers:
from the lowest finished floor level up to a horizontal plane at the height of 10 cm above; and
by a vertical circumscribing virtual surface at a distance of 120 cm from the centre of the fixed shower head(s) and/or water outlet(s) limited by fixed partitions restricting the water to enter into the area on the other side of the partition (see Fig. 5, Fig. 6, Fig. 7, Fig. 8 and Fig. 9).
Shower doors intended to be closed when taking a shower are delimiting the zone 0, (see Fig. 10).
4.1.5.5.103 Description of zone 1
Zone 1 is limited:
a) for a bath tub by:
the floor level below the bath tub;
a horizontal plane lying 225 cm above the floor level below the bath tub or a horizontal plane corresponding to the highest fixed shower head, if any, or fixed water outlet, whichever is higher;
the vertical virtual surface circumscribing the bath tub (see Fig. 2 to Fig. 4); and
excluding zone 0.
b) for showers by:
the lowest finished floor level;
a horizontal plane corresponding to the highest fixed shower head or fixed water outlet or the horizontal plane lying 225 cm above the lowest finished floor level, whichever is higher;
the vertical circumscribing virtual surface at a distance of 120 cm from the centre of the fixed shower head(s) and/or fixed water outlet(s) limited by fixed partitions restricting the water to enter into the area on the other side of the partition;
4.2 Protection Against Electric Shock
4.2.1 General Requirements
4.2.2 Replace the Existing Text by the Following:
The protective measure electrical separation shall only be used for:
a) circuits supplying one item of current-using equipment; or
b) one single socket-outlet.
The protective measure electrical separation for the supply shall not be applied for heating cables and embedded heating systems.
4.2.6 Replace the existing text by the following:
The protective measures of obstacles and placing out of reach, as specified in IS 732 : 2019, Annex B shall not be applied.
4.2.7 Replace the existing text by the following:
The protective measures of non-conducting location, earth-free local equipotential bonding and electrical separation for the supply of more than one item of current-using equipment, as specified in IS 732 : 2019, Annex C shall not be applied.
4.2.11 Protective Measure: Automatic Disconnection of Supply
4.2.11.3 Requirements for fault protection
4.2.11.3.1.2 Protective earthing and protective equipotential bonding
4.2.11.3.1.2.101 If no protective equipotential bonding in accordance with IS 732 : 2019, 4.2.11.3.1.2 exists, supplementary protective equipotential bonding in accordance with IEC 60364-4-41 : 2005 and IS 732 : 2019, 4.2.15.2 shall be installed within the location.
4.2.14 Protective Measure: Extra-Low-Voltage Provided by SELV and PELV
4.2.14.1 General
4.2.14.1.101 All electrical equipment installed in zones 0 and 1 shall have basic insulation capable of with standing a test voltage of 500 V a.c. RMS for 1 min.
SP 30 : 2023
All electrical equipment installed in a zone 2 shall have:
basic insulation capable of withstanding a test voltage of 500 V a.c. RMS for 1 min; or
enclosures affording a degree of protection of at least IPXXB or IP2X.
4.2.15 Additional Protection
4.2.15.1 Additional protection: residual current protective devices (RCDs)
4.2.15.1.101 Except for circuits with protective measures “SELV or PELV” or “protection by electrical separation”, additional protection by the use of one or more RCDs having a rated residual operating current not exceeding 30 mA shall be provided for:
5Selection and Erection of Electrical Equipment
5.1 Common Rules
5.1.2 Operational Conditions and External Influences
5.1.2.2 External influences
5.1.2.12.101 Erection of equipment according to external influences
5.1.2.2.101.1 General
Electrical equipment that is likely to be exposed to water jets (e.g. for cleaning purposes) shall have a degree of protection at least IPX5. A higher degree of protection shall be considered if more severe conditions are expected.
EXAMPLE — For a luminaire extending from zone 1 to zone 2, the requirements of zone 1 apply.
For flush mounted electrical equipment in parts of walls, floor or ceilings limiting a zone, the requirements of that zone apply.
5.1.2.2.101.2 Zone 0
Only fixed current using equipment may be erected provided that the equipment:
complies with the relevant standard and is suitable for use in that zone according to the manufacturer’s instructions for use and mounting;
is permanently connected;
is protected by SELV with a rated voltage not exceeding 12 V a.c. or 30 V d.c., with the source of supply installed outside of zones 0 and 1; and
has a degree of protection at least IPX7.
5.1.2.2.101.3 Zone 1
Only the following equipment may be erected:
a) current-using equipment protected by SELV or PELV with a rated voltage not exceeding 25 V a.c. or 60 V d.c., with the source of supply installed outside zones 0 and 1; or
b) socket-outlets of circuits protected by SELV or PELV with a rated voltage not exceeding 25 V a.c. or 60 V d.c., with the source of supply installed outside zones 0 and 1; or
c) fixed or stationary current-using equipment permanently connected and suitable for installation in zone 1 according to the manufacturer’s instruction for use and mounting; or
d) junction boxes and fittings necessary for the supply of equipment installed according to a), b) and c).
Equipment shall have a degree of protection at least IPX4.
EXAMPLE — Equipment likely to be installed in zone 1 includes hot tubs, shower pumps, ventilation equipment, towel rails, water heating appliances, luminaires, washing machines, active glazing, infrared and ultraviolet emitters.
5.1.2.2.101.4 Zone 2
Only the following equipment may be erected:
fixed current-using equipment, having a degree of protection of at least IPX4, that is permanently connected;
socket-outlets, having a degree of protection of at least IPX4, of circuits protected by SELV or PELV with the source of supply installed outside zones 0 and 1;
electrical accessories, other than socket-outlets, having a degree of protection at least IPX4, that are permanently connected;
shaver supply units according to IEC 61558-2-5. If the shaver supply unit is located such that direct spray from the shower is likely, it shall have a degree of protection of at least IPX4.
5.2Wiring Systems
5.2.5 Selection and Erection of Wiring Systems in Relation to External Influences
5.2.5.3 Presence of water (AD) or high humidity (AB)
5.2.5.3.101 Wiring systems that do not supply equipment in zone 0 shall not be routed through zone 0.
5.2.5.8 Other mechanical stresses (AJ)
5.2.5.8.101
NOTE — The following requirements are given to reduce the risk of damaging the wiring caused by drilling holes in the wall, for e.g., mounting handles.
The following requirements apply:
a) Wiring systems supplying current using equipment in zones 0, 1 or 2 and erected in parts of walls which are limiting these zones shall be mounted:
Key
0 Zone 0
1 Zone 1
A Other room
B Bathroom
L 1 Remaining wall thickness, minimum 6 cm
Fig. 1 Remaining Wall Thickness Behind Zones
SP 30 : 2023
either vertically from above or horizontally through the adjacent wall on the rear of the appliance when the fixed equipment is mounted above the bath tub or shower basin, for showers without a basin above the surface of the finished floor level (e.g. water heating appliances);
either vertically rising from below or horizontally through the adjacent wall on the rear of the appliance when the equipment is placed in the space below the bath tub or shower basin.
b) All other embedded wiring systems including their accessories in parts of walls or partitions which limit a zone 0, 1 or 2 shall not be mounted at a depth less than 6 cm from the wall surface limiting the zone, see L 1 in Fig. 1.
c) Where a) or b) are not fulfilled, wiring systems may be erected either if:
the circuits are protected either by one of the protective measures SELV or PELV or electrical separation; or the circuits are protected by additional protection according to IS 732 : 2019, 4.2.15.1 provided by RCDs with a rated residual operating current not exceeding 30 mA; such circuits shall contain a protective conductor; or embedded cables incorporating an earthed screen or a metallic covering which complies with the requirements for a protective conductor of the circuit concerned are used; or the cables are enclosed in an earthed conduit, satisfying the requirements for a protective conductor.
5.3Devices for Protection for Safety, Isolation, Switching, Control and Monitoring
5.3.2 Devices for Protection Against Indirect Contact by Automatic Disconnection of Supply
5.3.2.2 Residual current protective devices
The type of RCD selected for a circuit shall be compatible with the expected loads to be supplied (i.e. RCD of type a.c., type A, type F or type B).
5.3.2.2.101
101 EXAMPLES OF ZONE DIMENSIONS
Fig. 3 Dimensions of Zones: Top View of a Bath Tub without Partition
Dimensions in centimetres
Fig. 5 Dimensions of Zones 0 and 1: Side View of a Shower
0 Zone 0
S Fixed water outlet
1 Zone 1
SP 30 : 2023
Dimensions in centimetres
Key
0 Zone 0
1 Zone 1
P Fixed partition
Fig. 6 Dimensions of Zones 0 and 1: Side View of a Shower with Fixed Partition
T Thread gauge for minimum distance
S Fixed water outlet
Dimensions in centimetres
Key
1 Zone 1
S Fixed water outlet
Fig. 7 Dimensions of Zones 0 and 1: Top View of a Shower with Fixed Water Outlet Close to a Corner
Dimensions in centimetres
1 Zone 1
S Fixed water outlet
Fig. 8 Dimensions of Zones 0 and 1: Top View of a Shower with Fixed Water Outlet at a Distance From a Corner
SP 30 : 2023
Dimensions in centimetres
1 Zone 0 and zone 1
P Fixed partition
T Thread gauge for minimum distance
Fig. 9 Dimensions of Zones 0 and 1: Top View of a Shower with a Fixed Partition
S Fixed water outlet
Key
1 Zone 0 and zone 1
A Opened shower door
C Shower doors when shower is in use
B Shower doors when shower is not in use
S Fixed water outlet
Fig. 10 Example of Zone for Shower with Doors
SP 30 : 2023
Section 3Requirements for Swimming Pools and Fountains
Swimming pools and fountains can be classified based on the extent of activity involved and the locations they are situated in. They generally utilise electricity for their functioning. The combination of water and electricity can create dangerous and unintended paths of electrical current. Depending on the amount of current, the duration of exposure, and the current path through the body, electrical exposures can result in a broad range of injuries, from minor tingling to severe burns or death.
This section shall cover the requirements for construction and installation of electrical wiring, and other equipment that could be used in swimming pools and fountains.
For the purpose of this part of NEC Part 3 Section 3, the requirements of IS 732 : 2019 and shall apply. This Part 3/Sec 3 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3/Sec 3 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The particular requirements of this section of NEC apply to electrical installations of:
a) basins of swimming pools and paddling pools and their surrounding zones;
b) areas in natural waters, lakes in gravel pits and coastal and similar areas, specially intended to be occupied by persons for swimming, paddling and similar purposes, and their surrounding zones. Such areas in natural waters, lakes in gravel pits and coastal and similar areas, are considered as swimming pools;
c) basins of fountains and their surrounding zones.
NOTE — In these areas, in normal use, the effect of an electric shock is increased by a reduction in body resistance and contact of the body with earth potential.
For swimming pools for medical use, special requirements may apply.
This standard does not cover the use of mobile equipment, e.g. pool cleaning equipment.
2 REFERENCES
IS/IEC No.
Title
IEC 60364-7-702 : 2010 Low-voltage electrical installations — Requirements for special installations or locations — Swimming pools and fountains
IEC 60335-2-41 Household and similar electrical appliances — Safety — Part 2-41: Particular requirements for pumps
732 : 2019 Code of practice for electrical wiring installations
IS/IEC 60529 : 1989 Degrees of protection provided by enclosures (IP Code)
16205 (Part 1) : 2017 Conduit systems for cable management: Part 1 General requirements
IS/IEC No.
IEC 60245 (all parts) Rubber insulated cables — Rated voltages up to and including 450/750 V
IEC 60598-2-18 Luminaires — Part 2: Particular requirements — Section 18: Luminaires for swimming pools and similar applications
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
3.1 Fountain — Arrangement, typically for decorative purposes, where water issues from a source and fills a basin of some kind.
3.2 Basin of Fountain — Part of the fountain which collects discharged water.
3.3 Swimming Pool — Water basin designed for purposes such as swimming, diving, etc and not for personal cleaning activity.
3.4 Paddling Pool — Water basin with low water level, e.g. for playing or wading.
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.5 Assessment of general characteristics
4.1.5.5.101 General
Add the following:
The requirements of this part are based on the dimensions of three zones, zone 0, zone 1 and zone 2 as described in 4.1.5.5.102 to 4.1.5.5.104 (see Fig. A-1 to A-4).
For electrical equipment in parts of walls, floors or ceilings limiting the zones specified in 4.1.5.5.102 to 4.1.5.5.104 but being part of the surface of that wall, floor or ceiling, the same requirements that apply for the zone limited by the surface shall be fulfilled unless specific requirements exist (see 5.5).
The width of zone 1 or zone 2 may be reduced by fixed partitions having a minimum height of 2.5 m.
The requirements for swimming pools also apply to paddling pools.
For basins of fountains which are intended to be occupied by persons, the specifications, and requirements for zone 0 and zone 1 for swimming pools apply.
NOTES
1 Fixed partitions are fixed separating walls, walls including windows and doors. The zones are also limited by ceilings, slopes of roofs and floors. Fixed partitions that are lower than 2.5 m are only limiting if they end at a ceiling or slope of a roof.
2 When a fixed partition is erected inside a zone, its effects on the zone are illustrated in Fig. A-3.
3 For the installation of a prefabricated swimming pool, the requirements of this standard are applicable.
4 Annex A provides some examples of the zones.
4.1.5.5.102 Description of zone 0
This zone comprises
a) the interior of basins, including any recesses in their walls or floors,
b) the interior of basins for foot cleaning, and
c) the interior of waterjets or waterfalls, and the space below them (see Fig. A-4).
NOTE — If the zone cannot be precisely determined under waterjets or waterfalls, it is recommended to take the vertical plane from the rim of the basin as the horizontal limitation of the zone and the maximum height of the water jet or waterfall as the limitation of height.
4.1.5.5.103 Description of zone 1
This zone is limited by
a) the zone 0 boundaries,
b) a vertical plane 2 m from the rim of the basin,
NATIONAL ELECTRICAL CODE OF INDIA
c) the floor or surface expected to be occupied by persons, and
SP 30 : 2023
d) the horizontal plane 2.5 m above the floor or the surface expected to be occupied by persons.
NOTE — Inaccessible equipment installed in an enclosure below the surface of a floor or wall or above a ceiling is not considered to be within zone 1 (see 5.5.5.101.3).
Where the swimming pool contains diving structures, starting blocks, chutes or other components expected to be occupied or accessible by persons, zone 1 also comprises the zone limited by
a) a vertical plane situated 1.5 m around the diving boards, springboards, starting blocks, chutes and other components such as accessible sculptures and decorative basins,
b) the horizontal plane 2.5 m above the highest surface expected to be occupied by persons.
4.1.5.5.104 Description of zone 2
This zone is limited by:
a) the vertical plane external to zone 1 and a parallel plane 1.5 m from the former,
b) the floor or surface expected to be occupied by persons, and
c) the horizontal plane 2.5 m above the floor or surface expected to be occupied by persons.
There is no zone 2 for fountains.
NOTE — Inaccessible equipment installed in an enclosure below the surface of a floor or wall or above a ceiling is not considered to be within zone 2 (see 5.5.5.101.3).
4.2Protection Against Electric Shock
NOTES
1 For selection and erection of socket-outlets, see 5.3.
2 For selection and erection of other equipment, see 5.5.
4.2.1 General Requirements
4.2.6 Replace the existing by the following
The protective measures of obstacles and placing out of reach, as specified in Annex B of IS 732, shall not be applied.
4.2.7 Replace the existing by the following
The protective measures of non-conducting location, earth-free local equipotential bonding and electrical separation for the supply of more than one item of current-using equipment, as specified in Annex C of IS 732 shall not be applied.
4.1.101 Particular Requirements For Each Zone
Add the following:
4.1.101.1 Zones 0 and 1 of swimming pools and in areas of natural waters, lakes in gravel pits and coastal and similar areas
In zones 0 and 1 only protection by SELV at a nominal voltage not exceeding 12 V a.c. or 30 V d.c. is permitted, except where 5.5.104 applies. The source of supply shall be installed external to zones 0 and 1. Where the source of supply is installed in zone 2, 5.3 applies.
4.1.101.2 Zones 0 and 1 of fountains
In zones 0 and 1, only the following protective measures shall be employed:
a) SELV (see 4.2.14 of IS 732 : 2019), the source of supply being installed external to zones 0 and 1; or
b) automatic disconnection of supply (see 4.2.11 of IS 732 : 2019) using a residual current protective device with a rated residual operating current not exceeding 30 mA; or
c) electrical separation (see 4.2.13 of IS 732 : 2019), the separation source supplying a single item of equipment and being installed external to zones 0 and 1.
4.1.101.3 Zone 2 of swimming pools and in areas of natural waters, lakes in gravel pits and coastal and similar areas
NOTE — There is no zone 2 for fountains.
One or more of the following protective measures shall be employed:
a) SELV (see 4.2.14 of IS 732 : 2019). The source of supply shall be installed external to zone 0 and 1. Where the source of supply is installed in zone 2, 5.3 applies; or
b) automatic disconnection of supply (see 4.2.11 of IS 732 : 2019) using a residual current protective device with a rated residual operating current not exceeding 30 mA; or
c) electrical separation (see 4.2.13 of IS 732 : 2019). The separation source shall supply a single item of equipment and be installed external to zones 0 and 1. Where the separation source is installed in zone 2, 5.3 applies.
4.2.14 Protective Measure: Extra-Low-Voltage (SELV and PELV)
4.2.14.4 Requirements for SELV and PELV circuits
Add the following in 4.2.14 of IS 732 : 2019
PELV is not permitted.
4.2.14.4.5 Add the following
Where SELV is used, whatever the nominal voltage, basic protection (protection against direct contact) shall be provided by:
a) barriers or enclosures affording at least the degree of protection according to IEC 60529 IP2X or IPXXB, or
b) insulation capable of withstanding a test voltage of 500 V a.c. for 1 min.
All extraneous-conductive-parts in zones 0, 1 and 2 shall be connected by protective equipotential bonding conductors to the protective conductors of the exposed-conductive-parts of equipment situated in these zones.
1 This connection with the protective conductor may be provided in close proximity to the location, for example at an accessory or a distribution board or other equipment.
2 See also 5.2.5.8 and 5.5.101
Extraneous-conductive-parts are conductive parts not forming part of the electrical installation and liable to introduce an electric potential, including the electric potential of a local earth – for the scope of this standard, from outside zones 0, 1 and 2 into these zones. 3 Such parts may, for example, be
a) metallic pipelines for freshwater, waste water, gas, heating, climate control,
b) metallic parts of building construction,
c) metallic parts of the basin construction,
d) metal reinforcement of non-insulating floors,
e) metal reinforcement of concrete basins.
Floors made of individual concrete tiles, the reinforcement of which is fully encapsulated within the tile and not accessible without damaging the tile, are not considered as extraneous-conductive-parts and therefore need not be included in additional protective equipotential bonding.
Concrete tiles without metallic reinforcement, tile coverings and topsoil (e.g. lawn) are not considered as extraneous-conductive-parts and therefore need not be included in additional protective equipotential bonding.
4 The following conductive parts generally need not be included in additional protective equipotential bonding:
a) basin ladders and barriers;
b) diving structure ladders;
c) handrails and handholds on the rim of the basin;
d) grid covers including the mounting frames of overflow pipes;
e) window frames;
NATIONAL ELECTRICAL CODE OF INDIA
f) door frames;
g) starting blocks.
SP 30 : 2023
5Selection and Erection of Electrical Equipment
5.1 Common Rules
5.1.2.1 Operational conditions
5.1.2.2 External influences
Add the following:
Electrical equipment shall have at least the IP code (see IS/IEC 60529) according to Table 1.
Table 1
Minimum IP Numbe (Clause 5.1.2.2)
r Per Zone
Zone
Outdoor, with Waterjets During Cleaning Operation
Outdoor, without Waterjets
Indoor, with Waterjets During Cleaning Operation
Indoor, Without Waterjets
0
IPX5/IPX8
IPX8
IPX5/IPX8
IPX8
1
IPX5
IPX4
IPX5
IPX4
2
IPX5
IPX4
IPX5
IPX2
NOTES
1 IS/IEC 60529 states that, unless there is a relevant product standard, the test conditions for IPX8 are subject to agreement between manufacturer and user.
2 For zone 0, where waterjets during cleaning operations are expected, both IPX5 (to ensure resistance to the operations during the cleaning process) and IPX8 (to ensure resistance to the immersion in the water) are necessary (see 4.3 of IS/IEC 60529). Both IPX5 and IPX8 are necessary because IPX8 does not include protection against water jets.
5.2 Wiring Systems
5.2.5 Selection and Erection in Relation to External Influences
5.2.5.8 Other mechanical stresses
Add the following:
5.2.5.8.101 Erection according to the zones
In zones 0, 1 and 2, wiring systems shall not have accessible metallic covering. Metallic coverings which are inaccessible shall be connected to the supplementary equipotential bonding.
NOTE — Cables should be installed in conduits to facilitate rewiring.
5.2.5.8.102 Limitation of wiring systems according to the zones
In zones 0 and 1, wiring systems shall be limited to those necessary to supply equipment situated in these zones. Circuits erected in zone 2 or in walls, ceilings or floors delimiting zones 0, 1 or 2 and supplying equipment outside the zones shall be:
a) embedded at a minimum depth of 5 cm; or
b) protected by a residual current protective device with a rated residual operating current not exceeding 30 mA; or
c) supplied by SELV; or
d) protected by electrical separation.
5.2.5.8.103 Additional requirements for the wiring of fountains
Only cables of type 66 according to IEC 60245 series or a type with at least equivalent properties shall be used.
NOTE — Their suitability for permanent contact with water should be declared by the cable manufacturer in addition to compliance with IEC 60245-1 and IEC 60245-4.
Only conduit with classification code X5XX according to the resistance to impact in IS 16205-1/IEC 61386-1 shall be used.
For fountains not intended to be occupied by persons the following additional requirements shall be met:
a) cables or insulated conductors in non-metallic conduit for electrical equipment in zone 0 shall be installed as far outside the basin rim as possible and run to the electrical equipment inside the basin by the shortest practicable route. The cables shall be installed in conduits to facilitate rewiring;
b) in zones 0 and 1, cables or insulated conductors in non-metallic conduit shall be installed with suitable mechanical protection.
5.2.5.8.104 Junction boxes
Junction boxes shall not be installed in zone 0.
In zone 1, only junction boxes for SELV circuits are permitted (see 4.1.101).
5.3 Switchgear and Control Gear
Add the following:
In zone 0, no switchgear or control gear, including socket-outlets, shall be installed.
In zone 1, switchgear, control gear and socket-outlets may be installed only if supplied by SELV, the source of supply of which being installed outside zones 0 and 1. Where the source for SELV is installed in zone 2 its supply circuit shall be protected by a residual current protective device with a rated residual operating current not exceeding 30 mA.
In zone 2, switchgear, control gear and socket-outlets are not allowed unless protected by one of the following protective measures:
a) SELV (see 4.2.14.3 of IS 732 : 2019), the source of supply being installed outside zones 0 et 1. Where the source for SELV is installed in zone 2, its supply circuit shall be protected by a residual current protective device with a rated residual operating current not exceeding 30 mA; or
b) automatic disconnection of the supply with additional protection (see 4.2.15.1 of IS 732 : 2019), using a residual current protective device with a rated residual operating current not exceeding 30 mA; or
c) electrical separation (see 4.2.13 of IS 732 : 2019), supplied individually by the separation source which is installed outside zones 0 and 1. Where the source for electrical separation is installed in zone 2 its supply circuit shall be protected by a residual current protective device with a rated residual operating current not exceeding 30 mA.
5.5 Other Equipment
Add the following:
5.5.101 Current-Using Equipment Of Swimming Pools
5.5.101.1 In zones 0 and 1, only fixed current-using equipment especially designed for use in swimming pools may be installed, taking into account the requirements of 5.4.1.2 and 5.4.1.4.2.
5.5.101.2 Fixed connected swimming pool cleaning equipment intended to be used in zones 0 and 1 shall be supplied by SELV not exceeding 12 V a.c. or 30 V d.c. with the source being installed outside zones 0 and 1. Where the source of supply is installed in zone 2, 5.3 applies (see 3.3.4.1.101.1).
5.5.101.3 Feed pumps, or other special electrical equipment especially intended for use in swimming pools located in a room or location adjacent to the swimming pool and accessible via a hatch (or door) located on the deck surrounding the swimming pool, shall be protected by one of the following protective measures:
a) SELV not exceeding 12 V a.c. or 30 V d.c. with the source being installed outside zones 0 and 1. Where the source of supply is installed in zone 2, 5.3 applies (see 4.1.101.1);
b) electrical separation according to 4.2.13 of IS 732 with simultaneous fulfilment of the following conditions:
where the pump or other equipment is connected to the swimming pool basin, the connection shall only be made by non-conductive water piping;
it shall only be possible to open the hatch or the door by means of a key or tool;
all equipment installed in the room or location shall have a degree of protection of at least IPX5 or such protection shall be provided by an enclosure.
SP 30 : 2023
c) automatic disconnection of the power supply with simultaneous fulfilment of the following conditions:
where the pump or other equipment is connected to the swimming pool basin, the connection shall be made by either electrically insulated water piping, or metal water piping connected to the pool basin’s equipotential bonding:
it shall only be possible to open the hatch or the door by means of a key or tool;
all equipment installed in the room or location shall have a degree of protection of at least IPX5 or such protection shall be provided by an enclosure;
additional equipotential bonding shall be installed in accordance with 4.2.15.2;
the equipment shall be protected by a residual current protective device with a rated residual operating current not exceeding 30 mA.
NOTE — The room where the equipment is located is considered to be outside zones 1 and 2.
5.5.102 Underwater Lighting of Swimming Pools
Luminaires for use in the water or in contact with the water shall comply with IEC 60598-2-18.
Section 4 Requirements for Special Installations or Locations — Rooms and Cabins Containing Sauna Heaters
Rooms and cabins containing sauna heaters are considered as special locations necessitating distinct electrical requirements because of the increased electric shock risk associated with, extreme high temperatures with high humidity, lack of clothing and reduced skin resistance. This section shall cover the requirements for construction and installation of electrical wiring, and other equipment that could be used in locations containing sauna heaters.
For the purpose of this part of NEC Part 3/Sec 4, the requirements of IS 732 : 2019 shall apply. This Part 3/Sec 4 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3/Sec 4 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially
1 SCOPE
The particular requirements of this section (Part 3/Sec 4) of NEC apply to:
a) sauna cabins erected on site, for example, in a location or in a room.
b) the room where the sauna heater is, or the sauna heating appliances are installed. In this case the whole room is considered as the sauna.
They do not apply to prefabricated sauna cabins complying with a relevant equipment standard.
Where facilities like cold water basins or showers, etc. are installed, the requirements of Part 3/Sec 2 also apply.
2 REFERENCES
IS/IEC Number
732 : 2019
NEC Part 3/Sec 2
Code of practice for electrical wiring installations
IEC 60335-2-53
National Electric Code: Part 3 Requirements for special installations or locations. Section 2 Locations containing a bath or shower
Household and similar electrical appliances — Safety — Part 2-53: Particular requirements for sauna heating appliances
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.5 Assessment of general characteristics
4.1.5.1.1 General
When applying this standard, the zones specified in 4.1.5.11.1 to 4.1.5.11.3 shall be taken into account.
4.1.5.11.1 Description of Zone 1
4.2 Protection for Safety – Protection Against Electric Shock
4.3.2.3.11 Protection against direct contact shall be provided for all electrical equipment by:
a) barriers or enclosures affording a degree of protection of at least IPXXB or IP2X, or
b) insulation capable of withstanding a test voltage of 500 V a.c. r.m.s for 1 min.
4.1.2.1 Protection against direct contact
4.1.2.1.101 Obstacles
Protection against direct contact by means of obstacles is not permitted.
4.1.2.1.102 Placing out of reach
Protection against direct contact by placing out of reach is not permitted.
4.2.11.3.3 Additional protection by residual current protective devices (RCDs)
Additional protection shall be provided for all circuits of the sauna, except for the sauna heater, by the use of one or more residual current protective devices with a rated residual operating current not exceeding 30 mA.
4.1.2.2 Protection against indirect contact
4.1.2.2.101 Non-conducting location
Protection against indirect contact by using the protective measure: non-conducting location is not permitted.
4.1.2.2.102 Protection by earth-free local equipotential bonding
Protection against indirect contact by using the measure: earth-free local equipotential bonding is not permitted.
5Selection and Erection of Equipment – Common Rules
5.1.2.2 External influences
The equipment shall have at least the degree of protection IP24.
If cleaning by use of water jets may be reasonably expected, electrical equipment shall be at least IPX5.
Three zones are defined as shown in Fig. 1:
a) in zone 1: only equipment belonging to the sauna heater shall be installed;
b) in zone 2: there is no special requirement concerning heat resistance of equipment;
c) in zone 3: the equipment shall withstand a minimum temperature of 125 °C and the insulation of wires shall withstand a minimum temperature of 170 °C (see also 5.2 below for wiring).
5.2 Selection and Erection of Electrical Equipment – Wiring Systems
The wiring systems should be preferably installed outside the zones, that is, on the cold side of the thermal insulation. If the wiring system is installed in zone 1 or 3, that is, on the warm side of the thermal insulation, it shall be heat-resistant according to 5.1.2.2 of this section. Metallic sheaths and metallic conduits shall not be accessible in normal use.
5.3 Selection and Erection of Electrical Equipment – Isolation, Switching and Control
5.3.7.6 Functional switching (control)
Switchgear and controlgear which forms part of the sauna heater equipment or of other fixed equipment installed in zone 2, may be installed within the sauna room or cabin according to the manufacturer’s instructions. Other switchgear and controlgear, for example, lighting, shall be placed outside the sauna room or cabin. Socket-outlets shall not be erected within the location containing the sauna heater.
5.5 Other Equipment
Sauna heating appliances shall be installed according to manufacturer’s instructions, see 7.12.1 of IEC 60335-2-53.
b connection box
Fig. 1 Zones of Ambient Temperature
Section 5 Requirements for Special Installations or Locations — Construction and Demolition Site Installations
There is some confusion about the standard, maintenance, and testing of appliances and equipment on construction and demolition sites. Because of the short-term nature of these sites, the electrical equipment used is often sourced from multiple locations, or multiple contractors. It can be difficult to ensure that they have been appropriately maintained and tested prior to their use on the site. This section provides requirements electrical installations for the purpose of the ‘construction and demolition work’.
For the purpose of this part of NEC Part 3 Section 5, the requirements of IS 732 : 2019 shall apply. This Part 3 Section 5 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 5 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially
1 SCOPE
The requirements of this section (Part 3/Sec 5) of NEC apply to installations for construction and demolition sites for use during the period of the construction or demolition work which are intended to be taken out of service upon completion of the works. Examples include the following:
a) construction work of new buildings;
b) repair, alteration, extension or demolition of existing buildings or parts of existing buildings;
c) engineering works;
d) earthworks;
e) work of similar nature.
The requirements apply to fixed or moveable installations.
445
The requirements do not apply to installations in administrative locations of construction sites (for example, offices, cloakrooms, meeting rooms, canteens, restaurants, dormitories, toilets).
2 REFERENCES
IS/IEC/ISO Number
IS/IEC 61439-4 : 2012 Low-voltage switchgear and controlgear assemblies: Part 4 Particular requirements for assemblies for construction sites (ACS)
IS/IEC 60309-2 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 2 Dimensional interchangeability requirements for pin and contact-tube accessories (first revision)
IS/IEC 60309-1 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 1 General requirements (first revision)
IEC 60245-4 : 2011 Rubber insulated cables — Rated voltages upto and including 450/750 V — Part 4: Cords and flexible cables
4.1 Protection for Safety
4.1.2 Protection against Electric Shock
4.2.6 Replace with the following:
The protective measures:
a) obstacles, and
b) placing out of reach
as specified in IS 732 : 2019, Annex B shall not be used.
4.2.7 Replace with the following:
The protective measures:
a) non-conducting location,
b) earth-free equipotential bonding, and
c) electrical separation for the supply of more than one current-using equipment as specified in IS 732 : 2019, Annex C shall not be used.
4.2.101 Circuits supplying socket-outlets with rated current up to and including 32 A and other circuits supplying hand-held electrical equipment with rated current up to and including 32 A shall:
a) be protected by automatic disconnection of supply together with additional protection by the use of residual current devices having a rated residual operating current not exceeding 30 mA (see IS 732 : 2019, 4.2.15.1), or
b) be supplied by SELV or PELV (see IS 732 : 2019, 4.2.14), or
c) have electrical separation of circuits (see IS 732 : 2019, 4.2.13), each socket-outlet and hand-held electrical equipment being supplied by an individual isolating transformer or by separate windings of an isolating transformer.
4.2.11 Protective Measure: Automatic Disconnection of Supply
4.2.11.3 Requirements for fault protection
4.2.11.3.2 Automatic disconnection in case of a fault
4.2.11.3.2.101 For circuits supplying socket-outlets with a rated current exceeding 32 A, residual current devices shall be used as disconnection devices.
4.2.14 Protective Measure: Extra-Low Voltage Provided By SELV and PELV
4.2.14.4 Requirements for SELV and PELV circuits
4.2.14.4.5 Replace the subclause with the following:
Irrespective of the nominal voltage, in a.c. and d.c. circuits, the requirement for basic protection shall be provided by the following:
a) insulation in accordance with IS 732 : 2019, A.1, or
b) barriers or enclosures in accordance with IS 732 : 2019, A.2.
SP 30 : 2023
4.5 Protection Against Voltage Disturbances And Electromagnetic Disturbances
4.5.3.3.2 Protection against transient overvoltage of atmospheric origin or due to switching
4.5.3.3.2.101 Cranes, lifts, cement mixers and similar items of equipment are liable to produce switching overvoltages. Where such equipment is present, consideration should be given to the need for protection against switching overvoltages.
5Selection and Erection of Equipment
5.1 Common Rules
5.1.1 Compliance with Standards
5.1.1.1 Add the following:
All assemblies on construction and demolition sites (ACS) for the distribution of electricity shall be in compliance with the requirements of IS/IEC 61439-4.
Where interchangeability is required:
a) socket-outlets with a rated current not exceeding 16 A shall comply with IS/IEC 60309-2 or relevant national standards, and
b) socket-outlets with a rated current exceeding 16 A but not exceeding 125 A shall comply with IS/IEC 60309-2. Socket-outlets shall comply with IS/IEC 60309-1 where:
a) the rated current exceeds 125 A, or
b) interchangeability is not required.
5.1.2 Operational Conditions and External Influences
5.1.2.2 External influences
Consideration shall be given to the risk of damage to electrical equipment by corrosive substances, movement of structures and vehicles, wear and tear, tension, flexing, impact, abrasion, severing and ingress of liquids or solids.
5.2 Wiring Systems
5.2.5.8 Other mechanical stresses (AJ)
5.2.5.8.101 To avoid damage, cables should not be run across site roads or walkways. Where this is necessary, special protection against mechanical damage and contact with construction plant machinery shall be provided. Particular attention shall be given to the protection of surface run and overhead cables against mechanical damage, given the environment and activities at the construction site.
Flexible cables that are subject to movement shall be IEC 60245-4 type 66 or equivalent, resistant to abrasion and to water.
5.3 Isolation, Switching and Control
5.3.7 Isolation and Switching
5.3.7.3 Isolation
5.3.7.3.2 Devices for isolation
The following requirements are added:
Each assembly for construction sites (ACS) shall incorporate devices for isolating the incoming supply.
6Verification
6.101 Site work is in a constant state of change and, therefore, the associated electrical installation is subject to risk of damage or misuse. Therefore, in addition to initial and periodic verification, the installation shall be inspected frequently, for example daily, weekly, or monthly, as appropriate. Examples of some items to be inspected include:
a) the adequacy of connections and the condition of the protective conductors;
b) the condition of flexible conductors and their connections to portable equipment and hand-held equipment;
c) the rating and condition of fuses and the setting of the circuit-breakers to ensure that they are not unduly altered; and
d) the functioning of residual current devices.
SP 30 : 2023
Section 6 Conducting Locations with Restricted Movement
In most installations, access to earthed metal and conducting surfaces is fairly limited and the contact area of the body is generally comparatively low. As a result the likelihood of receiving a fatal electric shock is relatively small. In a conducting location where movement is restricted the situation is quite different.
Conducting locations with restricted movement are classed as special locations as the risk of electric shock is greatly increased. Work in these locations is often done by persons who are not electrically skilled. Conducting locations with restricted movement. Location is comprised mainly of metallic or other conductive parts. A person within the location will come into contact with a substantial portion of the conducting surface. The possibility of breaking the contact between the body and the conducting surface is limited.
For the purpose of this part of NEC Part 3 Section 6, the requirements of IS 732 : 2019 shall apply. This Part 3 Section 6 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 6 clauses are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
5Selection and Erection of Electrical Equipment
See IS/IEC TS 61439-7.
5.1 Selection and Erection of Electrical Equipment – Common Rules
5.1.2 Operational Conditions and External Influences
5.1.2.2 External influences
Add the following:
NOTE — In a caravan park or camping park, special consideration is given to the protection of people, due to the fact that the human body can be in contact with earth potential, to the protection of wiring due to tent pegs or ground anchors and to the movement of heavy or high vehicles.
5.2.5.3.101 Presence of water (AD)
Equipment shall be selected with a degree of protection of at least IPX4 in order to protect against water splashes (AD4).
5.2.5.4.101 Presence of solid foreign bodies (AE)
Equipment shall be selected or provided with a degree of protection of at least IP4X in order to protect against the ingress of very small objects (AE3).
5.2.5.6.101 Impact (AG)
Equipment installed in a campsite shall be protected against mechanical damage (impact of high severity AG3). Protection of the equipment shall be afforded by one or more of the following:
a) the position or location shall be selected to avoid damage by any reasonably foreseeable impact;
b) local or general mechanical protection shall be provided; and
c) equipment that complies with a minimum degree of protection against external mechanical impact of IK08 (see IS 17050 : 2018/IEC 62262 : 2002) shall be installed.
5.2 Wiring Systems
5.2.4 Types of Wiring Systems
5.2.4.7 Several circuits in one cable
5.2.4.7.101 Supply for the caravan or tent pitch
The preferred method of supply for feeding the caravan pitch or tent pitch electrical supply equipment is by means of underground distribution circuits.
5.2.4.7.101.1 Underground cables
5Selection and Erection of Electrical Equipment
5.1.2 Operational Conditions and External Influences
5.1.2.2 External influences
Add the following:
NOTE — For marinas particular attention is given in this part to the likelihood of corrosive elements, movement of structures, mechanical damage, presence of flammable fuel and the increased risk of electric shock due to:
a) presence of water;
b) reduction in body resistance;
c) contact of the body with earth potential.
5.2.5.4 Presence of water (AD)
In marinas, equipment installed on or above a jetty, wharf, pier or pontoon shall be selected as follows, according to the external influences which may be present:
a) water splashes (AD4): IPX4;
b) water jets (AD5): IPX5;
c) water waves (AD6): IPX6.
5.2.5.4 Presence of solid foreign bodies (AE)
Equipment installed on or above a jetty, wharf, pier or pontoon shall be selected with a degree of protection of at least IP4X in order to protect against the ingress of very small objects (AE3).
5.2.5.5 Presence of corrosive or polluting substances (AF)
Equipment installed on or above a jetty, wharf, pier or pontoon shall be suitable for use in the presence of atmospheric corrosive or polluting substances (AF2). If hydrocarbons are present AF3 is applicable.
5.2.5.6 Impact (AG)
Equipment installed on or above a jetty, wharf, pier or pontoon shall be protected against mechanical damage (impact of medium severity AG2). Protection shall be afforded by one or more of the following:
a) the position or location of the equipment shall be selected to avoid being damaged by any reasonably foreseeable impact;
b) local or general mechanical protection shall be provided;
c) equipment shall be installed which complies with a minimum degree of protection for external mechanical impact of IK07 (see IS 17050 : 2018/IEC 62262 : 2002).
5.2.4 Types of Wiring Systems
Annex BExample of an Instruction Notice to BE Placed in Marinas
B-1 It is recommended that the marina operator provides every pleasure craft operator who wishes to connect a pleasure craft to an electrical supply with an up-to-date copy of this instruction notice and also installs an up-to-date, clearly legible and weather protected copy of this instruction notice at every supply point.
B-2 The instruction notice should be in the national language(s) of the country and in English.
B-3 The instruction notice should contain, at least, the following:
Instructions for Connection to the Shore Supply
This marina provides a direct, earthed, connection to the shore supply.
General
a) Unless you have an isolating transformer fitted on board to isolate the electrical system on your craft from the shore supply, there is an increased risk of galvanic corrosion (electrolysis) damaging your craft.
b) The supply voltage at this marina is ……1) V, ……1) Hz (normally 230 V 50 Hz single-phase and 400 V 50 Hz three-phase), supplied by socket-outlets complying with IEC 60309-2.
c) Measures should be taken to prevent the connecting flexible cable or the connectors from falling into the water during connection and disconnection.
d) Only the connecting flexible cable from the craft should be connected to any socket–outlet.
e) Only one craft should be connected to one socket-outlet.
f) The connecting flexible cable should be undamaged and in one length, without joints and the connectors should be in good condition.
g) Moisture, dust and salt in the craft appliance inlet can constitute a serious hazard. Examine the appliance inlet: clean and dry it, if necessary, before plugging in the connecting flexible cable from the marina shore supply.
h) It is dangerous for unskilled persons to attempt repairs or alterations. If any difficulty arises, consult the marina operator.
On arrival
a) After mooring, switch off all current-using equipment on the craft.
b) Examine the flexible cable and its connectors to ensure it is undamaged and in good condition.
c) Connect the flexible cable first at the appliance inlet of the craft and then at the shore supply.
6Protection for Safety
For Protection for Safety, please refer to relevant items under 4 of IS 732. Additional requirements have been mentioned against each sub-clause below.
6.1 Protection Against Electric Shock
6.1.1 Protection against Both Direct and Indirect Contact
6.1.1.1 SELV and PELV
When using SELV and/or PELV circuits in medical locations of group 1 and group 2, the nominal voltage applied to current-using equipment shall not exceed 25 V r.m.s. a.c. or 60 V ripple free d.c.. Protection by insulation of live parts according to 4.2.12.1 of IS 732 and by barriers or enclosures according to 4.2.12.2 of IS 732 is essential. In medical locations of group 2, exposed-conductive-parts of equipment (for example, operating theatre luminaries), shall be connected to the equipotential bonding conductor.
6.1.2 Protection Against Direct Contact
6.1.2.1 Obstacles
Protection by obstacles is not permitted.
6.1.2.2 Placing out of reach
Protection by placing out of reach is not permitted.
Only protection by insulation of live parts or protection by barriers or enclosures is permitted.
6.1.3 Protection Against Indirect Contact
6.1.3.1 Automatic disconnection of supply
6.1.3.1.1 Disconnection of supply
In medical locations of group 1 and group 2, the following shall apply:
a) For IT, TN and TT systems, the conventional touch voltage U L shall not exceed 2 5 V ( U L ≤ 2 5 V ) ); and b) For TN and IT systems, Table 1 shall apply.
Table 1 Maximum Disconnecting Times
(Clause 6.1.3.1.1)
TN system
IT system
Installation Nominal Voltage
Disconnecting Times
Installation Nominal Voltage
Disconnecting Times
Uo a V
Uo/U V
Neutralnot distributed
Neutral distributed
7Selection and Erection of Electrical Equipment
For Selection and erection of electrical equipment, please refer relevant items under 5 of IS 732. Additional requirements have been mentioned against each item below.
7.1 Common Rules
7.1.1 Operational Conditions and External Influences
7.1.1.1 Operating conditions
7.1.1.1.1 Transformers for medical IT systems
It is recommended that the medical IT distribution board is located within 25 m of the point of use. The distribution board should be easily accessible for maintenance which will require it to be located on the same level and the same fire section as the load it serves.
Distribution boards shall be installed outside the group 2 medical locations and should be safely guarded against unauthorized persons.
The rated voltage U n on the secondary side of transformers shall not exceed 250 V a.c.
7.1.1.1.2 Medical IT systems for group 2 medical locations
Transformers shall be in accordance with IEC 61558-2-15, with the following additional requirements:
The leakage current of the output winding to earth and the leakage current of the enclosure, when measured in no-load condition and the transformer supplied at rated voltage and rated frequency shall not exceed 0.5 mA.
Single-phase transformers shall be used to form the medical IT systems for portable and fixed equipment and the rated output shall not be less than 0.5 kVA and shall not exceed 10 kVA.
If the supply of three-phase loads via an IT system is also required, a separate three-phase transformer shall be provided for this purpose with output line-to-line voltage not exceeding 250 V.
7.1.1.2 External influences
NOTE — Where appropriate, attention should be given to prevention of electromagnetic interference.
7.1.1.2.1 Explosion risk
NOTES
1 Requirements for medical electrical equipment for use in conjunction with flammable gases and vapors are contained of IS 13450 (Part 1).
2 Where hazardous conditions are likely to occur (for example, in the presence of flammable gases and vapors),special precautions may be required.
9Verification
The dates and results of each verification shall be recorded.
9.1 Initial Verification
The tests specified below under items a) to e) in addition to the requirements of IS 732, shall be carried out, both prior to commissioning and after alterations or repairs and before-commissioning.
a) Functional test of insulation monitoring devices and the over load monitoring of medical IT systems and acoustical/visual alarm systems.
b) Measurements to verify that the supplementary equipotential bonding is in accordance with Supplementary equipotential bonding.
c) Verification of the integrity of the facilities required with Supplementary equipotential bonding for equipotential bonding.
d) Verification of the integrity of the requirements of Safety services for safety services.
e) Measurements of leakage current of the output circuit and of the enclosure of medical IT transformers in no-load condition.
9.2 Periodic Verification
Periodic verification of items a) to e) of Initial verification shall be carried out in accordance with local/national regulations. If no local/national regulations exist, the following intervals are recommended:
a) Functional testing of changeover devices: 12 months;
b) Functional testing of insulation monitoring devices: 12 months;
c) Checking, by visual inspection, settings of protective devices: 12 months;
d) Measurement verifying the supplementary equipotential bonding: 36 months ;
e) Verifying integrity of facilities required for equipotential bonding: 36 months;
f) Monthly functional testing of:
Safety services with batteries: 15 min;
Safety services with combustion engines: until rated running temperature is achieved; 12 months for “endurance run”;
Safety services with batteries: capacity test;
Safety services with combustion engines: 60 min;
In all cases at least 50 percent to 100 percent of the rated power shall be taken over.
g) Measurement of leakage currents of IT transformers: 36 months; and
h) Checking of the tripping of RCDs at I∆N: not less than 12 months.
Annex BExamples for Allocation of Group Numbers and Classification for Safety Services of Medical Locations
B-1 A definitive list of medical locations showing their assigned groups is impracticable, as the use to which locations (rooms) might be put will differ within a country.
The accompanying list of examples is provided in Table B-1 as a guide only.
Table B-1 List of Examples(Clause B-1)
Medical location
Group
Class
0
1
2
≤ 0.5 s
>0.5s ≤ 15 s
1. Massage room
x
X
X
2. Bedrooms
X
3. Delivery room
x
Xa
X
4. ECG, EEG, EHG room
x
X
5. Endoscopic room
Xb
Xb
6. Examination or treatment room
X
X
7. Urology room
Xb
Xb
8. Radiological diagnostic and therapy room, other than mentioned under 21
The following values may be outdated and should be updated with the appropriate parts of the
IEC 61000 series. Some equipment will be more sensitive to electromagnetic interference (EMI). Therefore, the EMI limits of the medical equipment should be those recommended by the manufacturer.
Disturbances are not expected, if the magnetic induction B at 50 Hz does not exceed the following values at the patient position:
a) Btt = 0,1 μT for electromyogram (EMG);
b) Btt = 0,2 μT for electroencephalogram (EEG); and
c) Btt = 0,4 μT for electrocardiogram (ECG).
In general, these limit values are not exceeded, if the following minimum distances in all directions are observed between electrical equipment, which can cause magnetic disturbances, and the places of patient examination:
a) where inductive equipment with large output is used, a distance of 6 m in general is sufficient;
Examples of such equipment:
transformer of the electrical power installation, for example of the IT system;
– permanently installed motors, especially motors with nominal output exceeding 3 kW.
b) between multi-strand cables and lines of the electrical power installation and patient positions to be protected, in accordance with Table C-1.
Table C-1Minimum Distances
Conductor Cross-section
Minimum Distance
10 mm<sup>2</sup> to 70 mm<sup>2</sup>
3 m
95 mm<sup>2</sup> to 185 mm<sup>2</sup>
6 m
> 185 mm<sup>2</sup>
9 m
Larger distances may be required with single conductors. If there is a requirement to check the adherence of limit values, it is recommended to have an experts opinion.
Further mitigation measures may be:
a) passive (electrically) protective screening of the sources of electromagnetic fields;
b) passive (electrically) protective screening of the medical locations with special electromagnetic compatibility (EMC) needs;
5Selection and Erection of Electrical Equipment
5.1 Common Rules
5.1.101 Control and protective switchgear shall be placed in closed cabinets which can only be opened by the use of a key or a tool, except for those parts designed and intended to be operated by ordinary persons (BA1 in IS 732, Table 7).
5.1.1 Compliance with Standards
5.1.1.1 Add the following:
Where interchangeability is required:
a) socket-outlets with a rated current not exceeding 16 A shall comply with IS/IEC 60309 or relevant national standards, and
b) socket-outlets with a rated current exceeding 16 A but not exceeding 125 A shall comply with IS/IEC 60309-2.
SP 30 : 2023
Sockets-outlets shall comply with IS/IEC 60309-1 where:
a) the rated current exceeds 125 A, or
b) interchangeability is not required.
5.2 Wiring Systems
5.2.101 Conductors shall have a cross-sectional area of not less than 1.5 mm2 copper.
Cables shall be in accordance with IEC 60227 (all parts) or IEC 60245 (all parts), as appropriate.
Flexible cables shall not be laid in areas accessible to the public unless they are protected against mechanical damage.
5.2.4 Types of Wiring Systems
5.2.4.101 Where no fire alarm system is installed in a building used for exhibitions, etc. cable systems shall be either:
a) non-flame propagating according to IEC 60332-1-1 or IEC 60332-3 (all parts), and low smoke according to IEC 61034 (all parts), or
b) single or multicore unarmoured cables enclosed in metallic or non-metallic conduit or trunking, providing resistance to flame propagation in accordance with IS 16205 (all parts) or IS 14927 (all parts), providing a degree of protection of at least IP4X or IPXXD.
5.2.9 Electrical Connections
Joints shall not be made in cables except where necessary as a connection into a circuit. Where joints are made, these shall be either using connectors in accordance with the relevant IEC standards or the connection shall be made in an enclosure with a degree of protection of at least IP4X or IPXXD.
5Selection and Erection of Electrical Equipment
5.2 Wiring Systems
Add the following:
5.2.5.116 Selection of wiring system
The wiring system for connecting furniture to the electrical installation shall be:
a) rigid cable according to IEC 60227-3 or IEC 60245-1, if connected by permanent connection or installation coupler, as applicable; or of ordinary or heavy class of duty according to IEC 62440; and
b) rubber-insulated flexible cables and cords according to IEC 60245-4 or PVC-insulated flexible cables to IEC 60227-5 of ordinary or heavy class of duty according to IEC 62440, if connected by means of a plug and socket-outlet or by an installation coupler according to IEC 61535, as applicable.
Furniture intended to be moved shall be wired using flexible cables or cords according to IEC 60245-4 or IEC 60227-5.
Cables and cords shall be suitably protected against damage. They shall be securely fixed to the furniture or located in cable ducting, cable trunking, conduit, articulated systems for cable guiding, or a channel specially formed during the construction of the furniture.
5.5 Other Equipment
Add the following:
5.5.101 Selection of Accessories
Flush mounted boxes shall fulfil the requirements for hollow wall boxes according to IS 14772.
Surface mounted boxes shall comply with IS 14772.
Installed accessories shall be oriented or provided with a means to prevent the risk of electrical hazards from liquid spillage that can be reasonably expected.
Extra-low voltage (ELV) lighting is commonly used in domestic and commercial installations, particularly in the form of recessed downlighter luminaires. Specific requirements relating to ELV lighting installations are introduced in this section of NEC. The chapter also includes information on the requirements for the enclosure of terminations and joints in ELV lighting installations and on methods to be employed for minimising the spread of fire when installing downlighters.
For the purpose of this part of NEC Part 3 Section 12, the requirements of IS 732 : 2019 shall apply.
5Selection and Erection of Electrical Equipment
5.2 Wiring Systems
5.2.4 Types of Wiring System
5.2.4.1
Replace the text by the following:
The following wiring systems shall be used:
a) insulated conductors in conduit or cable trunking/ducting systems;
b) rigid cables;
c) flexible cables or cords;
d) systems for ELV lighting according to IEC 60598-2-23 : 1996;
e) track systems according to IEC 60570 : 2003; and
f) bare conductors (see 5.2.4.106).
Where parts of the ELV lighting installation are accessible, the requirements of 4.3.3 of IS 732 also apply.
Metallic structural parts of buildings, for example, pipe systems or parts of furniture, shall not be used as live conductors.
5.2.4.106 Bare conductors
If the nominal voltage does not exceed 25 V a.c. or 60 V d.c., bare conductors may be used provided that the extralowvoltage lighting installation complies with the following requirements:
a) the lighting installation is designed, installed or enclosed in such a way that the risk of a shortcircuit is reduced to a minimum;
b) the conductors used have a minimum cross sectional area according to 5.2.7 of this section ; and
c) the conductors or wires are not placed directly on combustible material.
For suspended bare conductors, at least one conductor and its terminals shall be insulated, for that part of the circuit between the transformer and the protective device, to prevent a short-circuit.
NOTE — Where bare conductors are used, consideration should be given to the possible presence of combustible material.
5.2.4.107 Suspended systems
Suspension devices for luminaires, including supporting conductors, shall be capable of carrying five times the mass of the luminaires (including their lamps) intended to be supported, but not less than 5 kg.
Terminations and connections of conductors shall be made by screw terminals or screwless clamping devices complying with IEC 60998-21 : 2002 or IEC 60998-22 : 2002.
Safety of the installation due to expected stresses in the conductors shall be in accordance with 5.5.3.5.2 of IS 732.
5Selection and Erection of Electrical Equipment
5.3 Isolation, Switching and Control
5.3.7 Isolation and Switching
Add the following:
5.3.7.101 The distance between the means of switching off for the electrical installation and the place where the corresponding supply cables enter the building shall be as short as practicable.
NOTE — National regulations may require that a means of switching off the electrical installation be provided. Such regulations may also prescribe its location and that it be either installed at an effectively locked location near the entrance to the building or directly accessible by authorized persons only from the outside.
5.3.7.102 If there is equipment in the premises that must remain energized when the building is unoccupied, the electrical installation shall be designed accordingly.
NOTE — Consideration should be given to the provision of separate circuits for such equipment.
SP 30 : 2023
5.5 Other Equipment
5.5.3 Luminaires and Lighting Installations
Add the following:
5.5.3.101 Maintenance of lighting circuits
5.5.3.101.1 Maintenance of adequate levels of illumination shall be determined by a risk assessment of the premises taking account of the classification of Table 7 of IS 732.
NOTE — In some countries legislation may impose additional requirements.
The different options are as follows:
a) Locations with low risk: single normal lighting final circuit.
NOTE — This is valid for code BD1 in Table 7 of IS 732.
b) Other locations: two or more normal lighting final circuits with luminaires supplied in such a way that failure of any one circuit will not leave any part of the location with an insufficient level of illumination.
If RCDs are used no RCD shall protect more than one final circuit..
NOTE — This is valid for codes BD2 to BD4 in Table 7 of IS 732.
NOTE — Emergency lighting circuits as required can be added to either option.
5.5.3.101.2 If the normal lighting of a location accessible to the public can be dimmed, means shall be provided to reinstate the full level of illumination by an appropriately located switch.
5Protection for Safety
For requirements of protection for Safety, relevant items under 4 of IS 732 may be referred. Additional requirements have been mentioned against each item below.
5.1 Protection against Electric Shock
5.1.1 The protective measures of obstacles and placing out of reach as specified in Annex B of IS 732 shall not be used.
5.1.2 The protective measures of non-conducting locations and earth-free local equipotential bonding as specified in Annex C of IS 732 shall not be used.
NOTE— This precludes the use of class 0 equipment.
5.1.3 Protective Measure: Automatic Disconnection of Supply
5.1.3.1 Protective equipotential bonding
Metal frame parts or thereto connected construction parts shall be connected through main protective bonding conductors to the main earthing terminal within the caravan.
5.1.4 Protective Measure: Electrical Separation
The protective measure: electrical separation shall not be used, except for a shaver socket-outlet.
5.1.5 Protective Measure: Extra-Low Voltage Provided by SELV and PELV
Any part of a caravan installation operating at extra-low voltage shall comply with the requirements of 4.2.14 of IS 732.
For extra-low voltage d.c. power sources, a maximum of 48 V are allowed. In exceptional cases, when a.c. extra-low voltage is required, the voltage (rms) is not allowed to exceed 48 V.
The requirements of this Part are also applicable to extra low-voltage d.c. installation. See Annex B for recommendations that can be applied in addition.
5.1.6 Additional Protection
5.1.6.1 Additional protection: residual current protective devices (RCDs)
Addition:
Where protection by automatic disconnection of supply is used, a residual current device with a rated residual operating current not exceeding 30 mA, complying with IS/IEC 60947-2, IS 12640 (Part 1), IS 12640 (Part 2) or IEC 62423 breaking all live conductors, shall be provided. Each supply inlet shall be directly connected to its associated RCD.
6Selection and Erection of Equipment
For selection and erection of electrical equipment, relevant items under 5 of IS 732 shall be referred. Additional requirements have been mentioned against each item below.
6.1 Common Rules
6.1.1 Introduction
6.1.1.1 General
Where there is more than one electrically independent installation, each independent installation shall be supplied by a separate connecting device and shall be segregated (in accordance with general rules) such that supplies at different voltages cannot be interconnected.
NOTE — Independent installations. An installation is an assembly of associated electrical equipment having co-ordinated characteristics to fulfil specific purposes.
6.1.2 Operational Conditions and External Influences
6.1.2.1 External influences
Consideration shall be given to the foreseeable external influences to which the caravan will be subjected.
SP 30 : 2023
6.1.3 Identification
6.1.3.1 General
Instructions for use shall be provided with the caravan so that the caravan can be used safely.
The instructions shall comprise:
a) a description of the installation;
b) a description of the function of the RCD(s) and the use of the test button;
c) a description of the function of the main isolating switch (es);
d) the text of the instructions of Annex A.
e) additional instructions necessary for user maintenance.
6.2 Wiring Systems
6.2.1 Types of Wiring Systems
6.2.1.1 The wiring system shall use one or more of the following:
a) insulated single-core cables, with flexible class 5 conductors, in non-metallic conduit or non-metallic trunking system;
b) insulated single-core cables, with stranded class 2 conductors (minimum of seven strands), in non-metallic conduit or non-metallic trunking system; and
c) sheathed flexible cables.
All cables shall as a minimum meet the requirements of IEC 60332-1-2.
Non-metallic conduit systems shall comply with the relevant part of IS 16205 (all parts) or IEC 61386 (relevant parts).
Annex A(Normative)
(Clause 6.1.3.1)
Instructions for Electricity Supply
A-1 Connection
a) Before connecting the caravan installation to the electricity supply, check that:
the supply available at the caravan pitch supply point is suitable for the caravan electrical installation and appliances, the voltage, frequency and current rating are suitable,
the cable and means of connection are suitable, and
the main isolating switch in the caravan is in the OFF position.
WARNING — The caravan supply flexible cable should be fully uncoiled to avoid damage by overheating.
b) Check the cable, the plug and the connector for damage.
c) Open the cover of the appliance inlet provided at the caravan, if any, and insert the connector of the flexible cable.
d) Insert the plug of the flexible cable into the electricity outlet provided on the pitch supply point.
e) Switch on the caravan main isolating switch.
f) Check the operation of residual current devices fitted in the caravan by depressing the test buttons and reset. In case of doubt or, if after carrying out the above procedure the supply does not become available, or if the supply fails, consult the caravan park operator.
A-2 Disconnection
Switch off at the caravan main isolating switch, unplug the cable, first on the caravan pitch supply point side and then at the caravan appliance inlet, if any.
A-3 Periodic Inspection
Preferably not less than once every three years and annually if the caravan is used frequently, the caravan electrical installation and supply cable should be inspected and tested by a competent electrician and a report on their condition obtained.
SP 30 : 2023
Annex B(Clause 5.1.5)
Extra Low-voltage DC Installations
B-1 Purposes, Supplies and Structure
B-1.1 Supplies
B-1.1.1 Sources of Supply
The supply should be obtained from one or more of the following sources:
a) the electrical installation of the towing vehicle;
b) an auxiliary battery mounted in the caravan;
c) a low-voltage d.c. supply via a transformer/rectifier unit complying with IS 302-1 and IS/IEC 61558-2-6;
d) a d.c. generator that is driven by any form of energy; and
e) solar photovoltaic (PV) power supply systems or similar.
B-2 Selection and Erection of Electrical Equipment
B-2.1 Common Rules
B-2.1.1 Identification
B-2.1.1.1 General
The following information should be provided in the instructions for use and should be in the official language(s) of the country in which the caravan is to be sold:
a) A warning worded as follows: “Any replacement of an auxiliary battery should be of the same type and specification as that originally specified by the caravan manufacturer”.
b) Instructions on the maintenance and recharging of an auxiliary battery where it is fitted. Where a battery charger is provided, instructions on its safe use should be included.
c) Instructions on selecting and installing an auxiliary battery in a compartment, if the caravan is intended for the installation of an auxiliary battery.
d) Details of the warning notice specified in B-2.4.1.3.7 and its importance for safety.
e) In order to ensure safe operation of the electrical installation, a simplified diagram of the wiring of the ELV and LV installation, with details of the cable colours and/or marking and the nominal values of the overcurrent protective devices should be provided.
f) Type of appliances that can be used and from what source of supply.
g) Instructions for the correct operation and maintenance of fitted appliances, as supplied by the appliance manufacturer.
h) A warning worded as follows: “Always disconnect the electrical connector between the towing vehicle and the caravan before connecting an LV supply to the caravan and before charging the caravan battery by any other means”.
B-2.1.2 Prevention of Mutual Detrimental Influence
Annex C(Clause B-2.2.2)
Current-carrying Capacities
C-1 The minimum conductor cross-sectional areas are to be selected from graphs (see Fig. C-1 and Fig. C-2) or calculated according to Formula (C-1).
C-1.1 Graphs for Obtaining Minimum Cross-Sectional Areas
Total length of both cables (positive and negative), in m (route length is half above length)
To obtain the minimum cross-sectional area for a circuit with a design current of 5 A and a total cable length of 24 m (12 m route length), the cross-sectional area of the conductors of that circuit should not be less than 4 mm2.
Fig. C-1 Graph for Obtaining Minimum Cross-Sectional Area for Conductors for Fixed Wiring Installations with a Voltage Drop of 0.8 V
Total length of both cables (positive and negative), in m (route length is half above length) Fig. C-2 Graph for Obtaining Minimum Cross-Sectional Area for Conductors for Battery Cable Installations with A Voltage Drop of 0.3 V
C-1.2 Calculation of the Minimum Cross-sectional Areas
The cross-sectional areas may be calculated from the following formula:
1.5 mm<sup>2</sup>
Branch circuit (DB to 6/16A power outlets 2 Nos.) for general use or 1 No. independent point for Water
2.5 mm<sup>2</sup>
heater/Microwave/OTG/Induction, total max. load 3 kW/circuit
Branch circuit (DB to 16/25A power point 1 No.) e.g. A.C. 2TR/3TR total max. load 5kW/circuit.
4.0 mm<sup>2</sup>
Mains/sub-mains for total connected load up to 5 kW
4 mm<sup>2</sup>
Mains/sub-mains for total connected load > 5 kW and < 7 kW
6 mm<sup>2</sup>
Mains/sub-mains for total connected load > 7 kW and < 10 kW
10 mm2/4 mm2 or 6 mm<sup>2</sup> (4 + E)*
* For 3-ph supply and load un-balance within 10 percent use 4 mm2, if load un-balance likely to exceed, use 6 mm2 (4+E)
NOTE — Mains for connected load equal to or above 10 kW; apply diversity factor, work out required current carrying capacity, find out suitable size from Annex C of Part 1 Section 9 and choose one size higher cable in anticipation of future additions.
5.5.3.5 Neutral
Neutral may be looped within respective circuit only. Size of neutral shall not be less than the phase conductor. Neutral shall not get individually isolated. For the purpose in single phase, SPN or DP and in three phase TPN or FP switches/MCBs shall be used.
5.5.3.5 Cables – colour code
Colour code shall generally follow norms specified in Part 1/Sec 9 for wiring installations. Circuit wires used for supply from inverter/standby supply arrangement shall be distinct.
5.5.3.6 Marking/identification
Ferruling shall be done with a mark of identification of circuit at every termination which shall also correspond to marking on DB.
5.5.3.7 Provision of DB(s)
Distribution board shall be of suitable type and size having required ways to accommodate number of circuits. Depending on expanse, provision of sub-distribution board/separate distribution board for lighting circuits and power circuits may be made. In case of three phase supply and single phase distribution DB with per phase isolation facility shall be preferred.
5.5.3.8 Location of DB
Location of distribution boards shall be in common areas like passages/lobby where entry is not restricted by lockable door. It shall be observed that, for easy operation and control during urgency/emergency, its position shall be within reach to an adult person without the aid of any tackle. Easy accessibility is also a mandatory requirement as per CEA safety regulations.
5.5.3.9 MCBs
Circuits having light, fan, on board plug socket shall be protected with 6A MCB. Circuits providing supply to more than two power outlets of 6A shall be protected with 6/10A MCB. Circuits providing supply to power outlets 16A up to two numbers, shall be protected with 16A MCB. Circuits providing supply to 25A power outlet shall be protected with 20/25A MCB. MCBs for lighting load may be of B series. MCBs for circuits of power outlets shall be B or C series depending on anticipated appliance going to be connected on that point, for example, motors, Air-Conditioners C series MCBs shall be provided.
NOTE — Use of old conventional Fuse/Kit-kat based DBs are not recommended for Domestic Dwellings from the point of view of safety, (see Note below 6.6.2 of Part 1/Sec 9).
5.5.3.10 Residual current devices (RCDs)
As per CEA (Measures Relating to Safety and Electric Supply) Regulations, 2010 (as amended), it is mandatory to provide RCD of 30 mA sensitivity to every electrical installation of capacity 1 kW and above to protect person from electrical shock. However, considering aspect of life safety, it is recommended to provide RCD to all installations without considering band of minimum load of 1 kW. To maintain supply redundancy, avoid blackouts provision of number of RCDs may be made suitably on each phase/each DB or particular appliance. RCD having 300 mA sensitivity shall also be installed at point of supply to prevent possibility of fire arising out of leakages.
NOTE — RCDs are also known as RCCBs or ELCBs.
1
1*
bath/toilet
2
1
passage/verandah
1
balcony/terrace
1
Entrance
1
1
servant room/garage
2
1
1
Dry balcony
1
* Optional provision
NOTES
1 Depending on number of rooms and area of room points shall be worked out.
2 Depending on extent of area of dwelling unit, internal communication facility may be a necessity. Intercom with additional telephone points may be considered at other locations including bathrooms.
k Washing machine/dishwasher
shower doors intended to be closed when taking a shower, if any, see Fig. 10; and
excluding zone 0.
4.1.5.5.104 Description of zone 2
Zone 2 is limited:
a) for a bath tub by the:
finished floor level;
horizontal plane corresponding to the highest fixed shower head or fixed water outlet or the horizontal plane lying 225 cm above the finished floor level, whichever is higher; and
vertical virtual surface at the boundary of zone 1 and the parallel vertical virtual surface at a distance of 60 cm from the zone 1 border (see Fig 2 to Fig. 4);
b) for showers, there is no zone 2. (see Fig. 5 to Fig. 10).
circuits serving the location containing a bath tub and/or a shower;
circuits passing through zone 1 and/or zone 2 not serving this location.
Underwater lighting located behind watertight portholes and serviced from behind shall be installed in such a way that no intentional or unintentional conductive connection between any exposed-conductive-part of the underwater luminaires and any conductive parts of the portholes can occur.
5.5.103 Electrical Equipment of Fountains
Electrical equipment in zones 0 and 1 shall be inaccessible, e.g. by use of mesh glass or by grids which can be removed only by tools.
Electric pumps shall comply with the requirements of IEC 60335-2-41.
5.5.104 Special Requirements for The Installation of Low Voltage Electrical Equipment in Zone 1 of Swimming Pools
5.5.104.1 Fixed equipment (e.g. filtration systems, jet stream pumps), especially intended for use in swimming pools and supplied at low voltage, is allowed in zone 1 provided all the following requirements are met:
a) the equipment shall be located inside an enclosure equivalent to supplementary insulation and providing protection against mechanical impact AG2;
b) the requirements of 5.5.101.3 apply;
c) the opening of the hatch specified in 5.5.101.3 shall result in the disconnection of all live conductors of the equipment located in the enclosure. The supply cable and the main disconnecting means shall be installed in a way which provides protection of class II or equivalent insulation.
5.5.104.2 For swimming pools where there is no zone 2, lighting equipment supplied by circuits other than SELV not exceeding 12 V a.c. or 30 V d.c. (see 4.1.101.1) may be installed in zone 1 on a wall or on the ceiling provided that both the following requirements are fulfilled:
a) the circuit is protected by automatic disconnection of supply and additional protection by using a residual current protective device with a rated operating current not exceeding 30 mA, and
b) the height of the lower part of the lighting equipment is at least 2 m from the lower limit of zone 1.
5.5.105 Floor And Ceiling Heating Systems
NOTE — See also IEC 60364-7-753.
Electric heating units embedded in the floor may be installed, provided that they are protected by either:
a) SELV (see 4.2.14 of IS 732 : 2019), the source of supply being installed outside zones 0 and 1. Where the source of supply is installed in zone 2, 5.6.5.5 applies; or
b) automatic disconnection of supply, the heating unit being covered by an embedded earthed metallic grid or by an embedded earthed metallic sheath connected to the supplementary equipotential bonding specified in 4.2.15.2 and the supply circuit being additionally protected by a residual current device with a rated residual operating current not exceeding 30 mA.
EXAMPLES OF ZONES formativ NNEX
Fig. A-1 Zone Dimensions for Swimming Pools and Paddling Pools (Side View)
NOTE — The measured zone dimensions are limited by walls and fixed partitions.
Fig. A-2 Zone Dimensions for Basin above Ground Level (Side View)
Fig. 3 Examples of Zone Dimensions (Top View) with Fixed Partitions of Height at least 2.5 m
NOTE — The thread gauge for distance could be, in this case, a string of specified length.
Fig. A-4 Example of Determination of the Zones of a Fountain (Side View)
Zone 1 is the volume containing the sauna heater limited by the floor, the cold side of the thermal insulation of the ceiling and a vertical surface circumscribing the sauna heater at a distance 0.5 m from the surface of the sauna heater. If the sauna heater is located closer than 0.5 m to a wall, then zone 1 is limited by the cold side of the thermal insulation of that wall.
4.1.5.11.2 Description of zone 2
Zone 2 is the volume outside zone 1, limited by the floor, the cold side of the thermal insulation of the walls and a horizontal surface located 1.0 m above the floor.
4.1.5.11.3 Description of zone 3
443
Zone 3 is the volume outside zone 1, limited by the cold side of the thermal insulation of the ceiling and walls and a horizontal surface located 1.0 m above the floor.
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.5 Assessment of general characteristics
4.1.5.5.101 The clearances for overhead lines above construction sites shall be agreed with the owner of the overhead power line, on the basis of the dimensions of the construction site machines, such as cranes, and equipment, such as ladders and scaffolding, to be used.
4.1.5.6 Purposes, supplies and structure
4.1.5.9 Supplies
The following note is added:
NOTE — A single construction site can be served by several sources of supply, including generating sets; see 5.5.2 of IS 732.
Devices for isolating the incoming supply shall be suitable for securing in the off position (see 5.3.7.3.1.2 of IS 732 : 2019) (for example, by providing a padlocking facility on the device or by locating the device inside a lockable enclosure). Safety and standby supplies shall be connected by means of devices arranged to prevent interconnection of the different supplies.
5.6 Safety Services
Add the following:
Site conditions may require the provision of safety services, for example escape lighting.
1 SCOPE
The particular requirements of this section (Part 3/Sec 6) apply to:
a) fixed equipment within conducting locations with restricted movement; and
b) supplies to equipment used within conducting locations with restricted movement.
2 REFERENCES
IS/IEC/ISO Number
Title
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
3.1 Conducting Location With Restricted Movement —Location surrounded by mainly extraneous-conductiveparts and where contact through one or more points on a person’s body with the extraneous-conductive-parts is likely and where there is limited possibility of interrupting this contact.
4 PROTECTION FOR SAFETY
4.2 Protection against Electric Shock
General Requirements:
The following requirement is added:
4.1.1 In conducting locations with restricted movement the following protective measures apply to circuits supplying the following current-using equipment:
a) For the supply to hand-held tools and portable equipment:
SELV (4.2.14 of IS 732), or
electrical separation (4.2.13 of IS 732) subject to only one item of equipment being connected to a secondary winding of the isolating transformer. NOTE — An isolating transformer may have several secondary windings.
b) For the supply to handlamps:
SELV (4.2.11 of IS 732).
NOTE — A fluorescent luminaire with built-in step-up transformer with electrically separated windings transformer supplied at SELV is equally permitted.
c) For the supply to fixed equipment:
automatic disconnection of the supply (see 4.2.11 of IS 732) with supplementary equipotential bonding (see 4.2.15.2 of IS 732) that shall connect exposed-conductive-parts of fixed equipment and the conductive parts of the location, or
SELV (see 4.2.14 of IS 732), or
PELV (see 4.2.14 of IS 732) where equipotential bonding shall be provided between all exposed-conductive-parts, all extraneous-conductive-parts inside the conducting location with restrictive movement, and the connection of the PELV system to earth, or
electrical separation (see 4.2.13 of IS 732) subject to one item of equipment being connected to a secondary winding of the isolating transformer, or
by use of Class II equipment or equipment having equivalent insulation (see 4.2.12 of IS 732) provided the supplying circuits are protected by additional protection by the use of residual current devices (see 4.2.15.1 of IS 732) with a rated residual operating current not exceeding 30 mA.
NOTE — A fluorescent luminaire with built-in step-up transformer with electrically separated windings and supplied at SELV is equally permitted.
4.2.3 Replace the existing text with the following
For the supply to mobile equipment, one of the following protective measures shall be applied:
a) SELV in accordance with IS 732 : 2019, 4.2.14, or
b) electrical separation for the supply of one item of current using equipment in accordance with IS 732 : 2019, 4.2.13.3.
NOTE — An isolating transformer can have several secondary windings.
For the supply to fixed equipment, one of the following protective measures shall be applied:
a) automatic disconnection of the supply in accordance with IS 732 : 2019, 4.2.11 together with additional protection by supplementary equipotential bonding in accordance with IS 732 : 2019, 4.2.15.2, or
b) SELV in accordance with 4.2.14 of IS 732 : 2019.
c) PELV in accordance with 4.2.14 of IS 732 : 2019 together with equipotential bonding between all exposed-conductive-parts and extraneous-conductive-parts and the connection of the PELV system to earth, or
d) electrical separation for the supply of one item of current using equipment in accordance with IS 732 : 2019, 4.2.13, or
e) double or reinforced insulation in accordance with 4.2.12 of IS 732 : 2019 together with additional protection by the use of a residual current device (RCD) with a rated residual operating current not exceeding 30 mA.
4.2.6 Replace the requirement with the following:
The protective measures of obstacles and placing out of reach in accordance with IS 732 : 2019, Annex B shall not be used.
4.2.13 Protection against both direct and indirect contact
The following requirements are added:
4.2.13.101 Sources for SELV and PELV
4.2.13.101.1 with restrictive movement, unless they are part of the fixed installation within the conducting location with restricted movement as provided by item c) of 4.2.1 of this section.
4.2.13.102 Requirements for unearthed circuits (SELV)
4.2.13.102.1 Basic protection (protection against direct contact) in accordance with 4.2.14.4 shall be provided, irrespective of the nominal voltage of the SELV circuits.
4.2.13.103 Requirements for earthed circuits (PELV)
4.2.13.103.1 Basic protection (protection against direct contact) in accordance with 4.2.14.4 shall be provided, irrespective of the nominal voltage of the PELV circuits.
4.2.12 Protection against Direct Contact
The following requirements are added:
4.2.12.101 Obstacles
Protection by means of obstacles (Annex B, B.2) is not permitted.
4.2.12.102 Placing out of reach
Protection by placing out of reach (Annex B, B.3) is not permitted.
4.2.13 Protective measure: electrical separation
The following requirements are added:
Only circuits and the protective measures for supplying equipment indicated in 4.2.1 of this section are permitted.
4.2.13.101 Equipotential bonding and functional earth
If a functional earth is required for certain equipment, for example measuring and control apparatus, equipotential bonding shall be provided between all exposed-conductive-parts, extraneous-conductive-parts inside the conducting location with restrictive movement and the functional earth.
4.2.13.3 Requirements for fault protection
4.2.13.3.2 Add the following requirement:
The source shall be situated outside the conducting location with restricted movement, unless the source is part of the fixed installation within the location.
4.2.13.3.7 Electrical separation
4.2.13.3.7.1 The source with protective separation in accordance with 4.2.13 of shall be situated outside the conducting location with restrictive movement, unless the source is part of the fixed installation within the conducting location with restrictive movement.
4.2.14 Protective measure: extra-low-voltage provided by SELV and PELV
4.2.14.3 Sources for SELV and PELV
The following requirements are added:
451
4.2.14.3.101 Sources for SELV and PELV shall be situated outside the conducting location with restricted movement, unless they are part of the fixed installation within the conducting location with restricted movement.
4.2.14.4 Requirements for SELV and PELV Circuits
4.2.14.4.5 Replace the first paragraph and first two dashed items with the following:
If the nominal voltage exceeds 25 V a.c. or 60 V d.c., or if the equipment is immersed, basic protection shall be provided for SELV and PELV circuits by:
a) insulation in accordance with A.1 of IS 732 : 2019, or
b) barriers or enclosures in accordance with A.2 of IS 732 : 2019.
Where functional earthing is required, supplementary equipotential bonding shall be provided between all exposed-conductive-parts, extraneous-conductive-parts and the terminals for functional earthing.
Section 7 Requirements for Special Installations or Locations — Caravan Parks, Camping Parks and Similar Locations
This section applies to the electrical installations in caravan/camping parks and similar locations providing connection points for supplying leisure accommodation vehicles (including caravans) and tents. It covers circuits intended to supply residential park homes in caravan parks, camping parks and similar locations. In addition it also specifies requirements to socket outlet requirements, RCD protection, and external influences.
For the purpose of this part of NEC Part 3/Sec 7, the requirements of IS 732 : 2019 shall apply. This Part 3/Sec 7 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3/Sec 7 clauses are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The particular requirements contained in this section (Part 3/Sec 7) apply only to circuits intended to supply leisure accommodation vehicles, tents or residential park homes in caravan parks, camping parks and similar locations.
NOTE — For the purposes of this document caravan park includes camping parks and similar locations.
The particular requirements do not apply to the internal electrical installations of leisure accommodation vehicles, mobile or transportable units or residential park homes.
2 REFERENCES
IS No./Other Title Publications
12360 : 1988 Voltage bands for electrical installations including preferred voltages and frequency
16205 (Part 24) : 2017 Conduit systems for cable management: Part 24 Particular requirements conduit systems buried under ground
17050 : 2018/ Degrees of protection provided by enclosures for electrical equipment against external IEC 62262 : 2002 mechanical impacts (IK code)
IS/IEC 60309-2 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 2 Dimensional interchangeability requirements for pin and contact-tubes accessories (first revision)
IS/IEC 60309-1 : 2002 Plugs, socket-outlets and couplers for industrial purposes — Part 1: General requirements
IEC 60309-4 : 2006 Plugs, socket-outlets and couplers for industrial purposes — Part 4: Switched socket-outlets and connectors with or without interlock
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
3.1 Leisure Accommodation Vehicle — Unit of living accommodation for temporary or seasonal occupation that may meet the requirements for the construction and use of road vehicles.
SP 30 : 2023
3.1.1 Caravan — Trailer leisure accommodation vehicle, used for touring, that meets the requirements for the construction and use of road vehicles.
3.1.2 Motor Caravan — Self-propelled leisure accommodation vehicle, used for touring, that meets the requirements for the construction and use of road vehicles.
NOTE — The motor caravan is either adapted from a series production vehicle, or designed and built on an existing chassis, with or without the driving cab, the accommodation being either fixed or demountable.
3.1.3 Mobile Home — Transportable leisure accommodation vehicle that includes means for mobility but does not meet the requirements for the construction and use of road vehicles.
3.2 Caravan/Tent Pitch — Plot of ground intended to be occupied by a leisure accommodation vehicle or tent
3.3 Caravan Park — Camping Park Area of land that contains two or more caravan or tent pitches.
3.4 Residential Park Home — Factory-produced relocatable dwelling
4 ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.6 Purposes, supplies and structure
4.1.5.8 Conductor arrangement and system earthing
4.1 5.8.2 Types of system earthing
4.1.5.8.2.1 TN-systems
Add the following:
For a TN-system, the final circuit for the supply to a leisure accommodation vehicle, tent or residential park home shall not include a PEN conductor.
4.1.5.9 Supplies
4.1.5.9.1 General
4.1.5.9.1.101 The nominal supply system voltage shall be selected from IS 12360/IEC 60038.
The nominal supply voltage of the installation for the supply of leisure accommodation vehicles shall not exceed 230 V a.c. single-phase and/or 400 V a.c. three-phase and 48 V d.c.
4.1 Protection for Safety
4.1.2 Protection against Electric Shock
General requirements
4.2.6 Add the following:
The protective measures of obstacles and placing out of reach as specified in Annex B of IS 732 shall not be used.
4.2.7 Add the following:
The protective measures of non-conducting location and earth-free local equipotential bonding as specified in Annex C of IS 732 : 2019 shall not be used.
4.2.11.3.3 Additional Protection
4.2.15.1 Residual current protective devices (RCDs)
Every socket-outlet shall be individually protected by an RCD having a rated residual operating current not exceeding 30 mA. Devices selected shall disconnect all live conductors.
A final circuit intended for the fixed connection for a supply to a mobile home or a residential park home shall be individually protected by an RCD having a rated residual operating current not exceeding 30 mA. Devices selected shall disconnect all live conductors.
An underground distribution circuit shall, unless provided with additional mechanical protection, be buried at a sufficient depth to avoid being damaged, for example by tent pegs or ground anchors or by the movement of vehicles.
A depth of 0.6 m is generally considered as a minimum depth to fulfill this requirement. Alternatively the cable may be installed outside the pitch or other area where tent pegs or ground anchors may be driven.
NOTE — For conduit systems buried underground, see IS 16205-24.
5.2.4.7.101.2 Overhead cables or overhead insulated conductors
Every overhead conductor shall be insulated.
Poles and other supports for overhead wiring shall be located or protected so that they are unlikely to be damaged by any foreseeable movement of vehicles.
NATIONAL ELECTRICAL CODE OF INDIA
Every overhead conductor shall be at a height above ground of not less than 6 m in all areas subject to the movement of vehicles and 3.5 m in all other areas.
SP 30 : 2023
5.3 Isolation, Switching and Control
5.3.4 Devices for Protection Against Overcurrent
In addition the following applies:
Every socket-outlet shall be individually protected by an overcurrent protective device, in accordance with the requirements of 4.4 of IS 732.
A fixed connection for a supply to a mobile home or residential park home shall be individually protected by an overcurrent protective device, in accordance with the requirements of 4.4 of IS 732.
5.3.7 Isolation and Switching
5.3.7.3 Isolation
5.3.7.3.1 General
5.3.7.3.1.1 Add the following:
At least one means of isolation shall be installed in each distribution cabinet. This device shall disconnect all live conductors.
5.5 Other Equipment
5.5.101 Socket-Outlets
5.5.101.1 Every socket-outlet shall comply with IS/IEC 60309-2.
Every socket-outlet shall meet the degree of protection of at least IP44 or such protection shall be provided by an enclosure.
To prevent the socket contacts being live when accessible, every socket-outlet or connector shall either comply with IS/IEC 60309-2 and shall be interlocked and classified according to IS/IEC 60309-1 : 1999, or shall be part of an interlocked self-contained product complying with IEC 60309-4 and classified according to IEC 60309-4 : 2006.
5.5.101.2 Every socket-outlet shall be located as close as practicable to the caravan pitch or tent pitch to be supplied.
Socket-outlets shall be installed in the distribution board or in separate enclosures.
5.5.101.3 In order to avoid any hazard due to long connection cables no more than four socketoutlets shall be grouped together in any one enclosure. To ensure that the degree of protection is maintained when the socket-outlets are in use, no more than four socket-outlets shall be mounted within the same enclosure.
Columns (pillars) should be located so as to minimize the need for extension cables to cross gangways, etc.
5.5.101.4 Every caravan pitch or tent pitch shall be supplied with at least one socket-outlet.
5.5.101.5 The current rating of socket-outlets shall be not less than 16 A.
5.5.101.6 The lowest part of any socket-outlet shall be placed at a height between 0.5 m and 1.5 m from the ground. In special cases of extreme environmental conditions, it is permitted to exceed the stated maximum height of 1.5 m. In such cases, special measures shall be taken to ensure the safe insertion and removal of plugs.
NOTE — This can be necessary if the caravan park or camping park risks being flooded. This can also be necessary if the caravan park is used during winter after heavy snow falls.
Section 8 Requirements for Special Installations or Locations — Marinas and Similar Locations
Marinas and similar locations are considered to be locations with an increased risk of electric shock. This is because of the presence of water, a reduction in body resistance, and contact of the body with Earth potential. In this Section we give an overview of the requirements of electrical circuits intended to supply houseboats and pleasure craft in marinas and similar locations
For the purpose of this part of NEC Part 3/Sec 8, the requirements of IS 732 : 2019 shall apply. This Part 3 Section 8 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 8 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The particular requirements specified in this section (Part 3/Sec 8) of NEC apply only to circuits intended to supply pleasure craft or houseboats in marinas and similar locations.
NOTE — In this part “marina” means “marina and similar locations”.
The particular requirements do not apply to the supply of house boats if they are directly supplied from the public network.
The particular requirements do not apply to the internal electrical installations of pleasure craft or house boats.
NOTES
1 For electrical installations of pleasure craft, see IEC 60092-507.
2 The electrical installations of house boats should comply with the general requirements of IEC 60364, together with the relevant particular requirements of IEC 603647.
For the remainder of the electrical installation of marinas and similar locations the general requirements of IEC 60364 together with the relevant particular requirements of IEC 603647 apply.
2 REFERENCES
IS/IEC/ISO Number
Title
IS/IEC 60309-2 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 2 Dimensional interchangeability requirements for pin and contact-tubes accessories (first revision)
IS/IEC 60309-1 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 1 General requirements (first revision)
IS 12360 : 1988 Voltage bands for electrical installations including preferred voltages and frequency IS 17050 : 2018/ Degrees of protection provided by enclosures for electrical equipment against external IEC 62262 : 2002 mechanical impacts (IK code)
IS/IEC 61558 Safety of transformers, reactors, power supply units and similar product for supply (Part 2/Sec 4) : 2009 voltages up to 1100 V: Part 2-4 Particular requirements and tests for isolating transformers and power supply units incorporating isolating transformers
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
3.1 Pleasure Craft — Any boat, vessel, yacht, motor launch, houseboat or other floating craft used exclusively for sport or leisure.
3.2 Marina — Facility for the mooring of pleasure craft with fixed wharves, jetties, piers or a pontoon arrangement capable of berthing one or more pleasure craft.
3.3 Houseboat — Floating decked structure which is designed or adapted for use as a place of permanent residence often kept in one place on inland water.
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.6 Purposes, supplies and structure
4.15.8 Conductor arrangement and system earthing
4.1.5.8.2 Types of system earthing
4.1.5.8.2.1 TN-systems
Add the following:
For a TN-system, the final circuits for the supply of pleasure craft or houseboats shall not include a PEN conductor.
4.1.5.9 Supplies
457
4.1.5.9.1.101 Add the following:
The nominal supply system voltage shall be selected from IS 12360.
The nominal supply voltage shall not exceed 230 V single-phase, or 400 V three-phase.
4.1 Protection for Safety
4.2 Protection against Electric Shock
4.2.11.2 Requirements for basic protection
709.521.7 Wiring systems of marinas
709.521.7.1 The following wiring systems are suitable for distribution circuits in marinas:
a) underground cables;
b) overhead cables or overhead insulated conductors;
c) cables with copper conductors and thermoplastic or elastomeric insulation and installed within an appropriate cable management system taking into account external influences such as movement, impact, corrosion and ambient temperature;
SP 30 : 2023
d) mineral-insulated cables with PVC protective covering;
e) armoured cables with a thermoplastic or elastomeric covering;
f) other cables and materials that are no less suitable than those listed under a), b), c), d) or e) above.
709.521.7.2 The following wiring systems shall not be used on or above a jetty, wharf, pier or pontoon:
a) overhead cables and overhead conductors in free air suspended from or incorporating a support wire, e.g. as installation method Nos. 35 and 36 in Table 19, Annex R of IS 732;
b) insulated conductors in conduits, trunking etc., e.g. as installation methods Nos. 4 and 6 in Table 19, Annex R of IS 732;
c) cables with aluminium conductors; and
d) mineral-insulated cables.
709.521.7.3 Cables and cable management systems shall be selected and installed so that mechanical damage due to tidal and other movement of floating structures is prevented.
Cable management systems shall be installed to allow the drainage of water/condensate e.g. by sloping way and/or drainage holes.
709.521.7.4 Underground cables
Underground distribution circuits shall, unless provided with additional mechanical protection be buried at a sufficient depth to avoid being damaged, e.g. by movement of vehicles.
NOTES
1 A depth of 0.5 m is generally considered as a minimum depth to fulfil this requirement.
2 For conduit systems buried underground, see IS 16205-24/IEC 61386-24.
709.521.7.5 Overhead cables or overhead insulated conductors
All overhead conductors shall be insulated.
Poles and other supports for overhead wiring shall be located or protected so that they are unlikely to be damaged by any foreseeable movement of vehicles.
Overhead conductors shall be at a height above ground of not less than 6 m in all areas subjected to movement of vehicles movement and 3.5 m in all other areas.
5.3.2 Devices for Protection against Indirect Contact by Automatic Disconnection of supply
5.3.2.2 Residual current protective devices (RCD’s)
Add the following:
Every socket-outlet with a rated current up to 63 A shall be individually protected by an RCD having a rated residual operating current not exceeding 30 mA. The RCD selected shall disconnect all poles, including the neutral.
Every socket-outlet with a rated current above 63 A shall be individually protected by an RCD having a rated residual operating current not exceeding 300 mA. The RCD selected shall disconnect all poles, including the neutral.
Account should be taken of the need for selectivity, e.g. by the use of Type S.
Every final circuit intended for the fixed connection of a supply to a house boat shall be protected individually by an RCD having a rated residual operating current not exceeding 30 mA. The RCD selected shall disconnect all poles, including the neutral.
5.3.4 Devices for Protection against Overcurrent
In addition the following applies:
Each socket – outlet shall be individually protected by an overcurrent protective device, in accordance with the requirements of 4.4 of IS 732.
Every final circuit intended for the fixed connection of a supply to a house boat shall be individually protected by an overcurrent protective device, in accordance with the requirements of 4.4 of IS 732.
5.3.7 Isolation and Switching
5.3.7.3 Isolation
5.3.7.3.1 General
5.3.7.3.1.1 At least one means of isolation shall be installed in each distribution board. This device shall disconnect all live conductors including the neutral conductor.
5.5 Other Equipment
5.5.101 Socket-Outlets General
5.5.101.1 Every socket-outlet with a current rating up to 63 A shall comply with IEC 60309-2. Every socket-outlet with a current rating over 63 A shall comply with IEC 60309-1.
Every socket-outlet shall meet the degree of protection of at least IP44 or such protection shall be provided by an enclosure.
Where the codes AD 5 or AD 6 are applicable the degree of protection shall be at least IPX5 or IPX6 respectively.
5.5.101.2 Every socket-outlet shall be located as close as practicable to the berth to be supplied.
Socket-outlets shall be installed in the distribution board or in separate enclosures.
5.5.101.3 In order to avoid any hazard due to long connection cords no more than four socket-outlets shall be grouped together in any one enclosure.
NOTE — See Annex B regarding recommended notices to be placed in marinas adjacent to each group of socket-outlets.
5.5.101.4 One socket-outlet shall supply only one pleasure craft or house boat.
5.5.101.5 In general single phase socket-outlets with rated voltage 200 V – 250 V and rated current 16 A shall be provided.
Where greater demands are envisaged socket-outlets with higher ratings may be provided.
5.5.101.6 Every socket-outlet, both on fixed jetties or piers and on floating pontoons, shall be placed in such a position as to avoid the effect of splashing and/or submersion unless appropriate measures are taken.
ANNEX A
(Informative)
EXAMPLES OF METHODS OF OBTAINING SUPPLY IN MARINAS
NOTE — In the Fig. A.1 through A.5 functional switches are not shown.
There is a risk of electrolytic corrosion resulting from circulating galvanic currents in the protective conductor to shore.
Fig. A-1 Direct Connection to A Single Phase Mains Supply
No connection shall be made between the PE conductor of the vessel and the PE conductor of the shore supply. This is to prevent galvanic currents circulating between the hull of the vessel and metallic parts on the shore side.
Fig. A-2 Direct Connection to a Single Phase Mains Supply with an Isolating Transformer on The Vessel
There is a risk of electrolytic corrosion resulting from circulating galvanic currents in the protective conductor to shore.
Fig. A-3 Direct Connection to a Three Phase Mains Supply
No connection shall be made between the PE conductor of the vessel and the PE conductor of the shore supply. This is to prevent galvanic currents circulating between the hull of the vessel and metallic parts on the shore side.
Fig. A-4 Direct Connection to a Three Phase Mains Supply with an Isolating Transformer on the Vessel
No connection shall be made between the PE conductor of the supply on the vessel and the PE conductor of the shore supply. This is to prevent galvanic currents circulating between the hull of the vessel and metallic parts on the shore side.
Only one socket-outlet shall be connected to each secondary winding of the isolating transformer.
The metallic parts of the vessel in contact with the water are bonded to the PE of the vessel.
Fig. A-5 Connection to a Single-Phase Supply Through a Shore-Mounted Isolating Transformer
d) Ensure the cable is placed where it will no be damaged and ensure that it will not a trip hazard to other persons.
Before leaving
a) Switch off all current-using equipment on the craft.
b) Disconnect the flexible cable from the socket–outlet on the shore and then from the appliance inlet on the craft.
c) Replace the cover on the appliance inlet on the craft to prevent the ingress of water.
d) Coil up the connecting flexible cable, ensure that the connectors are clean and dry, and store the cable in a dry location where it will not be damaged.
To be completed by the marina operator.
Bibliography
IEC 60092-507, Electrical installations in ships – Part 507: Pleasure craft
IEC 60364-5-52, Electrical installations of buildings – Part 5-52: Selection and erection of electrical equipment – Wiring systems
IEC 61386-24, Conduit systems for cable management – Part 24: Particular requirements – Conduit systems buried underground
Section 9 Requirements for Medical Locations
In medical locations it is necessary to ensure the safety of patients likely to be subjected to the application of medical electrical equipment. For every activity and function in a medical location, the particular requirements for safety have to be considered. Safety can be achieved by ensuring the safety of the installation and the safe operation and maintenance of medical electrical equipment connected to it. The use of medical electrical equipment on patients undergoing intensive care (of critical importance) has called for enhanced reliability and safety of electrical installations in hospitals so as to improve the safety and continuity of supplies which is met by application of this standard. Variations of the standard to further enhance safety and reliability are acceptable.
1 SCOPE
The particular requirements of this section (Part 3/Sec 9) of NEC apply to electrical installations in medical locations so as to ensure safety of patients and medical staff. These requirements, mainly, refer to hospitals, private clinics, medical and dental practices, health care centers and dedicated medical rooms in the work place. The requirements in this section shall be considered in addition to the requirements in other parts of NEC for medical locations.
NOTES
1 It may be necessary to modify the existing electrical installation, in accordance with this standard, when a change of utilization of the location occurs. Special care should be taken where intracardiac procedures are performed in existing installations.
2 Where applicable this standard can also be used in veterinary clinics. The requirements of this part do not apply to medical electrical equipment.
3 For medical electrical equipment; refer to the IS 13450 series.
2 REFERENCES
12032 (Part 1) : 1987 Graphical symbols for diagrams in the field of electrotechnology: Part 1 General information
12032 (Part 11) : 1987 Graphical symbols for diagrams in the field of electrotechnology: Part 11 Architectural and topographical installation plans and diagrams
13450 (Part 1) : 2018 Medical electrical equipment: Part 1 General requirements for basic safety and essential performance (second revision)
14700 (Part 3/Sec 2 and 3) Electromagneticcompatibility (EMC): Part 3 Limits: 2018
IEC 61000-2 series Electromagnetic compatibility (EMC) — Part 2: Environment
IEC 61082-1 : 2014 Preparation of documents used in electrotechnology — Part 1: Rules
IEC 61557-8 : 2014 Electrical safety in low voltage distribution systems up to 1000 Vac. and 1500 Vd.c. — Equipment for testing, measuring or monitoring of protective measures — Part 8: Insulation monitoring devices for IT systems
IEC 61558-2-15 : 2011 Safety of transformers + reactors + power supply units and combinations thereof — Part 2-15: Particular requirements and tests for isolating transformers for the supply of medical locations
13450 (Part 1) : 2018 Medical Electrical Equipment Part 1 General Requirements for Basic Safety and Essential Performance
SP 30 : 2023
3 DEFINITIONS
For the purposes of this part of NEC, the following definitions apply.
3.1 Medical Location — Location intended for purposes of diagnosis, treatment (including cosmetic treatment), monitoring and care of patients.
NOTE — To ensure protection of patients from possible electrical hazards, additional protective measures need to be applied in medical locations. The type and description of these hazards can vary according to the treatment being administered. The manner in which a room is to be used necessitates some division into different areas for differing medical procedures.
3.2 Patient — Living being (person or animal) undergoing medical or dental investigation or treatment.
NOTE — The person under treatment for cosmetic purposes may be considered, as far as this standard is concerned, as a patient.
3.3 Medical Electrical Equipment — Electrical equipment provided with not more than one connection to particular supply mains and intended to diagnose, treat or monitor the patient under medical supervision and which:
a) makes physical or electrical contact with the patient,
b) transfers energy to or from the patient, and
c) detects such energy transfer to or from the patient.
NOTE— The equipment includes those accessories defined by the manufacturer as being necessary to enable normal use of the equipment.
3.4 Applied Part — Part of the medical electrical equipment which in normal use:
a) Necessarily comes into physical contact with the patient for the equipment to perform its function,
b) can be brought into contact with the patient, or
c) needs to be touched by the patient.
3.5 Group 0 — Medical location where no applied parts are intended to be used.
3.6 Group 1 — Medical location where applied parts are intended to be used as follows:
a) Externally; and
b) Invasively to any part of the body, except where Group 2 applies.
3.7 Group 2 — Medical location where applied parts are intended to be used in applications such as intracardiac procedures, operating theatres and vital treatment where discontinuity (failure) of the supply can cause danger to life.
NOTE — An intracardiac procedure is a procedure whereby an electrical conductor is placed within the heart of a patient or is likely to come into contact with the heart, such conductor being accessible outside the patient’s body.In this context, an electrical conductor includes insulated wires such as cardiac pacing electrodes or intracardiac ECG electrodes, or insulated tubes filled with conducting fluids.
3.8 Medical Electrical System — Combination of items of equipment, at least one of which is an item of medical electrical equipment and inter-connected by functional connection or use of a multiple portable socket-outlet.
NOTE— The system includes those accessories which are needed for operating the system and are specified by the manufacturer.
3.9 Patient Environment — Any volume in which intentional or unintentional contact can occur between patient and parts of the system or between patient and other persons touching parts of the system (for illustration, see Fig.1).
NOTE — This applies when the patient’s position is pre-determined, if not, all possible patient positions should be considered.
3.10 Main Distribution Board — Board in the building which fulfils all the functions of a main electrical distribution for the supply building area assigned to it and where the voltage drop is measured for operating the safety services.
3.11 Medical IT System — IT electrical system having specific requirements for medical applications.
3.12 electric source for safety services-electric source intended to be used as part of an electric supply system for safety services.
3.13 medical insulation monitoring device (MED-IMD)-specific insulation monitoring device (IMD) dedicated to monitor medical IT systems.
3.14 insulation fault location system (IFLS) - device or combination of devices used for insulation fault location in IT systems, where the insulation fault location system is used in addition to an insulation monitoring device and is used to locate insulation faults.
4 ASSESSMENT OF GENERAL CHARACTERISTICS
For assessment of general characteristics, please refer 4.1.5.5 of IS 732 for relevant items given under this clause. Additional requirements have been mentioned against each sub-clause below.
4.1 The assessment shall be made in conjunction with medical staff and the person(s) responsible for medical safety, shall consider what effects discontinuity of the electric supply will have on the ME equipment or ME systems including:
the duration of the discontinuity (failure) of the electrical supply;
the effect of any supply interruption on the treatment, monitoring or examination, including if any procedure repetition is hazardous to the patient or if it is impossible to repeat the examination results.
A comprehensive assessment shall be performed to identify the proper electrical supply requirements for the ME equipment, ME systems and supporting electrical equipment intended to be used.
Having identified these requirements, the appropriate classification for the medical location shall be determined. In order to determine the extent of a medical location, all possible patient positions shall be considered.
Where assessment shows any given location that falls into both group 1 or group 2 categories, the location shall be classified as group 2.
1 For the classification of electric supply systems for safety services, see 5.6 of IS 732 and 8 of this document.
2 Guidance on the allocation of a group number and classification of electric supply systems for safety services for medical locations is shown in Annex A.
5 PURPOSES, SUPPLIES AND STRUCTURE
5.1 Types of System Earthing
The TN-C system is not allowed in medical locations and medical buildings downstream of the main distribution board.
5.2 Power Supply
5.2.1 General
In medical locations the distribution system should be designed and installed to facilitate the automatic change-over from the main distribution network to the electrical safety source feeding essential loads (according to IS 732).
5.2.2 Supplies for electric supply systems for safety services and standby systems in medical locations of group 1 and group 2
In medical locations of group 1 and group 2, the distribution system shall be designed and installed to facilitate the automatic transfer switching or automatic change-over equipment from the main distribution network to the electric source for safety services feeding essential loads (see 5.6 of IS 732). Consideration shall be given to all other essential medical and non-medical loads.
Consideration should also be given to the inrush current of any connected equipment.
NOTE — This could also apply to group 0 medical locations.
5.2.3 Power supply for medical locations of group 2
In case of a single fault in the power supply, a total loss of power shall be prevented. This may be achieved by:
– provision of two independent supply lines, and/or
• a UPS within the same fire section for supplying the medical IT system, or
• a UPS that supplies a number of group 2 locations.
SP 30 : 2023
120
0.35
120-240
0.4
1
230
0.2
230/400
0.2
0.5
277
0.2
277/480
0.2
0.5
400, 480
0.05
400/690
0.06
0.2
580
0.02b
580/1 000
0.02b
0.08
a Uo is the voltage between phase and neutral. b If such disconnecting time cannot be guaranteed, it is necessary to take other protective measures, such as supplementary equipotential bonding.
NOTE— Disconnection of supply when overload or short-circuit conditions occur, can be achieved by different design methods within the procedures of the general rules in order to satisfy the required safety level.
6.1.3.1.1.1 TN systems
In medical locations of group 1, in final circuits with overcurrent protective devices rated up to 32 A, residual current protective devices with a rated residual operating current not exceeding 30 mA shall be used.
In medical locations of group 2 protection by automatic disconnection of supply by means of residual current protective devices with a rated residual-operating current not exceeding 30 mA shall only be used on the following circuits that are supplying only one single equipment:
Final circuits of ME equipment and ME systems shall be for the exclusive use of such equipment.
Except those of the medical IT system, additional protection by residual current protective devices with a rated residual operating current not exceeding 30 mA shall be used in all final circuits as follows:
a) medical locations of group 1 with overcurrent protective devices rated 32A and below; and
b) medical locations of group 2.
6.1.3.1.1.2 TT systems
In medical locations of group 1 and group 2, the requirements of TN systems apply and, in all cases, residual current protective devices shall be used.
6.1.3.1.1.3 Medical IT system
In Group 2 medical locations, an IT system shall be used for final circuits and where the same final circuit is connected to more than one ME equipment or ME system, located within the patient environment, excluding:
a) equipment with a rated power greater than 5kVA;
b) X-ray equipment; and
c) the supply of movements of fixed operating tables.
In medical locations of group 2, the supply to final circuits for socket-outlets for ME equipment and ME systems used for life-support of the patient, shall not be automatically disconnected in the event of a first fault.
For each group of rooms serving the same function, at least one separate medical IT system is necessary. The medical IT system shall be equipped with an insulation monitoring device in accordance with IEC 61557-8 with the following specific requirements:
a) The a.c. internal impedance shall be at least 100 kΩ;
b) The test voltage shall not be greater than 25 V d.c.;
c) The injected current, even under fault conditions, shall not be greater than 1mA peak; and
d) Indication shall take place at the latest when the insulation resistance has decreased to 50 kΩ. A test device shall be provided;
NOTE — The necessary additional requirements on IMDs given above are at this time not covered in the equipment standard IEC 61557-8. They will be removed from this publication as soon as they have been treated in the relevant equipment standard.
For each medical IT system, an acoustic and visual alarm system incorporating the following components shall be arranged at a suitable place so that it can be permanently monitored (audible and visual signals) by the medical staff:
a) A green signal lamp to indicate normal operation;
b) A yellow signal lamp which lights when the minimum value set for the insulation resistance is reached. It shall not be possible for this light to be cancelled or disconnected;
c) An audible alarm which sounds when the minimum value set for the insulation resistance is reached. This audible alarm may be silenced; and
d) The yellow signal shall go out on removal of the fault and when the normal condition is restored.
Monitoring of overload and high temperature for the medical IT transformer is required.
6.1.3.1.2 Supplementary equipotential bonding
In each medical location of group 1 and group 2, supplementary equipotential bonding conductors shall be installed and connected to the equipotential bonding bus bar for the purpose of equalizing potential differences between the following parts, located in the “patient environment”:
a) Protective conductors;
b) Extraneous-conductive-parts;
SP 30 : 2023
c) Screening against electrical interference fields, if installed;
d) Connection to conductive floor grids, if installed; and
e) Metal screen of the isolating transformer, if any.
NOTE — Fixed conductive non-electrical patient supports such as operating theatre tables, physiotherapy couches and dental chairs should be connected to the equipotential bonding conductor unless they are intended to be isolated from earth.
6.1.3.1.3 In medical locations of group 2, the resistance of the conductors, including the resistance of the connections, between the terminals for the protective conductor of socket-outlets and of fixed equipment or any extraneous-conductive-parts and the equipotential bonding bus bar shall not exceed 0.2 Ω.
NOTE— This resistive value can also be determined by the use of a suitable cross-sectional area of the conductor.
6.1.3.1.4 The equipotential bonding bus bar shall be located in or near the medical location. In each distribution board or in its proximity, an additional equipotential bonding bar shall be provided to which the supplementary equipotential bonding conductor and protective earth conductor shall be connected. Connections shall be so arranged that they are clearly visible and easily disconnected individually.
6.1.4 Fire Protection
In medical locations of Group 1 and 2 Arc Fault Detection Devices (AFDDs) are not required to be installed.
In medical locations of Group 0 any Arc Fault Detection Device (AFDD) used shall be subject to a risk assessment.
6.1.5 Protection for safety – Protection against voltage disturbances and electromagnetic disturbances
6.1.5.1 Measures against electromagnetic influences
Special consideration shall be given to electromagnetic interference and electromagnetic compatibility. Further information is provided in Annex C.
3 Prevention of build-up of static electricity is recommended.
Electrical devices ( for example, socket-outlets and switches) shall be installed at a distance of at least 0.2 m horizontally (center to center) from any medical gas-outlets, so as to minimize the risk of ignition of flammable gases.
7.1.1.3 Diagrams, documentation and operating instructions
Plans of the electrical installation together with records, drawings, wiring diagrams and modifications thereto, as well as instructions for operation and maintenance, shall be provided for the user.
NOTE — Drawings and wiring diagrams should be in accordance with IS 12032 and IEC 61082-1.
The relevant documents are in particular:
a) Block diagrams showing the distribution system of the normal power supply and power supply for safety services in a single-line representation. These diagrams shall contain information on the location of the sub-distribution boards within the building;
b) Main and sub-distribution board block diagrams showing switchgear and control-gear and distribution boards in a single-line representation;
c) Architectural diagrams according to IS 12032 (Part 11);
d) Schematic diagrams of controls;
e) Instructions for operation, inspection, testing and maintenance of storage batteries and power sources for safety services;
f) Computational verification of compliance with the requirements of standards (e.g. with Automatic disconnection of supply);
g) List of loads permanently connected to the power supply for safety services indicating the normal currents and, in the case of motor-operated loads, the starting currents; and
h) A logbook containing a record of all tests and inspections which require to be completed prior to commissioning.
7.2 Wiring Systems
Any wiring system within group 2 medical locations shall be exclusive to the use of equipment and fittings in that location.
7.3 Switchgear and Control-gear
7.3.1 Protection of Wiring Systems in Medical Locations of Group 2
Total selectivity shall be ensured for any prospective overcurrent: In case of a short-circuit in a final circuit the incoming circuits of the upstream distribution board shall not be interrupted.
Overcurrent protection against short-circuit and overload current is necessary for each final circuit. Overload current protection is not allowed in the feeder circuits upstream and downstream of the transformer of medical IT-system.
7.4 Other Equipment
7.4.1 Lighting Circuits
In medical locations of group 1 and group 2, at least two different sources of supply shall be provided for some of the luminaries by two circuits. One of the two circuits shall be connected to the safety service.
In escape routes, alternate luminaries shall be connected to the safety service (see Safety services).
SP 30 : 2023
7.4.2 Socket-outlet Circuits in the Medical IT System for Medical Locations of Group 2
At each patient’s place of treatment, for example, bedheads, the configuration of socket-outlets shall be as follows:
a) Either a minimum of two separate circuits feeding socket-outlets shall be installed; or
b) Each socket-outlet shall be individually protected against overcurrent.
Where circuits are supplied from other systems (TN-S or TT systems) in the same medical location, socket-outlets connected to the medical IT system shall either:
a) be of such construction that prevents their use in other systems, or
b) be clearly and permanently marked.
7.4.3 Architecture of Special Safety Supply System in Operation Theatre
Operating Rooms require impeccable availability and quality of Electric power to ensure maximum patient safety. There shall be dedicated UPS system to ensure the back-up power for at least 3 h. Refer 6.1.3.1.1 Table 1 for safety provisions.
In Group 2 rooms that is operating rooms, an isolated power system panel shall be used for circuits powering medical electrical equipment and systems for survival and surgical applications.The above system architecture shall be supplied as integrated solution comprising of electrical switchgear, insulation monitoring device, medical rated transformer(as per NABH and this section’s guidelines) connected to building management system on non proprietory or open protocol communication system.Medical Rated Transformer shall conform to IEC 61558-2-15 and need to be protected against overload and short circuit and temperature monitoring of transfomrer is needed. Insulation monitoring device shall conform to IEC 61557-8. An audible and visual alarm shall be provided to alert medical and facility personnel. For optimum operation of medical equipments,prevention of electromagnetic disturbance is necessary. The above system shall be tested to attenuate electromagnetic disturbances according to 4.5 of IS 732, IEC 61000-2 and IS 14700 (Part 3) (see Fig. 2).
Fig.1 Architecture of Special Safety Supply System in Operation Theatre 8 Safety Services
NOTE Dimensions shown are not prescriptive.
Fig. 2 Example of Patient Environment
8.1 Sources
Classification of safety services are given in Annex A.
8.2 General Requirements for Safety Power Supply Sources of Group 1 and Group 2
8.2.1 In medical locations, a power supply for safety services is required which, incase of a failure of the normal power supply source, shall be energized to feed the equipment stated in detailed requirements for safety power supply services with electrical energy for a defined period of time and within a pre-determined changeover period.
8.2.2 If the voltage at the main distribution board drops in one or several line conductors by more than 10 percent of the nominal voltage, a safety power supply source shall assume the supply automatically.
The supply transfer should be achieved with a delay in order to cater for auto re-closure of circuit-breakers of incoming supplies (short-time interruptions).
8.2.3 For interconnecting cables between the individual components and sub-assemblies of safety power supply sources, see wiring systems.
NOTE — The circuit which connects the power supply source for safety services to the main distribution board should be considered a safety circuit.
8.2.4 Where socket-outlets are supplied from the safety power supply source they shall be readily identifiable.
SP 30 : 2023
8.3 Detailed Requirements for Safety Power Supply Services
8.3.1 Power Supply Sources with A Change-Over Period Less Than or Equal to 0.5 s
In the event of a voltage failure on one or more-line conductors at the distribution board, an electrical source for safety services shall be used which is capable of providing power supply for a period of at least 3 h for:
a) luminaries of operating theatre tables;
b) ME equipment containing light sources or equipment essential to the application.
As an example, this equipment may include endoscopes and essential equipment, such as monitors; and
c) critical life-supporting ME equipment.
The power supply shall be restored within a change-over period not exceeding 0.5 s.
The duration of 3 h battery may be reduced to 1 h, if a power source as diesel Generator is installed.
8.3.2 Power Supply Sources with A Change-Over Period Less Than or Equal to 15 s
Equipment according to Safety lighting and Other services shall be connected within 15 s to a safety power supply source capable of maintaining it for a minimum period of 24 h, when the voltage of one or more line conductors at the main distribution board for the safety services has decreased by more than 10 percent of the nominal value of supply voltage and of a duration greater than 3 s.
NOTE — The duration of 24 h can be reduced to a minimum of 3 h if the medical requirements and the use of the location, including any treatment, can be concluded and if the building can be evacuated in a time which is well within 24 h.
8.3.3 Power Supply Sources with a Changeover Period Greater than 15 s
Equipment other than those covered by ‘less than or equal to 0.5 s’ and ‘less than or equal to 15 s’, which is required for the maintenance of hospital services, may be connected either automatically or manually to a safety power supply source capable of maintaining it for a minimum period of 24 h. This equipment may include, for example:
a) Sterilization equipment;
b) Technical building installations, in particular air conditioning, heating and ventilation systems, building services and waste disposal systems;
c) cooling equipment; and
d) cooking equipment.
8.4 Safety Lighting Circuits
8.4.1 Safety Lighting
In the event of mains power failure, the necessary minimum illuminance shall be provided from the safety services source for the following locations. The changeover period to the safety source shall not exceed 15 s:
a) escape routes, stores, staircases ;
b) Lighting of exit signs/points;
c) Locations for switchgear and control-gear for emergency generation sets and for main distribution boards of the normal power supply and for power supply for safety services;
d) Rooms in which essential services are intended. In each room at least one luminaryshall be supplied from the power source for safety services;
e) Rooms of group 1 medical locations. In each room at least one luminary shall be supplied from the power supply source for safety services; and
f) Rooms of group 2 medical locations. A minimum of 50 percent of the lighting shall be supplied from the power source for safety services.
NOTE — The values for minimum illuminance can be given by national and/or local regulations.
8.5 Other Services
Services other than lighting which require a safety service supply with a changeover period not exceeding 15 s may include, for example, the following:
a) selected lifts for firemen;
b) ventilating systems for smoke extraction;
c) paging systems;
d) Medical electrical equipment used in group 2 medical locations which serves for surgical or other measures of vital importance. Such equipment will be defined by responsible staff;
e) Electrical equipment of medical gas supply including compressed air, vacuum supply and narcosis (anesthetics) exhaustion as well as their monitoring devices; and
f) Fire detection, fire alarms and fire extinguishing systems.
X
Xa
X
14. Operating plaster room
X
X
Xa
X
15. Operating recovery room
X
X
Xa
X
16. Heart catheterization room
X
Xa
X
17. Intensive care room
X
Xa
X
18. Angiographic examination room
X
Xa
X
19. Haemodialysis room
X
X
20. Magnetic resonance imaging (MRI) room
X
X
21. Nuclear medicine
X
X
22. Premature baby room
X
Xa
X
a Luminaries and life-support medical electrical equipment which needs power supply within 0.5s or less. b Not being an operating theatre.
B-2 Terminology
Terms listed in Table B-1.
B-2.1 Massage Room
B-2.2 General Ward (Bedrooms)
Medically used room or group of rooms in which patients are accommodated for the duration of their stay in a hospital, or in any other medical establishment.
Room intended for application of endoscopic methods for the examination of organs through natural or artificial orifices.
Examples of endoscopic methods are bronchoscopic, laryngoscopic, cystoscopic, gastroscopic and similar methods, if necessary, performed under anesthesia.
B-2.6 Examination or Treatment Room
B-2.7 Urology Room (Not Being an Operating Theatre)
Room in which diagnostic or therapeutic procedures are performed on the urogenital tract using medical electrical equipment, such as X-ray equipment, endoscopic equipment and high-frequency surgery equipment.
B-2.8 Radiological Diagnostic Room (Radiological Diagnostic and Therapy Room)
B-2.8.1 Radiological Diagnostic Room
Room intended for the use of ionizing radiation for display of internal structures of the body by means of radiography or fluoroscopy or by the use of radio-active isotopes or for other diagnostic purposes.
B-2.8.2 Therapy Room
Room intended for the use of ionizing radiation to obtain therapeutic effects.
B-2.9 Hydrotherapy Room
Room in which patients are treated by hydrotherapeutic methods Examples of such methods are therapeutic treatments with water, brine, mud, slime, clay, steam, sand, water with gases, brine with gases, inhalation therapy, electrotherapy in water (with or without additions), massage thermotherapy and thermotherapy in water (with or without additions).
Swimming pools for general use and normal bathrooms are not considered as hydrotherapy rooms.
B-2.10 Physiotherapy Room
Room in which patients are treated by physiotherapeutic methods.
B-2.11 Anesthetic Room
Medically used room in which general inhalation anesthetics are administered.
NOTE — The anesthetic room comprises for instance the actual operating theatre, the operating preparation room, the operating plaster room and treatment room.
B-2.12 Operating Theatre
Room in which surgical operations are performed.
B-2.13 Operating Preparation Room
Room in which patients are prepared for an operation, for example, by administering anesthetics.
479
B-2.14 Operating Plaster Room
Room in which plaster of paris or similar dressings are applied while anesthesia is maintained.
NOTE — Such a room belongs to the operating room group and is usually spatially connected to it.
B-2.15 Operating Recovery Room
Room in which the patient under observation recovers from the influence of anesthesia.
NOTE—Such a room is usually very close to the operating room group but not necessarily part of it.
B-2.16 Heart Catheterization Room
Room intended for the examination or treatment of the heart using catheters. Examples of applied procedures are measurement of action potentials of the hemodynamic of the heart, drawing of blood samples, injection of contrast agents or application of stimulants.
B-2.17 Intensive Care Room
Room in which bed patients are monitored independently of an operation by means ofmedical electrical equipment Body actions may be stimulated if required.
B-2.18 Angiographic Examination Room
Room intended for displaying arteries or veins, etc. with contrast media.
B-2.19 Haemodialysis Room
Room in a medical establishment intended to connect patients to medical electrical equipment in order to detoxicate their blood.
B-2.20 Magnetic Resonance Imaging (MRI)
B-2.21 Nuclear Medicine
B-2.22 Premature Baby Room
SP 30 : 2023
c) use of active compensation systems;
d) use of equipment with lower sensitivity against external electromagnetic fields.
Section 10 Requirements for Special Installations or Locations — Exhibitions, Shows and Stands
This section provides requirements for temporary electrical installations associated with exhibitions, shows and stands. Such installations may be installed indoors or outdoors within permanent or temporary structures. The electrical installation of the building, if any, in which the exhibition, show or stand will take place, will not be considered.
For the purpose of this part of NEC Part 3 Section 10, the requirements of IS 732 : 2019 shall apply. This Part 3 Section 10 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 10 clauses are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The particular requirements of this section (Part 3/Sec 10) of NEC apply to the temporary electrical installations of exhibitions, shows and stands (including mobile and portable displays and equipment).
2 REFERENCES
IEC 60332-1-1 : 2015 Tests on electric and optical fibre cables under fire conditions — Part 1-1: Test for vertical flame propagation for a single insulated wire or cable — Apparatus
IEC 60332-3 : 2018 Tests on electric and optical fibre cables under fire conditions : Test 3 Test for vertical flame spread of vertically-mounted bunched wires or cables — Apparatus
IS/IEC 60309-1 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 1 General requirements
IS/IEC 60309-2 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 2 Dimensional interchangeability requirements for pin and contact-tube accessories
IEC 60364-7-705 : 2006 Low-voltage electrical installations — Part 7-705: Requirements for special installations or locations — Agricultural and horticultural premises
15885 (all Parts) : 2011 Safety of lamp controlgear
IS/IEC 61558 (all parts) Safety of power transformers, powerSupply units and similar
16205 (all Parts) : 2017 Conduit systems for cable management
14927 (all parts) : 2001 Cable trunking and ducting systems for electrical installations
IEC 61034 (all parts) Measurement of smoke density of cables burning under defined conditions
IEC 60227 (all parts) Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V
IEC 60245 (all parts) Rubber insulated cables — Rated voltages up to and including 450/750 V
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
483
3.1 Exhibition — Event intended for the purpose of displaying and/or selling products etc., which can take place at any suitable location, for example a room, building or temporary structure or outdoors.
3.2 Show — Display, presentation or performance which can take place in any suitable location, for example a room, building or temporary structure or outdoors.
3.3 Stand — Area or temporary structure used for display, marketing, sales, entertainment, etc.
3.4 Temporary Structure — Unit or a part of a unit including mobile portable units, situated indoors or outdoors, designed and intended to be assembled and dismantled.
3.5 Temporary Electrical Installation — Electrical installation erected and dismantled in conjunction with, for example the stand or display with which it is associated.
3.6 Origin of the Temporary Electrical Installation — Point on the permanent installation or other source of supply from which electrical energy is delivered to the temporary electrical installation.
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.6 Purposes, supplies and structure
4.1.5.9 Supplies
Add the following:
The nominal supply voltage to earth of electrical installations in exhibitions, shows and stands shall not exceed 230 V RMS a.c. or 350 V ripple free d.c..
4.2 Protection for Safety-Protection against Electric Shock
General requirement
4.2.6 Replace the requirement with the following:
The protective measures:
a) obstacles, and
b) placing out of reach.
as specified in IS 732, Annex B shall not be used.
4.2.7 Replace the requirement with the following:
The protective measures:
a) non-conducting location,
b) earth-free equipotential bonding, and
c) electrical separation for the supply of more than one current-using equipment as specified in IS 732, Annex C shall not be used.
4.2.101 All final circuits not exceeding 32 A supplying socket-outlets, all final circuits for lighting, except emergency lighting and all final circuits supplying hand-held electrical equipment that has a rated current not exceeding 32 A shall:
a) be protected by automatic disconnection of supply together with additional protection by the use of residual current devices (RCD) having a rated residual operating current not exceeding 30 mA (IS 732, 4.2.15.1.1), or
b) be supplied by SELV or PELV (IS 732, 4.2.14), or
c) have electrical separation of circuits (IS 732, 4.2.13), each socket-outlet and hand-held electrical equipment being supplied by an individual isolating transformer or by separate windings of an isolating transformer.
4.2.11 Protective Measure: Automatic Disconnection of Supply
4.2.11.3 Requirements for fault protection
4.2.11.3.2 Automatic disconnection in case of a fault
4.2.11.3.2.101 For circuits supplying temporary structures, RCDs shall be used as automatic disconnection devices.
4.2.11.4 TN system
4.2.11.4.101 A PEN conductor shall not be used in the installation.
4.2.14 Protective Measure: Extra-Low Voltage provided by SELV and PELV
4.2.14.4 Requirements for SELV and PELV circuits
4.2.14.4.5 Replace the subclause with the following:
Irrespective of the nominal voltage, in a.c. and d.c. circuits, the requirement for basic protection shall be provided by the following:
a) basic insulation in accordance with A-1 of IS 732, or
b) barriers or enclosures in accordance with A-2 of IS 732.
In locations intended for livestock, consideration shall be given to applying the relevant supplementary protective equipotential bonding requirements of IEC 60364-7-705.
4.3.1 Protection against Thermal Effects
4.3.2 Precautions where Particular Risks of Fire Exist
4.3.2.4 Locations with combustible constructional materials
4.3.2.4.101 Heat generation
Lighting equipment such as incandescent lamps, spotlights and small projectors, and other equipment or appliances with high temperature surfaces shall be suitably guarded, and installed and located in accordance with the relevant standard. All such equipment shall be arranged well away from combustible material to prevent contact.
Showcases and signs shall be constructed of materials having an adequate heat resistance, mechanical strength, electrical insulation and ventilation, taking into account the combustibility of exhibits in relation to the heat generation.
Stand installations containing a concentration of electrical apparatus, lighting fittings or lamps liable to generate excessive heat shall not be installed unless adequate ventilation provisions are made, for example well-ventilated ceilings constructed of incombustible material.
5.3 Isolation, Switching and Control
5.3.6 Co-ordination of various Protective Devices
5.3.6.3 Discrimination between residual current protective devices
Replace the first paragraph with:
Discrimination between residual current protective devices installed in series shall be provided.
5.3.7 Isolation and Switching
5.3.7.3 Isolation
5.3.7.3.1.1 Add the following:
Every separate temporary structure, such as a vehicle, a stand or a unit, intended to be occupied by one specific user and each distribution circuit supplying outdoor installations shall be provided with their own readily accessible and properly identifiable means of isolation.
5.5 Other Equipment
5.5.101 ELV Transformers and Electronic Converters
Multiple connection extra low voltage (ELV) transformers shall conform with IEC 61558 (all parts) or provide an equivalent degree of safety.
Particular care shall be taken when installing ELV transformers, which shall be mounted out of arm’s reach of the public and shall have adequate ventilation. Access by skilled (BA5 in in IS 732, Table 7) or instructed (BA4 in IS 732, Table 7) persons for testing and maintenance shall be provided.
Electronic converters shall conform with IS 15885 (all parts).
5.5.3 Luminaires and Lighting Installations
5.5.3.3 General requirements for installations
5.5.3.3.101 Luminaires
Luminaires mounted below 2.5 m (arm’s reach) from floor level or otherwise accessible to accidental contact shall be firmly and adequately fixed, and so sited or guarded as to prevent risk of injury to persons or ignition of materials.
5.5.3.3.102 Lampholders
Insulation piercing lampholders shall not be used unless the cables and lampholders are compatible, and providing the lampholders are non-removable once fitted to the cable.
Circuits, other than the internal wiring of an exhibit not covered by a relevant product standard, operating at voltages exceeding 230/400 V a.c. derived from an installation of a lower nominal voltage, shall meet the requirements of 5.5.3.3.103.2 to 5.5.3.3.103.4.
5.5.3.3.103.2 Location
The sign or lamp shall be installed out of arm’s reach or shall be adequately protected to reduce the risk of injury to persons.
5.5.3.3.103.3 Installation
The facia or stand fitting material behind luminous tube signs or lamps shall be non-ignitable and protected as required by national standards.
Controlgear with output voltages higher than 230/400 V a.c. shall be mounted on non-ignitable material.
5.4.5.5 Emergency switching devices
A separate circuit shall be used to supply such signs, lamps or exhibits, which shall be controlled by an emergency switch.
The switch shall be easily visible, accessible and marked in accordance with the requirements of the local authority.
Section 11 Requirements for Special Installations or Locations — Furniture
In recent times, there are an increasing number of furniture products sold in the market that are designed using electrical components to enhance the features beyond those normally considered important for furniture (strength, durability and comfort). Therefore it imperative that the furniture industry has reliable access to information to ensure compliance, and of course safety for the end-users.
These enhancements may include power outlets, USB outlets, wi-fi induction chargers, short range wireless communication controllers and Bluetooth connected speakers/devices. This section provides the requirements for electrical installations included in furniture.
487
For the purpose of this part of NEC Part 3 Section 2, the requirements of IS 732 : 2019 shall apply. This Part 3 Section 2 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 2 clauses are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The particular requirements of this (Part 3/Sec 11) of NEC apply to the wiring system of furniture (and similar fitments) which is connected to the electrical installation.
Examples are beds, cupboards, desks and shop display cases, in which electrical equipment such as luminaires, installation couplers according to IEC 61535, socket-outlets, switching devices and wiring systems are installed.
The requirements of this part apply to all kinds of furniture, regardless of the connection to the electrical installation of the building, as long as the furniture together with its electrical installation is not the subject of another IEC publication.
The requirements of this part apply to electrical equipment of furniture connected to a supply with a nominal voltage U o not exceeding 230 V and a total load current not exceeding 32 A.
These requirements do not apply to electrical appliances and equipment specifically designed for installation in furniture and which are the subject of other IEC standards, for example radios, TV receivers, refrigerators and laboratory tables, installed in the furniture and ready for connection to the electrical installations of buildings via plugs and socket-outlets. For special locations, other specific requirements may apply, for example see Part 3/Section 2 of NEC.
2 REFERENCES
IS/IEC/ISO Number
Title
732 : 2019
Code of practice for electrical wiring installations (fourth revision)
14772 : 2020
General requirements for enclosures for accessories for household and similar fixed electrical installations — Specification
IEC 60227-3 : 1997 Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V — Part 3: Non-sheathed cables for fixed wiring
IS/IEC/ISO Number Title
IEC 60227-5 : 2011 Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V — Part 5: Flexible cables (cords)
IEC 60245-1 : 2007 Rubber insulated cables — Rated voltages up to and including 450/750 V: Part 1 General requirements
IEC 60245-4 : 2011 Rubber insulated cables — Rated voltages up to and including 450/750 V-Part 4 Cords and flexible cables
IEC 61535 : 2019 Installation couplers intended for permanent connection in fixed installations
IEC 62440 : 2008 Electric cables with a rated voltage not exceeding 450/750 V — Guide to use
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
3.1 Furniture — Movable or immovable articles such as desks, chairs, tables and work benches, cupboards, shelves and beds which are used for activities associated with work or leisure.
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.2 Protection for Safety – Protection against Electric Shock
4.2.15 Additional Protection
4.2.15.1 Additional protection: residual current protective devices (RCDs)
4.2.15.1.1
Add the following:
The electrical installation of the furniture shall be protected by an RCD with a rated residual operating current not exceeding 30 mA.
This Part 3 Section 12 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 12 clauses are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The particular requirements of this section (Part 3/Sec 12) of NEC apply to the selection and erection of extralow voltage lighting installations supplied from sources with a maximum rated voltage of 50 V a.c. or 120 V d.c.
NOTES
1 For the definition of an extralowvoltage lighting system see IEC 60598-2-23.
2 a.c. voltages are given as r.m.s. values.
2 REFERENCES
732 : 2019
Code of practice for electrical wiring installations (fourth revision)
IEC 60570 : 2019
Electrical supply track systems for luminaires
IEC 60598-2-23 : 2020
Luminaires — Part 2-23: Particular requirements — Extra-low-voltage lighting systems for filament lamps
IEC 60998-2-1 : 2002
Connecting devices for low-voltage circuits for household and similar purposes — Part 2-1: Particular requirements for connecting devices as separate entities with screw-type clamping units
IEC 60998-2-2 : 2002
Connecting devices for low-voltage circuits for household and similar purposes — Part 2-2: Particular requirements for connecting devices as separate entities with screwless-type clamping units
IEC 61347-2-2 : 2011
Lamp controlgear— Part 2-2: Particular requirements for d.c. or a.c. supplied electronic step-down convertors for filament lamps
IEC 61347-2-13 : 2016
Lamp controlgear — Part 2-13: Particular requirements for d.c. or a.c. supplied electronic controlgear for LED modules
IS/IEC 61558-2-6 : 1997
Safety of power transformers, powersupply units and similar: Part 2 Particular requirements, Section 6 Safety isolating transformers for general use
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1 Protection for Safety
4.2 Protection against Electric Shock
4.2.14 Protective Measure: Extra-Low-Voltage provided by SELV and PELV
For extralowvoltage lighting installations only SELV shall be applied. Where bare conductors are used, the maximum voltage shall be 25 V a.c. or 60 V d.c. according to 4.2.14.4.5.
The source of the ELV lighting installation can be one of the following:
A safety isolating transformer complying with IS/IEC 61558-2-6 : 2009.
Parallel operation of transformers in the secondary circuit is allowed only if they are also paralleled in the primary circuit and the transformers have identical electrical characteristics.
A safety isolating convertor complying with Annex I of IEC 61347-2-2 : 2000, for incandescent lamps, or IEC 61347-2-13 : 2006, Annex I for LED.
Parallel operation of convertors is not permitted.
4.3 Protection against Thermal Effects
4.3.2.3 Locations with risks of fire due to the nature of processed or stored materials
Add the following:
The manufacturer’s installation instructions shall be followed, including those relating to mounting on flammable or non-flammable surfaces.
Luminaires and their accessories shall be designed and placed to avoid harmful heating of materials or surroundings.
NOTE — See also IS 732 : 2019, 5.5.3.
Add the following:
4.3.2.106 Fire risk of transformers/convertors
Transformers shall be either:
protected on the primary side by the protective device required in 4.3.2.107.2; or
shortcircuit proof (both inherently and noninherently), see IS 732, (Annex EE, Annex A) for the symbol.
Electronic convertors shall comply with IEC 61347-2-2 : 2000 and, for LED-modules with IEC 61347-2-13 : 2006, Annex I.
NOTE — It is recommended that converters marked with the symbol are used. The temperature value limitation (of the convertor) within the triangle is given only as an example.
4.3.2.107 Fire risk due to short-circuit
4.3.2.107.1 If both circuit conductors are uninsulated, they shall be either:
a) provided with a special protective device complying with the requirements of 4.3.2.107.2;
b) supplied from a transformer or a convertor, the power of which does not exceed 200 VA; or
c) conductors of a system complying with IEC 60598223 : 1996.
4.3.2.107.2 The special protective device against the risk of fire shall comply with the following requirements:
a) continuous monitoring of the power demand of the luminaires;
b) automatic disconnection of the supply circuit within 0.3 s in case of a short-circuit or failure which causes a power increase of more than 60 W;
c) automatic disconnection while the supply circuit is operating with reduced power (for example by gating control or a regulating process or a lamp failure) if there is a failure which causes a power increase of more than 60 W;
d) automatic disconnection in the case of switching on the supply circuit if there is a failure which causes a power increase of more than 60 W; and
SP 30 : 2023
e) the special protective device shall be fail-safe.
NOTE — Account needs to be taken of starting currents.
4.4 Protection against Overcurrent
4.4.1.104 Protection against overcurrent in ELV lighting installations
The use of selfresetting overcurrent protective devices is permitted only for transformers up to 50 VA.
Insulation piercing connectors and termination wires, with counterweights, hung over suspended conductors shall not be used.
In the case of a suspended system with bare conductors it shall be fixed to walls or ceilings by insulated fixing means and shall be continuously accessible throughout the route.
5.2.6 Current-Carrying Capacities
Add the following:
NOTE — Values of current-carrying capacity for uninsulated conductors are under consideration.
5.2.7 Cross-Sectional Areas of Conductors
Replace the text by the following:
The minimum cross-sectional area of the ELV conductors which are connected to the output terminals or terminations of transformers/convertors shall be chosen according to the load current.
In the case of systems with luminaires suspended from the conductors, the minimum cross-sectional area of the ELV conductors which are connected to the output terminals or terminations of transformers/convertors shall be 4 mm2, for mechanical reasons.
5.2.8 Voltage Drop in Consumers’ Installations
Replace the text by the following:
In ELV lighting installations, the voltage drop between the transformer and the furthest luminaire shall not exceed 5 percent of the nominal voltage of the ELV installation.
5.3 Isolation, Switching and Control
5.3.1 General and Common Requirements
Add the following:
5.3.1.104
Protective devices shall be easily accessible.
Protective devices may be located above false ceilings, which are movable or easily accessible, provided that information is given about the presence and location of the device.
If the identification of a protective device for a circuit is not immediately evident, a sign or diagram (label) close to the protective device shall identify the circuit and its purpose.
SELV sources, protective devices or similar equipment mounted above false ceilings or in a similar place shall be permanently connected.
SELV sources and their protective devices shall be installed so as to:
a) avoid mechanical stress on their electrical connections; and
b) be adequately supported; and
c) avoid overheating of the equipment due to thermal insulation.
5.3.7 Isolation and Switching
Where transformers are operated in parallel, the primary circuits shall be permanently connected to a common isolating device.
SP 30 : 2023
Section 13 Requirements for Special Installations or Locations — Community Facilities and Workplaces
Community facilities and work places can be of various types depending on the size of the civil structure or the extent of activity involved in the building. High-rise buildings housing office complexes are common, calling for a coordinated planning while designing the electrical services therein. In small buildings with comparatively moderate loads, supply is normally at medium voltage and the distribution of power is less complex. However, in the case of multi-storied office-cum-commercial complex, where the large number of amenities is to be provided calls for a more complex distribution system. Some of such buildings has to incorporate a standby/emergency power plant for essential service needs.
For the purpose of this part of NEC Part 3/Sec 13, the requirements of IS 732 : 2019 shall apply. This Part 3/Sec 13 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 13 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
This section (Part 3/Sec 13) of NEC provides additional requirements for electrical installations applicable to community facilities and workplaces.
Typical examples of community facilities and workplaces are listed below:
Access routes and escape routes are part of the above-mentioned examples.
The necessity of providing safety services in special buildings and areas may be governed by national regulations which may contain more stringent requirements.
NOTE — For safety services see 5.6 of IS 732.
2 REFERENCES
IS Number Title
732 : 2019 Code of practice for electrical wiring installations
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
3.1 Community Facility
Location, building or part of a building open to the public.
3.2 Workplace
Location, building or part of a building in which employees conduct activities relating to their employment.
4 PROTECTION FOR SAFETY
4.1.2.3 Protection Against Thermal Effects
4.3.2 Precautions where Particular Risks of Fire Exist
4.3.2.2 Conditions of evacuation in an emergency
Add the following:
4.3.2.2.101 For communal facilities and workplaces the appropriate condition (BD2, BD3 of BD4) shall be established and the appropriate sub clauses of 4.3 of IS 732 have to be taken into account.
4.3.2.3.7
Add the following:
4.3.2.3.7.101 Motors which are not supervised continuously shall be protected by a thermal protective device or shall be impedance protected motors.
This requirement does not apply to:
a) motors in workplaces with a nominal power less than 500 W; and
b) motors which will not be overheated in the event of stalling.
NOTE — In areas such as some places of entertainment it may be necessary to ensure lighting cannot be operated by unauthorized persons.
Section 14 Requirements Electrical Installations in Caravans and Motor Caravans
The particular requirements of this section apply to the electrical installations in caravan/camping parks and similar locations that provide connection points for supplying leisure accommodation vehicles (including caravans) and tents. This section contains specific requirements for the electrical installations in caravans and motor caravans.
For the purpose of this part of NEC Part 3 Section 14, the requirements of IS 732 : 2019 and shall apply. This Part 3 Section 14 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 14 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
1.1 The particular requirements of this section of the code (Part 3/Section 14) apply to electrical installations in caravans and motor caravans.
They apply to those electrical circuits and equipment intended for the use of the caravan for habitation purposes.
1.2 They do not apply to those electrical circuits and equipment for automotive purposes.
They do not apply to the electrical installations of mobile homes, residential park homes and transportable units.
NOTES
1 For mobile homes and residential park homes the general requirements apply.
2 For transportable units, see 3 of IEC 60364-7-717. For the purposes of this document, caravans and motor caravans are referred to as “caravans”.
The particular requirements of some parts from the NEC Part 3 can also apply to such installations in caravans, for example, NEC Part 3 Section 2.
2 REFERENCES
IS/IEC/ISO Number Title
732 : 2019 Code of practice for electrical wiring installations
IEC 60038 : 2009 IEC standard voltages
IEC 60332-1-2 : 2015 Tests on electric and optical fibre cables under fire conditions — Part 1-2: Test for vertical flame propagation for a single insulated wire or cable — Procedure for 1 kW pre-mixed flame
IS/IEC 60947-2 : 2016 Low-voltage switchgear and controlgear — Part 2: Circuit-breakers (first revision)
12640 (Part 1) : 2016 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs): Part 1 General rules
12640 (Part 2) : 2016 Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs): Part 1 General rules
SP 30 : 2023
IS/IEC/ISO Number Title
14927 Cables trunking and ducting systems for electrical installations (Part 1 and Part 2) : 2001
IEC 61084 (all parts) Cables trunking and ducting systems for electrical installations
IEC 61386-25 : 2011 Conduit systems for cable management — Part 25: Particular requirements Conduit fixing devices
16205 : 2017 Conduit systems for cable management
IS/IEC 60309-2 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 2 Dimensional interchangeability requirements for pin and contact-tube accessories
IEC 62423 : 2009 Type F and Type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses
3 TERMINOLOGY
For the purposes of this standard, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
3.1 Leisure Accommodation Vehicle — Unit of living accommodation for temporary or seasonal occupation that may meet the requirements for the construction and use of road vehicles.
3.2 Caravan—Trailer leisure accommodation vehicle, used for touring, that meets the requirements for the construction and use of road vehicles.
3.3 Motor Caravan—Self-propelled leisure accommodation vehicle, used for touring, that meets the requirements for the construction and use of road vehicles.
NOTE — A motor caravan is either adapted from a series production vehicle, or designed and built on an existing chassis, with or without the driving cab, the accommodation being either fixed or dismountable.
3.4 Mobile Home— Transportable leisure accommodation vehicle that includes means for mobility but does not meet the requirements for the construction and use of road vehicles.
3.5 Residential Park Home—Factory produced relocatable dwelling.
4 PURPOSES, SUPPLIES AND STRUCTURE
For requirements of purposes supplies and structure, relevant items under 4.1 of IS 732 may be referred. Additional requirements have been mentioned against each item below.
4.1 Supplies
4.1.1 General
The nominal supply system voltage shall be selected from IEC 60038.
The nominal a.c. supply voltage of the installation of the caravan shall not exceed 230 V single-phase, or 400 V three-phase.
The nominal d.c. supply voltage of the installation of the caravan shall not exceed 48 V.
NOTE — This implies that there cannot be any taps or junctions in this connection.
Consideration should be given to the characteristics of the load in selection of the type of RCD.
5.2 Protection Against Overcurrent
5.2.1 Final Circuits
Each final circuit shall be protected by an overcurrent protective device which disconnects all live conductors of that circuit.
Cable trunking systems and cable ducting systems shall comply with the relevant part of IEC 61084 (all parts).
6.2.2 Selection and Erection of Wiring Systems in Relation to External Influences
6.2.2.1 Vibration (AH)
6.2.2.1.1 As the wiring will be subjected to vibration, all wiring shall be protected against mechanical damage either by location or by enhanced mechanical protection. Wiring passing through metalwork shall be protected by means of suitable bushes or grommets, securely fixed in position. Precautions shall be taken to avoid mechanical damage due to sharp edges or abrasive parts.
6.2.2.2 Other mechanical stresses (AJ)
6.2.2.2.1 All cables, unless enclosed in rigid conduit, trunking, or flexible conduit shall be supported at intervals not exceeding 0.4 m for vertical runs and 0.25 m for horizontal runs.
6.2.3 Cross-Sectional Areas of Conductors
6.2.3.1 The cross-sectional area of every conductor shall be not less than 1.5 mm2 copper or copper equivalent.
6.2.4 Electrical Connections
Connections between cables or conductors shall only be made in connecting boxes or by electrical equipment.
NOTE — Connections also include junctions and taps.
6.2.5 Proximity of Wiring Systems to Other Services
6.2.5.1 Proximity to non-electrical services
6.2.5.1.1 Add the following at the end of 5.2.11.3.1 of IS 732:
No electrical equipment including wiring systems, except:
a) ELV (extra low voltage) equipment for gas supply control; and
b) cables running through a gas compartment without connection shall be installed in any gas cylinder compartment.
Such electrical installations and components shall be constructed and installed so that they are not a potential source of ignition.
Where cables have to run through such a compartment such cables shall be protected against mechanical damage by installation within a continuous conduit or duct passing through the compartment at a height of not less than 500 mm above the base of the cylinders.
Where installed in a position where it is likely to be subject to mechanical damage this conduit or duct shall be able to with stand an impact equivalent to AG3 without visible physical damage.
6.3 Isolation, Switching and Control
6.3.1 Isolation and Switching
6.3.1.1 Isolation
6.3.1.1.1 Each independent installation shall be provided with its own main isolating switch which shall disconnect all live conductors and which shall be suitably placed in a readily accessible location in the caravan. In an installation consisting of only one final circuit, the isolating switch may be the overcurrent protection device providing such a device meets the requirements for isolation.
6.3.1.1.1.1 A notice in durable material shall be permanently fixed in the vicinity of the main isolating switch inside the caravan, bearing the text shown in Annex A in the official language(s) of the country in which the caravan is to be sold for the first time, in indelible and easily legible characters.
6.4 Earthing Arrangements and Protective Conductors
6.4.1 Protective Conductors
6.4.1.1 Types of protective conductors
Circuit protective conductors shall be incorporated in a multicore cable or in a conduit or trunking together with the live conductors.
6.4.2 Protective Bonding Conductors for Connection to the Main Earthing Terminal
The terminations of protective bonding conductors connecting the conductive structure of the unit shall be accessible and protected against corrosion.
6.5 Other Equipment
6.5.1 General Requirements
6.5.1.1 Inlets
6.5.1.1.1 Any a.c. electrical inlet on the caravan shall be an appliance inlet complying with IS/IEC 60309-2.
6.5.1.1.2 The inlet, if any, shall be installed
a) not more than 1.8 m above ground level,
b) in a readily accessible position,
c) have a minimum protection of IP44 with or without a connector engaged, and
d) the inlet shall not protrude significantly beyond the body of the caravan.
6.5.1.2 Accessories
6.5.1.2.1 Every low-voltage socket-outlet, other than a shaver socket-outlet, shall incorporate an earth contact.
6.5.1.2.2 Every socket-outlet supplied at extra-low voltage shall have its voltage visibly marked.
6.5.1.2.3 Where an accessory is located in a position in which it is exposed to the effects of moisture it shall be constructed or enclosed so as to provide a degree of protection not less than IPX4.
6.5.1.2.4 Each luminaire in a caravan shall preferably be fixed directly to the structure or lining of the caravan. Where a pendant luminaire is installed in a caravan, provision shall be made for securing the luminaire to prevent damage when the caravan is moved.
SP 30 : 2023
Accessories for the suspension of pendant luminaires shall be suitable for the mass suspended and the forces associated with vehicle movement.
6.1.5.2.5 A luminaire intended for dual voltage operation shall comply with the appropriate standard.
6.1.5.2.6
Table 1Cross-sectional Areas of Flexible Cords and Cables for Caravan Connection (Clause 6.1.5.2.6)
Rated Current
Minimum Cross-Sectional Area
A
mm<sup>2</sup>
16
2.5
25
4
32
6
63
16
100
35
The appliance inlet installed under 6.5.1.1 shall comply with IS/IEC 60309-2, and the means of connection to the caravan pitch socket-outlet shall comprise the following:
a) a plug complying with IS/IEC 60309-2.
b) a flexible cord or cable.
of 25 m (± 2 m) continuous length,
of harmonized code designation IEC 60245 (code 57) or equivalent,
incorporating a protective conductor, with a colour identification according to the appropriate IEC standard, and
with a cross-sectional area in accordance with Table 1, and
c) a connector complying with IS/IEC 60309-2.
The means of connection to the caravan pitch socket-outlet need not be supplied with the caravan.
B-2.1.2.1 The ELV installation should be so installed that the protective measures of the LV installation against direct contact, or in case of indirect contact are not impaired.
It should be ensured that operating currents of the ELV installation do not flow in the protective conductors of the LV installation.
B-2.2 Wiring Systems
B-2.2.1 Types of Wiring Systems
Cables should be of stranded construction and should comply with IEC 60227 (all parts), IEC 60245 (all parts) or IS/ISO 6722 (all parts).
B-2.2.2 Current-Carrying Capacities
The cross-sectional areas of the conductors selected for the fixed wiring should be in accordance with Annex C. Annex C does not apply to sensor and data lines.
B-2.2.3 Voltage Drop in Consumers’ Installations
Under normal service conditions, the voltage at the terminals of any fixed current-using equipment should be greater than the lower limit corresponding to the IEC standard relevant to the equipment. Where the equipment is not the subject of an IEC standard, the voltage at the terminals should be such as not to impair the safe functioning of that equipment. In the absence of precise data, a voltage drop of 0.8 V from the power supply to the equipment may be allowed.
The charging current Ic [A] to determine the voltage drop is established by Formula (B.1).
Ic=tc⋅0.1(B.1)
where,
I c = the charging current, in A;
c = the battery capacity, in Ah; and
t = the period, in h.
B-2.2.4 Proximity of Wiring Systems to Other Services
B-2.2.4.1 Proximity to non-electrical services
B-2.2.4.1.1 Cable runs and LPG installations
Cables including those used for automotive purposes should not be run through a compartment or housing intended for liquefied petroleum gas storage cylinders. Where cables have to run through such a compartment or housing, they should be run at a height of not less than 500 mm above the base of the cylinders, and such cables should be protected against mechanical damage by installation within a continuous gas tight conduit or duct passing through the compartment.
Where installed, this conduit or duct should be able to withstand an impact equivalent to AG3 without visible physical damage.
ELV cables and electrical equipment are only to be installed within the LPG cylinder compartment or housing if the installation serves the operation of the gas cylinders (for example, indication of empty gas cylinders) or is for use within the compartment or housing. Such electrical installations and components should be constructed and installed so that they are not a source of ignition and are in accordance with the relevant standards for any hazardous area classification of the compartment or housing.
B-2.3 Isolation, Switching and Control
B-2.3.1 Devices for Protection against Overcurrent
B-2.3.1.1 General requirements
B-2.3.1.1.1 The overcurrent protective device for the power supply from the towing vehicle should be installed as near as possible to the auxiliary battery, but in no case more than 1 000 mm away. The overcurrent protective device for the auxiliary battery should be fitted at the end of the battery cable and before the fixed installation. The ELV output of the transformer/rectifier unit and of the d.c. generator should be provided with an overcurrent protective device unless this is already incorporated within the unit or generator. The protective device should be installed as near as possible to the unit or generator and, in all cases, upstream of the distribution circuits.
B-2.3.1.1.2 Overcurrent protective devices should be either fuse links according to ISO 8820 (all parts) or suitable miniature circuit-breakers.
B-2.3.1.1.3 Fuses should be physically protected against accidental mechanical damage.
B-2.3.1.1.4 Overcurrent protective devices should not be fitted in a fuel storage compartment or fuel storage housing intended for the storage of liquefied petroleum gas cylinders or in the compartment for housing an auxiliary battery.
B-2.4 Other Equipment
B-2.4.1 General Requirements
B-2.4.1.1 Inlets
The inlet, when the plug is disconnected, should be protected against the ingress of water, foreign bodies and accidental damage.
B-2.4.1.2 Accessories
The means of connection to the towing vehicle should be supplied with the caravan and comprise the following:
e) a plug complying with IS 13461 and IS 13460 or ISO 11446 (all parts), and
f) a flexible cord or cable with the number of cores with the minimum cross-sectional area and the allocation according to Table B-1 and a length not exceeding 5 m, and
g) a connectorcomplying with IS 13461 and IS 13460 or ISO 11446 (all parts).
Table B-1Functional Allocation and Cross-sectional Areas of Cores for Caravan Connectors (Clause B-2.4.1.2)
Core No.
Function
Contact Numbers
Minimum Cross-sectional Area mm²
ISO 11446
IS 13461
1
Left-hand direction – indicator light
1
1
1.5
2
Rear fog light
2
2
1.5
3
Common return for core nos. 1,2, 4, 5, 6, 7 and 8
3a
3a
2.5
4
Right-hand direction – indicator light
4
4
1.5
5
Right hand-rear position and marker lights, and rear-registration-plate illumination device
5
5
1.5
6
Stop lights
6
6
1.5
7
Left-hand rear position and marker lights, and rear-registration-plate illumination device
7
7
1.5
IS 13460
8
Reversing light
8
1
1.5
9
Continuous power supply
9
4
2.5
10
Power supply controlled by ignition switch
10
6
2.5
11
Return for core No. 10
11a
7a
2.5
12
Coding for coupled trailer
12
2
-
13
Return for core No. 9
13a
3a
2.5
14
No allocation
-
5
1.5
a These return circuits should not be electrically connected in the trailer.
B-2.4.1.3 Auxiliary batteries
B-2.4.1.3.1 Type of battery
An auxiliary battery should be of the rechargeable type.
NOTE — Non-rechargeable batteries are not auxiliary batteries. They can be used in caravans, provided that they are used in circuits separated from other sources of electrical supply.
505
B-2.4.1.3.2 Capacity
An auxiliary battery should have a minimum capacity of 60 Ah at a 20 h discharge period.
It is recommended to use a battery designed to be discharged over long periods at a relatively low current.
B-2.4.1.3.3 Terminals
Auxiliary battery terminals should be clearly and durably marked “+” and “–”. Connections to auxiliary battery terminals should be securely clamped or bolted to ensure continuous contact and should be insulated unless the auxiliary battery is provided with an insulating device.
B-2.4.1.3.4 Location
An auxiliary battery should be placed in a separate compartment with easy access for maintenance or removal. The battery should be secured to prevent movement, for example when the caravan is in motion.
B-2.4.1.3.5 Auxiliary battery compartment
A tray should be installed under an auxiliary battery if the electrolyte of this battery is liquid. The tray should be sufficient to hold 20 percent of the volume of the electrolyte.
The interior of an auxiliary battery compartment should be ventilated and protected against the corrosive effects of acid-laden gases, by one of the following methods:
h) installing a sealed auxiliary battery that incorporates an external ventilating kit that is taken to the exterior of the caravan;
j) installing an auxiliary battery in an enclosed battery compartment that is protected internally against corrosion and is ventilated to the exterior of the caravan by means of a suitable tube with a minimum inside diameter of 10 mm at the top of the auxiliary battery compartment in accordance with the battery manufacturer’s instructions or as supplied by the manufacturer of the auxiliary battery; or
k) ventilating the compartment at low-level and high-level to the exterior of the caravan and constructing the interior of the compartment, including the sides of the ventilator openings, of acid-resistant material or providing it with an anti-corrosive finish. If the compartment opens into the interior of the caravan, the lid should provide an air seal. The minimum size of ventilation should be not less than 80 mm2 at low level and not less than 80 mm2 at high level.
If an auxiliary battery is not provided, then the position and instructions for the installation of the battery and compartment, in accordance with a), b) or c) of this sub-clause, should be included in the instructions for use and a notice should be fixed in or near the proposed location stating: “For instructions on auxiliary battery installation, see the instructions for use”.
When the manufacturer makes no provision for the installation of an auxiliary battery, the following statement should be made in the instructions for use: “This caravan has not been designed to accommodate an auxiliary battery. Do not fit one”.
B-2.4.1.3.6 Auxiliary battery cables
Cables from an auxiliary battery should be protected by additional sheathing or taping up to the overcurrent protective device.
B-2.4.1.3.7 Warning notice
A warning notice should be fixed in a prominent position near the auxiliary battery or displayed on the lid of the auxiliary battery compartment. This warning should be in the official language(s) of the country in which the caravan is to be sold and should state: “Switch off all appliances and lamps before disconnecting the auxiliary battery.”
The auxiliary battery compartment should be additionally marked “Smoking prohibited” in accordance with IS 12349 and in the language(s) of the country in which the caravan is to be sold.
B-2.4.1.4 Other sources of supply
B-2.4.1.4.1 Generators and transformer/rectifier units
If a supply is obtained from a generator or from a low-voltage supply via a transformer/rectifier unit, the extra-low voltage at the output terminals of the supply unit should be maintained between 11 V minimum and 15 V maximum with applied loads varying from 0.5 A minimum up to the maximum rated load of the supply unit. Over the same load range, alternating voltage ripple should not exceed 1.2 Vpp.
SP 30 : 2023
B-2.4.1.4.2 Regenerative sources
Regenerative energy sources, such as wind energy, solar energy, should be installed only for charging batteries and such sources should only generate extra-low voltage.
Regenerative energy sources should only be operated with a device which prevents overcharging of the battery (ies).
B-2.4.1.5 Charging of auxiliary battery and operation of refrigerator
B-2.4.1.5.1 The circuit to charge an auxiliary battery should be separate from a circuit to operate a refrigerator.
B-2.4.1.5.2 The charging circuit for an auxiliary battery should be energized only when the engine of the towing vehicle is running.
B-2.4.1.6 Terminal block
If the connection between the connecting cable(s) and the caravan’s fixed wiring is by means of a terminal block, it should have a protective cover. If the terminal block is positioned externally it should have a cover providing a degree of protection of not less than IP34 as given in IS/IEC 60529.
B-2.4.1.7 Appliances
B-2.4.1.7.1 General
The caravan manufacturer’s technical specification should state whether an ELV appliance is suitable for use with a supply obtained from a d.c. generator or a transformer/rectifier unit.
Appliances suitable for operation on both 12 V a.c. and 12 V d.c. are permitted provided that the a.c. and the d.c. systems are segregated and interconnection is prevented.
B-2.4.1.7.2 Selection and connection of appliances
All appliances should be fitted and connected in accordance with the appliance manufacturer’s instructions. Where polarity-sensitive appliances are fitted and connected, only those that have terminals clearly marked “–” and “+”, or that have two conductors, indicating polarity by colour or by identification tags or sleeves marked “–” and “+”should be used.
B-2.4.1.8 Socket-outlets
ELV socket-outlets should be two pole non-reversible and should be of a different type from those provided for any low-voltage installation. The voltage and maximum power rating of the circuit should be stated on or adjacent to the socket-outlets.
B-2.4.1.9 Battery charger
If a battery charger is connected to a low-voltage a.c. supply, it should comply with the relevant clauses of IEC 60335-2-29. The d.c. output should either be electronically regulated or the maximum d.c. output of the charger in A should be limited to 10 percent of the capacity of the auxiliary battery in Ah at 20 h discharge rate.
B-2.4.1.10 External lights
Lights, such as door lamps, fixed outside on a caravan should be constructed or enclosed to provide protection against the ingress of water with a degree of protection of not less than IP34 according to IS/IEC 60529.
A=
Uvρ⋅L⋅I
(C.1)
where
A = the cross-sectional area of conductor, in mm2;
ρ = the resistivity of copper (0.019 89 Ω mm2/m at 5 0 ° C ) ;
L = the total length (feed and return cable) of the conductors, in m;
I = the total current, in A ; and
U v = the permissible voltage drop.
(0.3 V for auxiliary battery charging cables, 0.8 V for fixed wiring cables).
With intermediate values, the result of the calculation should be rounded to the next higher cross-sectional area.
C-2 The graphs in Fig. C-1 and Fig. C-2 and Formula (C-1) are based on a conductor operating temperature of 5 0 ° C
If cables are installed for use under conditions of temperatures higher than 5 0 ° C the minimum cross-sectional area of the conductors should be increased.
C-3 If the appliance manufacturer requires a voltage drop which is different from 0.3 V or 0.8 V, this value should be inserted for U v in Formula (C-1).
Section 15 Supplies for Electric Vehicles
Electric vehicle supply equipment (EVSE) supplies electricity to an electric vehicle (EV). Commonly called charging stations or charging docks, they provide electric power to the vehicle and use that to recharge the vehicle’s batteries. EVSE systems include the electrical conductors, related equipment, software, and communications protocols that deliver energy efficiently and safely to the vehicle. Electric vehicle charging is a new load for low voltage electrical installations that can present some challenges.
This section shall cover the requirements for supplies of electrical vehicles.
For the purpose of this part of NEC Part 3 Section 15, the requirements of IS 732 : 2019 shall apply.
This Part 3 Section 15 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 15 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable.
The section of Part 3 supplement, modify or replace certain of the general requirements contained in IS 732.
The clause numbering appearing after 3.3 refers to the corresponding parts or clauses of IS 732. Numbering of clauses does not, therefore, necessarily follow sequentially. Numbering of additional text is shown by the addition of “.101 (Eg 3.3.4.4.5.5.101) & 201 (Eg. 3.3.3.201), etc”. Numbering of figures and tables takes the number of this part followed by a sequential number. For annexes, the numbering of figures and tables takes the letter of the annex, the number of the part and a sequential number.
1 SCOPE
The particular requirements of this section (Part 3/Sec 15) apply to:
a) circuits intended to supply energy to electric vehicles, and
b) circuits intended for feeding back electricity from electric vehicles.
Circuits covered by this standard are terminated at the connecting point.
1 The requirements for EV supply equipment for conductive charging and the relevant charging modes are described in IS 17017 (all parts). The requirements for EV supply equipment for wireless power transfer are described in IEC 61980 (all parts).
2 This standard does not cover the assessment of the risk of explosion due to the possible production of hydrogen/other flammable gases during the battery recharging phase.
3 Requirements specified in electricity regulation (with amendments) shall be complied.
2 REFERENCES
IS/IEC/ISO Number Title
732 : 2019 Code of practice for electrical wiring installations
IS/IEC 60309-1 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 1 General requirements
IS/IEC 60309-2 : 2002 Plugs, socket-outlets and couplers for industrial purposes: Part 2 Dimensional interchangeability requirements for pin and contact-tube accessories
IS/IEC 60947-2 : 2016 Low-voltage switchgear and controlgear: Part 2 Circuit-breakers
IS/IEC 60269 (all parts) Low voltage fuses
IS/IEC 60898 (all parts) Electrical accessories — Circuit-breakers for overcurrent protection for household and similar installations
IS/IEC/ISO Number
Title
IEC 60898-3 : 2019
Electrical accessories — Circuit-breakers for overcurrent protection for household and similar installations — Part 3: Circuit-breakers for d.c. operation
12640 (Part 1) : 2016
Residual current circuit-breakers without integral overvoltage protection for household and similar uses (RCCBs): Part 1 General rules
12640 (Part 2) : 2016
Residual current operated circuit-breakers with integral overvoltage protection for household and similar uses (RCBOs): Part 1 General rules
IS/IEC 61558-2-4 : 2009
Safety of transformers, reactors, power supply units and similar products for supply voltages up to 1 100 V: Part 2-4 Particular requirements and tests for isolating transformers and power supply units incorporating isolating transformers
17017 (all parts)
Electric vehicle conductive charging system
IEC 61851 (all parts)
Electric vehicle conductive charging system
IS 17050 : 2018/IEC 62262 : 2002
Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code)
IEC 62423 : 2009
Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses
IEC 62196 (all parts)
Plugs, socket-outlets, vehicle connectors and vehicle inlets — Conductive charging of electric vehicles
IEC 62196- 1 : 2014
Plugs, socket-outlets, vehicle connectors and vehicle inlets — Conductive charging of electric vehicles — Part 1: General requirements
IEC 62196-2 : 2016
Plugs, socket-outlets, vehicle connectors and vehicle inlets — Conductive charging of electric vehicles — Part 2: Dimensional compatibility and interchangeability requirements for a.c. pin and contact-tube accessories
IEC 61557-9 : 2014
Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. — Equipment for testing, measuring or monitoring of protective measures — Part 9: Equipment insulation fault location in IT systems
IEC 61557-8 : 2014
Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. — Equipment for testing, measuring or monitoring of protective measures — Part 8: Insulation monitoring devices for IT systems
IEC 61140 : 2016
Protection against electric shock — Common aspects for installation and equipment
IEC 60947-6-2 : 2007
Low-voltage switchgear and controlgear — Part 6-2: Multiple function equipment — Control and protective switching devices (or equipment) (CPS)
Under preparation. Stage at the time of publication IEC RFDIS 60364-8-2 : 2018.
Under preparation. Stage at the time of publication IEC TS BPUB 62196-4 : 2018
3 TERMS AND DEFINITIONS
For the purposes of this standard, in addition to definitions given in IS 732 the following terms and definitions shall apply.
3.1 Electric Vehicle Electric Road Vehicle EV— Any vehicle propelled by an electric motor drawing current from a rechargeable energy storage system (RESS), intended primarily for use on public roads.
3.2 Connecting Point —Terminating point in the fixed installation where energy is transferred to/from one electric vehicle.
EXAMPLE — A socket-outlet, a vehicle connector or a wireless power transfer device.
NOTE — to entry: The connecting point may be part of the fixed installed EV supply equipment.
3.3 Demand Factor — ratio, expressed as a numerical value or as a percentage, of the maximum demand of a circuit or a group of circuits within a specified period, to the corresponding total installed load of the circuit(s).
NOTE — In using this term, it is necessary to specify to which level of the system it relates.
3.4 EV Charging Station — Stationary part of EV supply equipment connected to the supply network.
3.5 EV Supply Equipment— Equipment or a combination of equipment, providing dedicated functions to supply electric energy from a fixed electrical installation or supply network to an EV for the purpose of charging.
3.6 Load Control— Electrical (energy) management system ensuring that the sum of load currents of dedicated circuits does not exceed a predetermined value.
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.6 Purposes, supplies and structure
4.1.5.6.1 Maximum Demand and Diversity
Add the following:
It shall be considered that in normal use each single connecting point is used at its rated current or at the configured maximum charging current of the charging station. The means for configuration of the maximum charging current shall only be made by the use of a key or a tool and only be accessible to skilled or instructed persons.
NOTE — For this application the demand factor of the final circuit supplying the connecting point (for example, the socket-outlet) is equal to 1.
Since all the connecting points of the installation can be used simultaneously, the diversity factor of the distribution circuit shall be taken as equal to 1 unless a load control is included in the EV supply equipment or installed upstream or a combination of both.
4.1.5.8 Conductor Arrangement and System Earthing
4.1.5.8.2.1 TN systems
Add the following:
In a TN system, a circuit supplying a connecting point shall not include a PEN conductor.
4.1.5.10 Division of Installation
Add the following:
A dedicated circuit shall be provided for the transfer of energy from/to the electric vehicle.
4.2 Protection For Safety - Protection Against Electric Shock
4.2.6 General Requirements
Replace the existing text by the following:
The protective measure obstacles as specified in B-2 of IS 732 shall not be applied.
The protective measure placing out of reach, as specified in B-3 of IS 732 may only be applied where an automatic connection system in accordance with IEC 61851 series used.
SP 30 : 2023
4.2.7 The protective measures as specified in Annex C of IS 732 : 2019 shall not be applied.
4.2.11 Protective Measure: Automatic Disconnection of Supply
4.2.11.3 Requirements for fault protection
4.2.11.3.3 Additional protection
Replace the existing text by the following:
Each a.c. connecting point shall be individually protected by a residual current device (RCD) with a rated residual operating current not exceeding 30 mA.
NOTE — This requirement implies that this RCD is not used for protecting other connecting points or current-using equipment.
4.2.13 Protective Measure: Electrical Separation
4.2.13.3 Requirements for fault protection
4.2.13.3.2
Replace the requirements as follows:
The separated circuit shall be supplied through an isolating transformer complying with IS/IEC 61558-2-4, and the voltage of the separated circuit shall not exceed 500 V.
4.1.2.6 Protection against Voltage Disturbances and Electromagnetic Disturbances
4.1.2.6.2
Add the following after the first paragraph:
A connecting point accessible to the public is considered as part of a public service and therefore shall be protected against transient overvoltages.
4.5.4 Measures Against Electromagnetic Influences
4.5.4.1 General
Add the following:
4.5.4.1.101 The equipment for wireless power transfer shall not impair the safety and the proper functioning of the electrical installation and shall be installed according to the manufacturer’s instructions.
Annex BB-2 Obstacles
Protection by obstacles shall not be used.
B-3 Placing Out of Reach
Protection by placing out of reach shall not be used.
6Verification
Under preparation. Stage at the time of publication IEC RFD IS 60364-8-2 : 2018.
6.2 Initial Verification
6.2.1 General
6.2.1.1
Add the following:
The existing installation which is influenced shall also be verified with respect to compliance with the requirements of IS 732 : 2019 (for example, requirements for protection against overcurrent due to the increase of load current).
6.2.1.5
Add the following:
NOTE — For periodic verification, follow CEA safety regulation.
Under preparation. Stage at the time of publication IEC RFDIS 60364-8-2 : 2018.
Section 16 Requirements for Operating or Maintenance Gangways
A gangway is a narrow walkway or platform that provides safe access to a ship, truck, or train. Gangways are typically used for two purposes: to allow passage or people and/or cargo to/from docks, moored marine vessels, or aircraft, or in the maintenance and loading/unloading of land-based trucks and trains. The models used for ships or boats are typically long so that they don’t slip off platforms or provide unsafe crossing for personnel walking on them and terms like “tower,” “truss,” or “telescoping” are added to better describe how and where the marine loading platforms are used.
For the purpose of this part of NEC Part 3 Section 16, the requirements of IS 732 : 2019 shall apply. This Part 3 Section 16 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 16 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
The requirements of this part of National electric code apply to basic protection and other aspects in restricted access areas with switchgear and controlgear assemblies, including requirements for operating or maintenance gangways.
2 REFERENCES
International Standard Title
732 : 2019 Code of Practice for Electrical Wiring Installations
4 FUNDAMENTAL PRINCIPLES, ASSESSMENT OF GENERAL CHARACTERISTICS
4.1.5.5 Assessment of general characteristics
Add the following requirements:
For restricted access areas the following apply:
a) restricted access areas shall be clearly and visibly marked by appropriate signs;
b) unauthorized persons shall not have access to restricted access areas; and
c) door(s) provided for closed restricted access areas shall allow easy evacuation to the outside by opening without the use of a key, tool or any other device which is not part of the opening mechanism.
517
4.2.8 Replace the paragraph with the following requirements:
In restricted access areas where it is not reasonably practicable to provide protective measures for basic protection (protection against direct contact) in accordance with IS 732, minimum distances are required.
NOTES
1 See 4.1.5.5 of IS 732 for assessment of general characteristics when deciding to use this method of protection.
2 In cases of protective devices with high ratings, such as a large circuit-breaker, greater distances may be necessary to permit withdrawal of the device.
4.2.8.101 Where the gangway has unprotected live parts arranged on one side only (see Fig. 1), the minimum distances shall be:
a) width of gangway between the wall and live parts 900 mm;
b) free passage in front of controls (handles, etc.) 700 mm;
c) height of live parts above the floor 2 500 mm.
Dimensions in millimetres
The 2 500 mm height above the floor given as the minimum distance to live parts applies only in the gangway where it is possible for persons to stand or walk.
Fig. 1 Gangways in Installations with Live Parts on One Side
SP 30 : 2023
4.2.8.102 Where the gangway has live parts on both sides (see Fig. 2), the minimum distances shall be:
a) width of gangway between live parts 1 300 mm;
b) minimum distance between the front of the handle and the live parts on the opposite side of 1 100 mm; the gangway
c) minimum free passage in front of controls (handles, isolation position of circuit-breakers, 900 mm; etc.)
d) height of live parts above the floor
2 500 mm.
Dimensions in millimetres
The 2 500 mm height above the floor given as the minimum distance to live parts applies only in the gangway where it is possible for persons to stand or walk.
Fig. 2 Gangways in Installations with Live Parts on Both Sides
5Selection and Erection of Electrical Equipment
5.1.3 Accessibility
Add the following paragraphs:
5.1.3.101 Requirements for operating and maintenance gangways
The width of gangways and access areas shall be adequate for work, operational access, emergency access, emergency evacuation and for the movement of equipment.
Gangways shall permit equipment doors or hinged panels to be opened to at least 90° (see also Annex A, A.1).
5.1.3.101.1 Restricted access areas where the protective measure of barriers or enclosures applies
Where the protective measure is provided by barriers or enclosures in accordance with 4.2 of IS 732, the following minimum distances apply (see Fig. 3):
a) width of gangways with barriers or enclosures between switch handles and circuit-breakers 600 mm; in position “isolation” or switch handles and the wall
b) width of gangway between barriers or enclosures and other barriers or enclosures, or 700 mm; barriers or enclosures and the wall
c) height of panelling above the floor
d) height of live parts above the floor
2 000 mm;
2 500 mm.
Dimensions in millimetres
NOTES
1 Where additional workspace is needed e.g. for special switchgear and controlgear assemblies, larger dimensions may be required. 2 The above dimensions apply after all parts of the panelling have been mounted and closed and to circuit-breakers in the position ‘‘isolation’’.
Fig. 3 Gangways In Installations Where the Protective Measure of Barriers or Enclosures Applies
SP 30 : 2023
5.1.3.101.2 Restricted access areas where the protective measure of obstacles applies
Where the protective measure of obstacles applies in accordance with IS 732, the following minimum distances apply (see Fig. 4):
a) width of gangway between obstacles and switch handles, or obstacles and the wall, or 700 mm; switch handles and the wall
b) height of panelling above the floor
c) height of live parts above the floor
2 000 mm;
2 500 mm.
Dimensions in millimetres
Fig. 4 Gangways in Installations where the Protective Measure of Obstacles Applies
SP 30 : 2023
5.1.3.101.3 Access of gangways
Gangways longer than 10 m shall be accessible from both ends.
NOTES
1 This may be accomplished by placement of the equipment a minimum of 700 mm from the end walls (see Fig. 5) or by providing an access door, if needed, on the opposite end wall. Closed restricted access areas with a length exceeding 20 m shall be accessible by doors from both ends.
2 For closed restricted access areas with a length exceeding 6 m, accessibility from both ends is recommended.
Dimensions in millimetres
Fig. 5 Examples of Positioning of Doors in Long Closed Restricted Access Areas
SP 30 : 2023
Annex A(Normative)
Additional Requirements for Closed Restricted Access Areas
A-1 Evacuation
To permit easy evacuation, the doors of any equipment inside the location shall close in the direction of the evacuation route. Gangways shall permit equipment doors or hinged panels to be opened to a minimum of 90° (see Fig. A-1).
NOTE — Fig. A-1, A-2 and A-3 show the minimum width of gangways and distances for passing in case of evacuation.
Dimensions in millimetres
*) A minimum width of 600 mm lies between the wall and the circuit-breaker in the “fully withdrawn” position.
Circuit-breaker in the “completely extracted and isolated” position
Handles (e.g. for controls or equipment)
Fig. A-1 Minimum Passing Width in Case of Evacuation – Case 1
For doors which can be fixed in the open position or circuit-breakers or equipment which are withdrawn fully for maintenance (position: completely extracted) a minimum distance of 500 mm shall be provided between the door edge or circuit-breaker/equipment edge and the opposite side of the gangway. (see Fig. A-2 and A-3).
NOTE — See Fig. A-3 for the minimum passing width in case of circuit-breaker in position: completely extracted.
Dimensions in millimetres
Fig. A-2 Minimum Passing Width in Case of Evacuation – Case 2
SP 30 : 2023
*) A minimum width gangway of 500 mm shall be provided between the wall and the circuit-breaker in the “fully withdrawn” position or the door which has been fixed in the open position.
Completely withdrawn circuit-breaker
Door fixed in open position
Doors giving access to gangways in closed restricted access areas shall open outwards (see Fig. 5) and they shall have the following minimum dimensions:
a) width: 700 mm;
b) height: 2 000 mm.
SP 30 : 2023
Annex CC-1 Non-conducting Location
Protection by non-conducting location shall not be used.
NOTE — This precludes the use of class 0 equipment.
C-2 Protection by Earth-free Local Equipotential Bonding
Protection by earth free local equipotential bonding shall not be used.
4.2.13 Protective Measure: Electrical Separation
Where the protective measure of electrical separation is used for supplying pleasure craft compliance with all the requirements of 4.2.13 and with 4.2.13.3.2 and 4.2.13.3.6 shall be ensured.
4.2.13.3.2 The circuit shall be supplied through a fixed isolating transformer complying with IS/IEC 61558-2-4. The protective conductor of the supply to the isolating transformer shall not be connected to the earth terminal in the socket-outlet supplying the pleasure craft.
NOTE — See Annex A.
4.2.13.3.6 Add the following:
The equipotential bonding of the pleasure craft shall not be connected to the protective conductor of the shore supply.
4Fundamental Principles, Assessment of General Characteristics
4.1 Protection for Safety
4.1.5.5 Assessment of general characteristics
4.1.5.6 Purposes, supplies and structure
4.1.5.9 Supplies
4.1.5.9.101 Voltage
The nominal supply voltage of temporary electrical installations in booths, stands and amusement devices shall not exceed 230/400 V a.c. in accordance with IS 12360/IEC 60038.
4.1.5.9.102 Supply from the public network
Irrespective of the number of sources of supply, the phase and neutral conductors from different sources shall not be interconnected. The instructions of the supply network operator shall be followed.
4.2 Protection against Electric Shock-Protection against Electric Shock in Normal Service - (Protection against Direct Contact, or Basic Protection)
4.2.11 Protection against indirect contact - Protection by automatic disconnection of supply
NOTE — For supplies to large a.c. motors, the use of RCDs with time delay is recommended.
4.2.11.4 TN system
If the supply is a TN system, only the TN-S system shall be used.
4.2.11.6 IT system
Where an alternative system is available, an IT system shall not be used. IT systems, however, may be used for d.c. applications in accordance with IEC 62020. Where an IT system is used, permanent earth fault monitoring shall be provided.
4.2.15.1 Additional protection by residual current devices
Except for emergency lighting, all final circuits for lighting, socket-outlets rated up to 32 A and portable equipment connected by means of flexible cable or cord with a current-carrying capacity of 32 A or less shall be additionally protected by RCDs with a rated residual operating current not exceeding 30 mA.
This requirement does not apply to socket-outlets supplied by a circuit incorporating one or more of the protective measures specified below:
a) protection by SELV;
b) protection by electrical separation;
c) protection by automatic disconnection of supply and reduced low voltage.
4.2.15.2 Supplementary equipotential bonding
4.2.15.2.101 In locations used for animals, supplementary equipotential bonding shall connect all exposed conductive parts and extraneous conductive parts which can be touched simultaneously to the protective conductor of the installation.
4.2.15.2.102 Isolation
Every separate temporary electrical installation for amusement devices and each distribution circuit supplying outdoor installations shall be provided with its own readily accessible and properly identified means of isolation.
4.2.101 Protection against Electric Shock in Normal Service
Protective measures against direct contact by means of obstacles (see Annex B, B-2 of IS 732 : 2019) and by placing out of reach (see Annex B, B-3 IS 732 : 2019) shall not be used.
4.2.102 Protection against Electric Shock in Case of a Fault
Protective measures against indirect contact by non-conducting location (see 4.2.11.3 of IS 732 : 2019) and by earth-free equipotential bonding (see Annex C, C-2 of IS 732 : 2019) shall not be used.
4.2.103 Choice of Protective Measures as a Function of external influences-Selection of Measures for Protection against Electric Shock in Relation to External Influences
For the application of the protective measure against indirect contact by automatic disconnection of supply, the conventional voltage limit in locations in which animals may be present is UL = 25 V a.c. r.m.s. or 60 V ripple-free d.c., or the maximum disconnecting time is that indicated in Table 48A of IEC 60364-4-481.
These conditions also apply to locations connected by conductive parts to the locations where animals may be present.
4.2.104 Choice of protective measures against indirect contact
4.2.104.1 Automatic disconnection of supply to the temporary structures shall be provided at the origin of the installation by RCDs with a rated residual operating current not exceeding 300 mA. These RCDs shall incorporate
a time delay in accordance with IS/IEC 60947-2 or be of the S-type in accordance with IS 12640-1/IEC 61008-1 or IS 12640-2/IEC 61009-1 for discrimination with RCDs protecting final circuits.
NOTE — The recommendation for additional protection relates to the increased risk of damage to cables in temporary locations.
4.2.104.2 In order to prevent all supplies from being disconnected and causing danger (including non-electrical danger by the loss of motive power or lighting), it may be necessary to utilise more than one circuit.
4.3.2 Protection against Fire
4.3.2.101 A motor which is automatically or remotely controlled and which is not continuously supervised shall be fitted with a manually reset protective device against excess temperature.
6Verification
531
The whole electrical installation shall be inspected and tested after each assembly on site.
Section 18 Requirements for Requirements for Heating Cables and Embedded Heating Systems
An embedded heating system functions by warming the floor or ceiling of a room. These objects then warm the air in the room. Some systems use electric heating panels to generate heat, which is radiated into rooms, other systems are thermal storage systems. The requirements apply to the installation of electric floor and ceiling heating systems which are erected both as direct acting heating or thermal storage systems. This section contains specific requirements for the installation of embedded heating systems which supplement the general requirements of that standard.
For the purpose of this part of NEC Part 3 Section 18, the requirements of IS 732 : 2019 shall apply. This Part 3 Section 18 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 18 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
This part of NEC applies to embedded electric heating systems for surface heating. It also applies to electric heating systems for de-icing or frost prevention or similar applications. Both indoor and outdoor systems are covered.
Heating systems for industrial and commercial applications complying with relevant parts of IS/IEC 60519, IEC 62395 and IS/IEC 60079 are not covered.
NOTE — Examples of heating systems covered by this standard are heating systems for walls, ceilings, floors, roofs, drainpipes, gutters, pipes, stairs, roadways, non-hardened compacted areas (e.g. football fields, lawns).
2 REFERENCES
Title
732 : 2019
Code of practice for electrical wiring installations
IS/IEC 60079-7 : 2015
Explosive atmospheres: Part 7 Equipment protection by increased safety “e”
IEC 60335-2-96 : 2019
Household and similar electrical appliances — Safety — Part 2-96: Particular requirements for flexible sheet heating elements for room heating
IEC 60364
Low-voltage electrical installations (all parts)
IEC 60800 : 2009 Heating cables with a rated voltage of 300/500 V for comfort heating and prevention of ice formation
3 TERMINOLOGY
For the purposes of this document, the following terms and definitions apply.
3.1 Thermal Storage Floor Heating System
Heating system in which, due to a limited charging period, a restricted availability of electrical energy is converted into heat and dissipated mainly through the surface of the floor to the room to be heated with an intended time delay.
SP 30 : 2023
3.2 Direct Heating System
Heating system which generates heat from electrical energy and dissipates it to the room to be heated with a response time being as low as possible.
3.3 Complementary Floor Heating
Direct heating system integrated into the floor construction, for example, in the border zones close to outer walls, which complements the heat dissipation of a thermal storage floor heating system.
3.4 Heating-Free Area
Area of a surface that is deliberately left free of all parts of the heating system.
3.5 Heating Cable
Cable with or without a shield or a metallic sheath, intended to give off heat for heating purposes.
3.6 Flexible Sheet Heating Element
Heating element consisting of sheets of electrical insulation laminated with electrical resistance material, or a base material on which electrically insulated heating wires are fixed.
3.7 Heating Unit
Heating cable or flexible sheet heating element with rigidly fixed cold leads or terminal fittings which are connected to the terminals of the electrical installation.
3.8 Cold Lead
Insulated cable or cord intended to connect the heating unit with the electrical installation.
3.9 Self-Limiting Heating Cable
Cable that cannot exceed 70 °C when tested according to IS/IEC 60079-7 and which does not require cold leads for connection to the electrical installation.
5Selection and Erection of Electrical Equipment
5.1 Common Rules
Switchgear and controlgear shall be placed in cabinets which can be opened only by the use of a key or a tool, except for those parts designed and intended to be operated by ordinary persons (Code BA1), as defined in Table 7 of IS 732.
5.1.4.2 Wiring systems
5.2.4 Types of Wiring Systems
5.2.4.9.101 Cables
529
Where appropriate, cables shall be of flexible construction.
Armoured cables or cables protected against mechanical damage shall be used wherever there is a risk of mechanical damage.
All temporary power distribution cables shall be multicore, except for circuits above 125 A where single-core cables may be used.
All cables shall meet the requirements of IEC 60332-1.
NOTE — Where enhanced performance is required, cables should meet the requirements of IEC 60332-3; where low smoke cables are needed, the minimum recommended performance is given in IEC 61034-2.
Cables shall have a minimum voltage designation of 450/750 V, except that, within amusement devices, cables and cords having a minimum voltage designation of 300/500 V may be used.
The routes of cables buried in the ground shall be marked at suitable intervals. Buried cables shall be protected against mechanical damage.
5.2.9 Electrical Connections
Joints shall not be made in cables and cords, except where necessary as a connection to a circuit. Any joint shall be made in an enclosure affording a degree of protection not less than IP4X or IPXXD.
Where strain may be transmitted to terminals, cable anchorage shall be provided.
5.3 Switchgear and Controlgear
5.3.7.3.2 Devices for isolation
Devices for isolation shall disconnect all phases, poles and the neutral.
5.3.7.3.2.101 General
Every electrical installation of a booth, stand or amusement device shall have its own means of isolation and over-current protection, which shall be readily accessible.
5.3.7.5.4.2 Emergency switching device
A separate circuit shall be used to supply such signs or lamps, which shall be controlled by an emergency switch. The switch shall be easily visible, accessible and marked in accordance with the requirements of the local authority.
5.3.7.5.4.2.101 Safety isolating transformers and electronic converters
Multiple connection safety isolating transformers shall comply with IS/IEC 61558-2-6 or provide an equivalent degree of safety.
A manually reset protective device shall protect the secondary circuit of each transformer or electronic converter (see IS 16504-1/IEC 60204-1).
Safety isolating transformers shall be mounted out of arm’s reach of the public and shall have adequate ventilation. Access by skilled or instructed persons for testing and protective device maintenance shall be provided.
Electronic converters shall conform to IEC 61046.
Enclosures containing rectifiers and transformers shall be adequately ventilated and the vents not obstructed when in use.
5.3.7.6.101 Socket-outlets and plugs
An adequate number of socket-outlets shall be installed to allow the user’s requirements to be met safely.
Not more than one flexible cable or cord shall be connected to a plug, unless the plug is specifically designed for multiple connection.
Multi-way plug-in type adapters shall not be used.
5.3.101 Electrical supply
At each amusement device, there shall be a connection point readily accessible and permanently marked to indicate the following essential characteristics:
a) rated voltage;
b) rated current;
c) rated frequency.
5.5 Other Equipment
5.5.2 Low-Voltage Generating Sets
5.5.2.101 Generators
All generators shall be so located or protected as to prevent danger and injury to people through inadvertent contact with hot surfaces and dangerous parts. Reference to injury and danger in this subclause also includes non-electrical danger and injury.
Electrical equipment associated with the generator shall be mounted securely and, if necessary, on anti-vibration mountings.
Significant changes in generator frequency and/or voltage shall be prevented.
Where a generator supplies a temporary installation, using a TN, TT or IT system, care shall be taken to ensure that the earthing arrangements are in accordance with 5.4.2.1 of IS 732 and, in cases where earth electrodes are used, with 5.4.2.2 of IS 732.
For TN systems, all exposed conductive parts shall be connected to the generator using a protective conductor with a cross-sectional area in accordance with 5.4.3 of IS 732.
The neutral conductor of the star-point of the generator shall, except for IT-systems, be connected to the exposed conductive parts of the generator.
5.5.3.1 Lighting installation
5.5.3.2.1.101 Luminaires
All luminaires and decorative chains shall be securely attached to the structure or support intended to carry them. Their weight shall not be carried by the supply cable, unless it has been selected and erected for this purpose.
Luminaires and decorative chains mounted less than 2.5 m (arm’s reach) above floor level or otherwise accessible to accidental contact shall be firmly fixed, and so sited or guarded as to prevent risk of injury to persons or ignition of materials. Access to the fixed light source shall only be possible after removing a barrier or an enclosure, which operation shall require the use of a tool.
5.5.3.3.101 Lampholders
Insulation-piercing lampholders shall not be used unless the cables and lampholders are compatible and the lampholders are non-removable once fitted to the cable.
5.5.3.3.102 Lamps in shooting galleries
All lamps in shooting galleries and other side-shows where projectiles are used shall be suitably protected against accidental damage.
5.5.3.3.103 Floodlights
When transportable floodlights are used, they shall be mounted so that the luminaire is inaccessible. Supply cables shall be flexible and have adequate protection against mechanical damage.
5.5.3.3.104 Fire risks for luminaires and floodlights
Luminaires and floodlights shall be so fixed and protected that a focusing or concentration of heat is not likely to cause ignition of any material.
Annex A(Normative) Classification of Safety Services for Medical Locations
Table A-1Classification of Safety Services Necessary for Medical Locations (see also IS 732)
Class 0 (no-break)
Automatic supply available at no-break
Class 0.15 (very short break)
Automatic supply available within 0.15s
Class 0.5 (short break)
Automatic supply available within 0.5s
Class 15 (medium break)
Automatic supply available within 15s
Class > 15 (long break)
Automatic supply available in more than 15s
NOTES 1 Generally, it is unnecessary to provide a no-break power supply for medical electrical equipment. However, certain microprocessor-controlled equipment may require such a supply. 2 Safety services provided for locations having differing classifications should meet that classification which gives the highest security of supply. Refer to Annex B for guidance on the association of classification of safety services with medical locations. 3 The notation "within" implies "≤ ".
5Selection and Erection of Electrical Equipment
5.1 Common Rules
5.1.1 Compliance With Standards
Add the following:
5.1.1.101 For conductive power transfer, EV charging stations shall comply with the appropriate parts of the IS 17017.
5.1.1.102 Wireless power transfer (WPT) systems for EVs shall comply with the appropriate parts of the IEC 61980 series.
5.1.2 Operational Conditions and External Influences
5.1.2.2 External influences
Add the following:
5.1.2.2.101 Presence of water (AD)
When installed outdoors, the equipment shall be selected with a degree of protection of at least IPX4 in order to protect against water splashes (AD4).
5.1.2.2.102 Presence of solid foreign bodies (AE)
When installed outdoors, the equipment shall be selected or provided with a degree of protection of at least IP4X in order to protect against the ingress of small objects (AE3).
5.1.2.2.103 Impact (AG)
Equipment installed in public areas shall be protected against mechanical damage considering an impact of high severity (AG3). This protection shall be provided by one or more of the following:
a) by locating the equipment to avoid damage by any reasonably foreseeable impact;
b) by providing local or general mechanical protection of the equipment; and
c) by selecting and erecting equipment with a minimum degree of protection against external mechanical impact in accordance with the requirements of IS 17050/IEC 62262 of IK08.
5.3 Selection and Erection of Electrical Equipment – Isolation, Switching and Control
5.3.1 Common Rule
Add the following:
5.3.1.101 The requirements of 5.3.1.102 and from 5.3.2 to 5.3.6.3 shall be achieved either by the selection and erection of the appropriate equipment in the fixed installation or by the selection of an EV charging station which incorporates the appropriate equipment or a combination of both.
NOTES
1 The requirements for the selection and erection of devices for isolation, switching and control of the wireless power transfer system are covered by 5.3 of IS 732.
2 The in-cable control and protection device (IC-CPD) according to IS 17120/IEC 62752 is not designed for use in fixed installations.
5.3.1.102 For circuits described in 5.3.2.2.101, and if more than one electric vehicle is supplied from the same unearthed supply, it is recommended to use an insulation fault location system (IFLS) according to IEC 61557-9 to detect the faulty circuitry within the shortest possible time.
5.3.2 Devices for Protection against Indirect Contact by Automatic Disconnection of Supply
5.3.2.2 Residual current protective devices
Add the following:
5.3.2.2.101 RCDs protecting each connecting point in accordance with 4.2.11.3.3 shall comply at least with the requirements of an RCD type A and shall have a rated residual operating current not exceeding 30 mA.
Where the EV charging station is equipped with a socket-outlet or vehicle connector complying with IS 17017/IEC 62196 (all parts), protective measures against d.c. fault current shall be taken, except where provided by the EV charging station. The appropriate measures, for each connection point, shall be as follows:
a) the use of an RCD type B;
b) the use of an RCD type A in conjunction with a residual direct current detecting device (RDC-DD) complying with IEC 62955; or
c) the use of an RCD type F in conjunction with a residual direct current detecting device (RDC-DD) complying with IEC 62955.
RCDs shall comply with one of the following standards: IS 12640 (Part 1), IS 12640 (Part 2), IS/IEC 609472 or IEC 62423.
NOTE — 5.3.2.2.101 is not applicable in case the connecting point is protected by other protective measures against electric shock such as SELV or electric separation.
5.3.2.2.1.1 RCDs shall disconnect all live conductors.
5.3.2.3 Insulation monitoring devices
Add the following:
5.3.2.3.101 Except where a protective device is installed to interrupt the circuit in the event of a first earth fault, an insulation monitoring device (IMD) in accordance with IEC 61557-8 shall be provided.
SP 30 : 2023
If the IMD is not part of the EV charging station then it is recommended that the IMD provides the following two response values:
a) Pre-warning — If the insulation resistance falls below 300 Ω/V an optical and/or acoustical signal should be issued to the user. An ongoing charging session may continue but a new charging session shall not take place.
b) Alarm—If the resistance falls below 100 Ω/V an optical and/or acoustical signal should be issued to the user. The charging circuit should shut down within 10 s.
5.3.4 Devices for Protection Against Overcurrent
5.3.4.101 Except where EV supply equipment in accordance with IS 17017-1 having more than one connecting point is installed and incorporates the necessary overcurrent protective device required by IS 17017-1, 13.1, each connecting point shall be supplied individually by a final circuit protected by an overcurrent protective device complying with IS/IEC 60947-2, IEC 60947-6-2 or IS 12640 (Part 2) or with the relevant parts of the IS/IEC 60898 series or the IS/IEC 60269 series.
NOTE — The EV supply equipment can have multiple connecting points.
5.3.6 Co-ordination of Various Protective Devices
5.3.6.3 Discrimination between residual current protective devices
Where required for service reasons, selectivity shall be maintained between the RCD protecting a connecting point and an RCD installed upstream.
5.4 Earthing Arrangements and Protective Conductors
5.4.3 Protective Conductors
Add the following:
5.4.3.101 Control signals on the protective conductor (PE) shall not flow into the fixed electrical installation upstream of the EV charging station; equipment shall be selected accordingly.
NOTES
1 The requirement is to prevent such signals, and the related devices impairing the correct functioning of the devices installed to provide the protective measure of automatic disconnection of supply ( for example, RCD).
2 This requirement can be achieved by using a galvanic separation of the control electronics.
3 Temporary currents used to perform the test of the continuity of protective conductors for safety purposes are not considered as signal currents.
5.5 Other Equipment
5.5.101 Socket-Outlets and Vehicle Connectors
5.5.101.1 Where the connecting point is a socket-outlet or a vehicle connector, it shall comply with:
a) IS/IEC 60309-1 or IEC 62196-1, where interchangeability is not required,
b) IS/IEC 60309-2, IS 17017 (Part 2/Sec 2)/IEC 62196-2, IS 17017 (Part 2/Sec 3)/IEC 62196-3 or IEC TS 62196-4 where interchangeability is required, or
c) the national standard for socket-outlets, provided the rated current does not exceed 16 A.
Except where electrical separation is used, each socket-outlet shall have an earthing contact connected to the protective conductor (PE).
5.5.101.2 Every socket-outlet or vehicle connector shall be located as close as practicable to the EV parking place to be supplied.
5.5.101.3 Portable socket-outlets shall not be used.
5.5.101.4 One socket-outlet or vehicle connector shall supply only one electric vehicle at the same time.
5.5.101 EV Charging Stations
EV charging stations for public use shall be so designed as to facilitate easy access to the charging point regardless of where the vehicle inlet is located on the electric vehicle.
5.5.2 Low Voltage Generating Sets
5.5.2.1 General
Add the following as e)
e) Electric vehicle
5.5.2.2 General requirements
Add the following:
5.5.2.2.101 Where electric vehicles are intended to feedback energy to the electric installations, the requirements of IEC 60364-8-23) apply.
NOTE — Additional requirements for circuits intended for feeding back electricity from electric vehicles are under consideration.
5.5.2.7 Additional requirements for installations where the generating set may operate in parallel with other sources including systems for distribution of electricity to the public.
5.5.2.7.2 Item b) shall be replaced by
b) The socket-outlet or vehicle connector shall comply with IS 17017 (all parts).
Annex BAdditional Information for Closed Restricted Access Areas
B-1 Ventilation and Conditioning
Closed restricted access areas should be either:
a) ventilated with the air being exhausted outdoors (naturally or mechanically), or
b) air-conditioned.
NOTES
1 The ventilation is installed in order to prevent introduction of dust in the equipment.
Air conditioning should be used, where necessary, to ensure a suitable temperature is maintained.
2 Switchgear and controlgear of distribution boards and accumulators are designed for temperature ranges specified by the manufacturer.
B-2 Construction and Lighting
Gangways should have a firm, even floor and should be provided with adequate lighting.
Section 17 Temporary Electrical Installations for Structures, Amusement Devices and Booths at Fairgrounds, Amusement Parks and Circuses
A temporary electrical installation is generally defined as a temporary electrical installation that is only intended to be in place for a short period of time. This Section specifies the minimum electrical installation requirements to facilitate the safe design, installation and operation of temporary erected mobile or transportable electrical machines and structures that incorporate electrical equipment. The machines and structures are intended to be installed repeatedly and temporarily, without loss of safety, at fairgrounds, amusement parks, circuses or similar places.
For the purpose of this part of NEC Part 3 Section 17, the requirements of IS 732 : 2019 shall apply. This Part 3 Section 17 of NEC contain particular requirements for special installations or locations which are based on the requirements of the general parts of IS 732 : 2019. Part 3 Section 17 parts are considered in conjunction with the requirements of the general parts.
The particular requirements of this part of NEC supplement, modify or replace certain of the requirements of the general parts of IS 732 : 2019 being valid at the time of publication of this part. The absence of reference to the exclusion of a part or a clause of a general part means that the corresponding clauses of the general part are applicable. Numbering of clauses does not, therefore, necessarily follow sequentially.
1 SCOPE
This section of NEC specifies the minimum electrical installation requirements to facilitate the safe design, installation and operation of mobile, temporarily or permanently installed electrical machines and structures which incorporate electrical equipment. The machines and structures are intended to be installed repeatedly, without loss of safety, temporarily or permanently, at fairgrounds, amusement parks, circuses or any other places.
The object of this part of IS 732 is to define the electrical installation requirements for such structures and machines, both being either integral parts or constituting the total amusement device.
This part does not apply to the electrical equipment of machines (see IS 16504-1/IEC 60204-1).
2 REFERENCES
IS/IEC/ISO Number Title
732 : 2019 Code of practice for electrical wiring installations
12640 (Part 1) : 2016 Residual current circuit -breakers without integral overvoltage protection for household and similar uses (RCCBs): Part 1 General rules
12640 (Part 2) : 2016 Residual current operated circuit-breakers with integral overvoltage protection for household and similar uses (RCBOs) — Part 1 General rules (first Revision)
IS/IEC 61558-2-6 : 1997 Safety of power transformers, power supply units and similar: Part 2 Particular requirements for safety isolating transformers for general use
IEC 60364-3 : 1993 Electrical installations of buildings — Part 3: Assessment of general characteristics
IEC 60364-4-481 : 1993 Electrical installations of buildings — Part 4: Protection for safety — Chapter 48: Choice of protective measures as a function of external influences — Section 481: Selection of measures for protection against electric shock in relation to external influences
SP 30 : 2023
IS/IEC/ISO Number Title
IS 16504-1 : 2019/ Safety of machinery Electrical equipment of industrial machines — Part 1: IEC 60204-1 : 2016 General requirements
IS 12360 : 1988/ Voltage bands for electrical installations including preferred voltages and frequency IEC 60038 : 2009
IEC 60050 (826) : 2004 International Electrotechnical Vocabulary (IEV) — Chapter 826: Electrical installations of buildings
IEC 60332-1 (all Parts) Tests on electric cables under fire conditions — Part 1: Tests on a single vertical, insulated wire or cable
IEC 60332-3 : 2018 Tests on electric cables under fire conditions — Part 3: Tests on bunched wires or cable
IS/IEC 60947-2 : 2016 Low-voltage switchgear and controlgear — Part 2: Circuit-breakers
IEC 61034 (all parts) Measurement of smoke density of cables burning under defined conditions
IEC 61046 : 1993 d.c. or a.c. supplied electronic step-down convertors for filament lamps — General and safety requirements
IEC 62020 : 2020 Electrical accessories — Residual current monitors for household and similar uses (RCMs)
CEN TC 152 Non-permanent structures and equipment for fairgrounds and amusement parks: Safety
3 TERMINOLOGY
For the purpose of this part of IEC 60364, the definitions given in IEC 60050 (826) as well as the following definitions apply.
3.1 Fairground
Area where one or more stands, amusement devices or booths are erected for leisure use.
3.2 Booth
Unit, usually movable, intended to accommodate equipment generally for pleasure or demonstration purposes.
3.3 Stand
Area or temporary structure used for display, marketing, sales, entertainment.
3.4 Amusement Device
Ride, stand, textile or membrane building, side stall, side show, tent, booth, grandstand intended for the entertainment of the public.
4Fundamental Principles, Assessment of General Characteristics
4.1 Protection for Safety
4.2 Protection against Electric Shock
4.2.6 Protection by Obstacles and Placing out of Reach
Replace the requirements with the following:
The protective measures “obstacles” and “placing out of reach” as specified in Annex B of IS 732 : 2019, shall not be used.
4.2.7 Replace the requirements with the following:
The protective measures “protection by non-conducting location”, “protection by earth-free local equipotential bonding” and “protection by electrical separation for the supply of more than one item of current-using equipment” as specified in Annex C of IS 732, shall not be used.
4.2.11 Automatic Disconnection of Supply
4.2.11.1 General
Add the following paragraph:
In the case of heating units which are delivered from the manufacturer without an earthed conductive shield a suitable conductive covering, for example, a mesh metallic grid, with a mesh size of not more than 30 mm for ceilings and floor installations and 3 mm for wall installations, shall be provided on site and connected to the protective conductor of the electrical installation.
Residual current protective devices shall be so selected, and the electrical circuits so subdivided, that any earth-leakage current which may be expected to occur during normal operation of the connected load(s) will be unlikely to cause unnecessary tripping of the device.
4.2.13 Protective Measure: Electrical Separation
Add the following:
Electrical separation is not permitted for wall heating systems.
4.2.15.1 Additional protection: residual current protective devices (RCDs)
4.2.15.1.1 Add, at the end of 4.2.15.1.1 of IS 732 : 2019 the following new paragraph:
Circuits supplying heating units shall have additional protection by the use of RCDs with a rated residual operating current not exceeding 30 mA. Time delayed type RCDs are not permitted.
4.1.2.3 Protection against thermal effects
4.3.3 Protection against Burns
Add the following:
Where contact with the skin or footwear is possible, the surface temperature shall be limited.
NOTE — Guidance on limitation of temperature is given in IEC Guide 117.
4.3.4 Protection against Overheating
Add the following:
4.3.4.101 Wall heating systems
For wall heating systems the heating units shall be provided with a metal sheath or metal enclosure or fine mesh metallic grid. The metal sheath or metal enclosure or fine mesh metallic grid shall be connected to the protective conductor of the supply circuit.
NOTE — This requirement is intended to protect against the effects of overheating caused by a short-circuit between live conductors due to penetration of an embedded heating unit.
4.3.4.102 To meet the requirements of 4.3 of IS 732, special care shall be taken to prevent the heating elements creating high temperatures to adjacent material. This may be achieved by using heating units with temperature self-limiting functions or by separation with heat-resistant materials. The latter may be accomplished by placing on a metal sheet, in metal conduit or at a distance of at least 10 mm in air from the ignitable structure.
Annex AInformation for the User of the Installation
A-1 description of the heating system shall be provided to the person ordering the work upon completion of the installation.
The description shall contain at least the following information:
a) description of the construction of the heating system, especially the installation depth of the heating units;
b) location diagram with information concerning:
the distribution of the heating circuits and their rated power,
the position of the heating units in each room,
particularities which have been taken into account when installing the heating units, for example heating-free areas, complementary heating zones, heating-free areas for fixing means penetrating into the covering material;
c) data on the control equipment used, with relevant circuit diagrams and the dimensioned position of floor temperature and weather conditions sensors, if any;
d) data on the type of heating units and their maximum operating temperature.
The installer shall inform the owner that the description of the heating system includes all necessary information, for example for repair work.
An appropriate number of instructions for use shall be provided to the owner or his agent upon completion. One copy of the instructions for use shall be permanently fixed in or near each relevant distribution board.
The instructions for use shall include at least the following data:
a) description of the heating system and its function;
b) operation of the heating installation in the first heating period in the case of a new building, for example, regarding drying out;
c) operation of the control equipment for the heating system in the dwelling area and in the complementary heating zones, if any;
d) information on restrictions on placing of furniture or similar:
additional floor coverings, for example, carpets with a thickness of >10 mm may lead to higher floor temperatures which can adversely affect the performance of the heating system;
pieces of furniture solidly covering the floor and/or built-in cupboards shall only be placed on heating-free areas,
furniture, such as carpets, seating and rest furniture with pelmets, which in part do not solidly cover the floor may not be placed in complementary heating zones, if any;
e) in the case of ceiling heating systems, restrictions regarding the height of furniture. Cupboards of room height may be placed only below the area of ceiling where no heating elements are installed;
f) dimensioned position of complementary heating zones and placing areas;
g) statement that, in the case of thermal floor, wall and ceiling heating systems, no fixing shall be made into the floor, wall or ceiling, respectively. Excluded from this requirement are heating-free areas. Alternatives shall be given, where applicable.
SP 30 : 2023
Section 19 Requirements for Office Buildings, Shopping and Commercial Centres and Institutions
Office buildings, shopping and commercial centres can be of various types depending on the size of the civil structure or the extent of activity involved in the building. High-rise buildings housing office complexes are common, calling for a coordinated planning while designing the electrical services therein.
In small buildings with comparatively moderate loads, supply is normally at medium voltage and the distribution of power is less complex. However, in the case of multi-storied office-cum-commercial complex, where the large number of amenities is to be provided calls for a more complex distribution system. Some of such buildings has to incorporate a standby/emergency power plant for essential service needs.
For editorial convenience, and keeping in view the similarly with the type of buildings covered in this section, educational and other institutional buildings are also covered here. Should any special provisions apply to them, they are identified at the relevant clauses. It is not possible to define strictly the type of buildings covered in this Section except in broad terms, an attempt has been made to identify the nature of the occupancy.
1 SCOPE
This Indian Standard (Part 3/Sec 19) of this Code covers requirements for electrical installations in office buildings, shopping and commercial centers and educational and similar institutional buildings.
2 REFERENCES
IS No.
Title
3646 (Part 2) :Code of practice for interior illumination: Part 2 Schedule for values of illumination and glare 1966 index
8061 : 1976 Code of practice for design, installation and maintenance of service lines up to and including 650 V
15707 : 2006 Testing, evaluation, installation and maintenance of ac electricity meters — Code of practice
3 TERMINOLOGY
For the purpose of this Section, the definitions given in Part 1/Sec 2 of this Code shall apply.
3.1 Coincidence Factor – It is the ratio, expressed as a numerical value or as a percentage, of the simultaneous maximum demand of a group of electrical appliances or consumers within a specified period, to the sum of their individual maximum demands within the same period.
4 CLASSIFICATION
The electrical installations covered in this Section, are those in buildings intended for the following purposes:
a) Office Buildings/Business Buildings — These include buildings for the transaction of business, for the keeping of accounts and records and similar purposes, professional establishments, offices, banks, research establishments, data processing installations, etc.
b) Shopping/Commercial Centres/Mercantile Buildings —These include buildings used as shops, stores, market, for display and sale of merchandise, wholesale or retail, departmental stores, etc.
5.1 Environment
The following environmental factors shall apply to office buildings, shopping and commercial centres and educational/institutional buildings.
Environment
Characteristics
Remarks
(1)
(2)
(3)
Presence of water
Probability of presence of water is negligible
Presence of foreign solid bodies
The quantity or nature of dust or foreign solid bodies is not significant
Presence of corrosive or polluting substances
The quantity and nature of corrosive or polluting substances is not significant
Locations where some chemical products are handled in small quantities, (for example, laboratories in schools and colleges) will be categorized as AF3. For office and other buildings covered by this Section situated by the sea or in industrial zones, producing serious pollution, the categorization AF2 applies
Mechanical stresses
Impact and vibration of low severity
Seismic effect and lighting
Depends on the location of the building
5.2 Utilization
The following aspects of utilization shall apply:
Utilization(1)
Characteristics(2)
Remarks(3)
Capability of persons
Uninstructed persons Children Persons adequately advised or supervised by skilled persons
A major percentage of occupantsApplies to schoolsApplies to areas such as building, substations and for operating and maintenance staff
Contact of persons
Persons in non-conducting situations
Conditions of evacuation during emergency
Low density occupation, easy conditions of evacuation.
Small offices and shops Departmental stores
High density occupation, difficult conditions of evacuation
High rise office occupation, commercial centres, underground shopping arcades etc.
Nature of processed of stored material
No significant risks
Small shops
Existence of fire risk
In view of large volume of paper and furniture, for example, office buildings, furniture shops, etc.
SP 30 : 2023
5Selection and Erection of Electrical Equipment
5.1 Common Rules
5.1.1 Compliance with Standards
Flexible sheet heating elements shall comply with the requirements of IEC 60335-2-96.
Heating cables shall comply with IEC 60800.
5.1.4 Identification
5.1.4.1 General
Replace the existing text by the following new text:
Documentation for each heating system shall be provided, containing the following information where relevant:
a) manufacturer and type of heating units;
b) number of heating units installed;
c) length/area of heating units;
d) rated power;
e) surface power density;
f) layout of the heating units in the form of a sketch, drawing or picture;
g) position/depth of heating units;
h) position of junction boxes;
j) conductors, shields and the like;
SP 30 : 2023
k) heated area;
m) rated voltage;
n) rated resistance (cold) of heating units;
p) rated current of overcurrent protective device;
q) rated residual operating current of RCD;
r) the insulation resistance of the heating installation and the test voltage used;
s) the leakage capacitance;
t) product information containing provisions about approved substances in the surroundings of the heating units, with necessary instructions for installation. If materials other than those recommended are used, the manufacturer shall be consulted.
This plan shall be fixed to, or adjacent to, the distribution board of the heating system.
Furthermore, the requirements of Annex A apply.
5.1.5 Prevention of Mutual Detrimental Influences
5.1.5.1 Replace the existing text by the following new text:
Electric heating systems shall be selected and erected so as to avoid any harmful influence between the heating system and any electrical or non-electrical installations envisaged.
NOTE — For example, an electric heating system can affect other parts of the electrical installation such as reducing the current-carrying capacity of cables of other circuits due to high local ambient temperature caused by the heating system.
Add the following new subclause:
5.1.5.1.101 Heating units shall not cross expansion joints of the building or structure.
5.2 Wiring Systems
5.2.1 Introduction
5.2.3 General
Add the following new subclause:
5.2.3.101 Heating-free areas
For the necessary attachment of room fittings, heating-free areas shall be provided in such a way that the heat emission is not prevented by such fittings.
5.2.5 Selection and Erection of Wiring Systems in Relation to External Influences
5.2.5.1 Ambient temperature (AA)
Add the following:
5.2.5.1.101 For cold leads (circuit wiring) and control leads installed in the zone of heated surfaces, the increase of ambient temperature shall be taken into account.
5.2.5.4 Presence of solid foreign bodies (AE)
Add the following:
5.2.5.4.101 Where heating units are installed there shall be heating-free areas where drilling and fixing by screws and the like may be carried out without risk of damage to the unit(s).
6Supply Characteristics and Parameters
6.1 Exchange of Information
6.1.1 Proper coordination shall be ensured between the architect, building contractor and the electrical engineer on the various aspects of installations design. From the point of view of the design of the various installations, the following shall be considered:
a) Maximum demand and Coincidence Factor;
b) Type of distribution system, mains and sub mains;
c) Nature of supply (current, frequency, nominal voltages);
d) Prospective short-circuit current at the supply intake point;
e) Division of the installation;
f) Nature of the external influences (see 5);
g) Maintainability of the installations;
h) Nature and details of building services;
Lighting,
Air-conditioning, and
Lifts.
j) Other details as relevant such as, pumps for fire-fighting, lighting, fire-alarm systems, telephones, call-bells, clock systems, etc.;
k) Telephone circuits including extensions and intercom facilities;
m) CCTV for information display and security;
n) Computer installation facility where applicable; and
p) Metering system for different loads.
NOTE — Fire protection system shall include such details such as locations of detectors, zonal indicators, central control console, public address system for fire-fighting, cable runs and their segregation from the other cable system.
q) Parking area
A complete drawing of layout of the electrical installation shall be prepared together with associated floor plans indicating the details mentioned in (a) to (q). This wiring diagram shall include outlets for lights, sockets, bells, ceiling fans, exhaust fans, location of sectionalized control switches, distribution boards, etc. In special occupancies such as school or college laboratories, the d.c. circuits be identifiable in the layout diagram. (Including protective devices like MCBs, or RCD where ever required.)
6.2 Branch Circuits
6.2.1 The general design of wiring of branch circuits shall conform to those laid down in Part 1/Sec 9 of this Code. However, for special cases such as for communication networks, fire-alarm system and wiring for data-processing equipment, the recommendations of the manufacturer shall apply.
6.2.2 The branch circuit calculations shall be done according to the general provisions laid down in Part 3/Section 1 of this Code. However, the specific demands of the lighting, appliance and motor loads as well as special loads encountered in the types of buildings covered in this Section shall be taken into account.
6.2.3 In offices and showrooms, the interior decoration normally include false ceiling, carpets and curtails. Any wiring laid above the false ceiling should be adequately protected such as by drawing the wires in metallic conduits/GI Cable trays and nor run in open. Wires shall not be covered by carpets. They shall be run at skirting level and encased for mechanical protection.
In modern offices cables/wires shall be laid in floor raceways made of GI/PVC with adequate compartments along with junction boxes/floor boxes
6.2.4 Adequate number of socket-outlets shall be provided for electrically operated office machines such as computers, desktop printers, xerox machines and scanners electrical typewriter, etc., to avoid running of wires and use of multiple outlets from one socket.
Power circuit (that is 16A/20A points/sockets and outlets) should be separate from the lighting circuit and protection provided for the same should be separate (like MCCBs/RCD).
6.2.5 Areas where corrosive or polluting substance are present intermittently or continuously, such as school laboratories and other buildings located in high industrial pollution zones, socket-outlets shall preferably be of metal clad weatherproof type with covers. The cable trays here could be of hot dip galvanized/SS material (suitable IP protection DBs to be used as per application/surrounding condition).
6.2.6 Lighting circuits shall preferably be combined in switched groups so that lighting can be limited to desks which are occupied. Each lighting circuit shall be protected by MCBs of suitable rating.
6.3 Service Lines
The general provisions laid down in IS 8061 shall apply.
6.4 Building Substations
6.4.1 General
The designer of power supply for office buildings and commercial centres shall take into account the great concentration of power demand of the electrical loads. Air-conditioning in office buildings absorbs an especially high proportion of the total power used. Consequently, such occupancies have to be provided with their own substation with vertical and horizontal forms of power distribution.
6.4.2 If the load demand is high, requiring supply at high voltage, accommodation for substation equipment will be required. Main switch room will serve feeders to various load centres, such as air-conditioning plant, elevators, water pumps, etc. Other loads are taken to local distribution boards.
6.4.3 The transformer power rating for the supply of the building shall be sufficient to cater to the highest simultaneous power requirements of the building. Typical proportions of power usage are given as follows:
Part of Electrical Installation
Part of the Total Power Requirement Percent
Coincidence Factor
(1)
(2)
(3)
Ventilation, heating (air-conditioning)
45
1.0
Power plant (drives)
5
0.65
Lighting
30
0.95
Lifts
20
1.0
6.4.4 The location and layout of building substation shall conform to the general rules laid down in Part 2 of this Code. The substation room shall be well ventilated and inaccessible to birds and reasonably reptile, rodent and insect-proof. Only authorized persons be allowed to enter the substation for operations/maintenance of any kind. Cables leading from the substation to the main building shall preferably be carried underground through ducts or pipes of adequate dimensions. Such pipes shall be properly sealed at both ends to reduce the possibility of rain water flowing through the pipes and flooding the trenches.
6.4.4.1 Buildings should be protected by suitable lightning and surge protectors/arresters.
6.4.5 Emergency Supply
Wherever emergency supply is considered necessary, it can be in the form of separate and independent feeder from the undertaking terminated in equipment isolated from the regular supply line. In case of standby supply from diesel generator set, it will be installed as per the general rules laid down in Part 2 of this Code. Automatic transfer switch can be used for the changeover.
6.4.5.1 In office buildings, certain safety and essential services shall be supplied even in the case of mains failure. These are governed by the rules and regulations of the respective authorities. Essential services include amongst others, water-pressure pumps, ventilation installations, essential lighting and lifts. also emergency lights on exit door to be installed. The power requirement of these essential loads is generally about 25 percent of the total power requirement of the building.
6.5 Metering
In multi-storied buildings, a number of offices and commercial centers occupy various areas. Electrical load for each of them would have to be metered separately; the meter-room normally is situated in the ground floor (see IS 15707 for further guidance).
6.6 System Protection
6.6.1 General
The general rules for protection for safety laid down in Part 1/Sec 22 of this Code shall apply. Reference is also drawn to SP 7 on guidelines for fire protection of buildings. The general rules given below shall apply.
6.6.2 The type of buildings covered in this Section fell under Group B (educational buildings). Group E (business buildings) and Group F (mercantile buildings) from the point of view of fire safety classification (see SP 7). Typical firefighting installation requirements are also covered therein. The electrical needs for the appropriate type of installation shall, therefore, be decided accordingly.
6.6.2.1 Educational buildings (Group B)
Educational buildings above 2-storeys having an area of more than 500 m2 per floor shall have besides firefighting equipment, manually operated electrical fire alarm and automatic fire alarm systems.
6.6.2.2 Business buildings (Group E)
Besides fire-fighting equipment, automatic fire alarm systems are recommended for offices, banks, professional establishments, parking areaetc, where the buildings are more than 2 storey with floor area above 500 m2 per floor, and for laboratories with delicate instruments as well as computer installations.
6.5.2.3 Mercantile buildings (Group F)
Besides fire-fighting equipment, automatic sprinklers and automatic fire alarm systems are recommended for wholesale establishments, warehouses, transport booking agencies, etc, as well as for shopping areas inside buildings with area more than 500 m2 on each floor. For other premises and shopping lines with central corridors open to sky, automatic fire-alarm systems shall be installed. Underground shopping centers shall be provided with automatic sprinklers.
6.7 Building Services
6.7.1 Lighting
6.7.1.1 The general rules laid down in Part 1/Section 15 of this Code shall apply. The choice of lamps, lighting fittings and general lighting design together with power requirement shall be planned based on the recommended values of illumination and limiting values of glare index given in Table 1. Maximum use of LED lighting should be preferred for energy conservation.
6.7.1.2 In commercial premises, a fairly high level of glare free lighting on working planes and subdued lighting in circulation areas are necessary with suitable protection like MCBs and RCDs. Aesthetics and interior decoration also play a part. Lighting design in showrooms includes high level of lighting in the vertical and horizontal planes, depending on the merchandise exhibited and their layout. Colour temperature characteristics of the light source shall also be taken into account in the case of showroom lighting.
6.7.1.3 External lighting like street lighting and building façade lighting maybe be connected through suitable Timers/Time switches to have auto switching based on time.
6.7.2 Air-conditioning
6.7.2.1 The general rules laid down in Part 1/Sec 15 of this Code shall apply. The design of the air conditioning system, shall take into account the requirements stipulated in the following clauses.
6.7.2.2 Each Split Unit a.c. shall be wired separately from the DB with separate MCB for each for short circuit and overload protection.
6.7.2.3 In case of large air-conditioning installations (500 tons and above) it is advisable to have a separate isolated equipment room together with electrical controls. All equipment rooms shall have provision for mechanical ventilation.
6.7.3 Lifts and Escalators
6.7.3.1 The general rules laid down in Part 1/Section 15, of this Code shall apply. However, the design of lifts shall take into account the following recommendations:
6.7.3.2 Occupant load
These shall be as follows:
Sl No.
Occupancy
Occupation Load Gross Area in m<sup>2</sup>/Person
(1)
(2)
(3)
i)
Educational
4
ii)
Business
10
iii)
Mercantile:
1) Ground floor and sales
3
2) Upper sale floor
6
6.7.3.3 Passenger handling capacity (H)
These are expressed in terms of percent of the estimated population that has to be handled in the building in the 5 min peak period as follows:
7Testing of Installation
The various tests on the installation shall be carried out as laid down in Part 1/Section 17 of this code.
8Miscellaneous Provisions
8.1 Group Control
The lighting circuits shall preferably be combined in switched groups as well as coordinated to functional groups of desks in an open plan office. The switching points may be combined centrally at the entrance passageways. In order to ensure proper co-ordination with design of the building for daylight use of devices such as automatic light sensors shall be encouraged for controlling lighting groups near windows for energy saving.
8.2 Telephones/Intercoms/Internet
Adequate coordination shall be ensured right from the planning stages with the telephone authorities to determine the needs for the telephone system catering to the various units in office buildings. For private intercom systems, entirely under the control of the user, it is necessary to pre-plan the coordination of external and intercom systems. Suitable single band or dual band routers to be installed depending upon number of users, level of security and throughput.
8.4Clock Systems
8.4.1 The general guidelines contained in Part 1/Section 15 shall apply regarding installation and maintenance of master and slave clock systems.
8.4.2 In simple installations, impulse clocks designed to operate at the same current may be connected in one series circuit, with a battery having sufficient voltage to ensure satisfactory operation. In a more complex installation like multistoried office buildings with large number of slave clocks, the impulse clocks may be arranged in number of series circuits. Each of which is connected to a pair of contact on a relay which is operated from the contacts of master clock.
8.4.3 Master clock shall be placed in a dust free location, readily accessible for maintenance at all times.
8.5 Closed Circuit TV
Commercial buildings may require the installations of CCTVs for one of more of the following purposes:
a) Security, and safety; or
b) Information display.
Educational/institutional buildings may use CCTV as a teaching aid for pre-recorded educational programs. Reference shall be made to good practice for installations of such facilities.
SP 30 : 2023
8.6 Emergency Lights for Critical Areas
Battery powered (at least 2 h rating) emergency lights should be installed at critical and strategic locations including emergency exit points. These will provide illumination by self-contained battery source even on failure of a.c. mains. On resumption of a.c. power supply, they will switch back to mains automatically and simultaneous recharge the battery to the required level.
8.7 Emergency Exit Lighting/Signage
Emergency lighting units are essential products that must be fully operational in order to ensure the safety of people in the event of emergency evacuation.
These should have LED bulbs and be capable of remaining ON for at least 2 h during an emergency and shall have IP42 class of protection.
Photo luminescent safety signage should be provided at different strategic locations.
5.1Environment
5.1.1 The following environmental factors apply to hotels:
Environment(1)
Characteristics(2)
Remarks(3)
Presence of water
Probability of presence of water is negligible
Majority of locations in hotels. Traces of water appearing for short periods are dried rapidly by good ventilation.
Possibility of jets of water from any direction
Applies to gardens
Possibility of permanent and total covering by water
Locations, such as swimming pools
Presence of foreign solid bodies
The quantity or nature of dust or foreign solid bodies is not significant
Presence of corrosive or polluting substances
The quantity and nature of corrosive or polluting substances is not significant
For hotels situated by the sea or industrial zones, other categorization applies (see Part 1/Section 8 of this Code)
Mechanical stresses
Impact and vibration of low severity
—
Seismic effect and lighting
Depends on the location of the building
5.2Utilization
5.2.1 The following aspects of utilization shall apply:
Utilization(1)
Characteristics(2)
Remarks(3)
Capability of persons
Ordinary, uninstructed persons
A major proportion of occupants in Hotels
Persons adequately advised or supervised by skilled persons
Applies to areas, such as building substation and for operating and maintenance staff
Contact of persons with earth potential
Persons in non-conducting situations
Condition of evacuation during emergency
Low density occupation, easy conditions of evacuation
Applies to lodging houses
High density occupation, difficult conditions of evacuation
Large hotels, high-rise buildings.
Nature of processed of stored material
No significant risks
Contamination risks due to presence of unprotected food stuffs
Applies to kitchens
6 SUPPLY CHARACTERISTICS AND PARAMETERS
6.1Exchange of Information
Proper coordination shall be ensured between the architect, building contractor and the electrical engineer on the various aspects of installation design. In addition to the general aspects which require coordination and identified in other sections, information shall be obtained on the following services:
a) Whether central air-conditioning system is intended. If so, layout of air handling units, fan coil units, ducting, false ceiling and chilled water lines should be obtained.
b) Whether centrally controlled fire-fighting is intended. If so, layout of fire-fighting installation should be obtained.
c) Whether telephone and TV facilities are intended in each room. If so, layout of the telephone installation and TV circuits should be obtained.
d) Whether centrally heated out water system is intended. If so, layout of hot water pipe-line be obtained.
6.7Building Services
6.7.1 Lighting
6.7.1.1 The general rule laid down in Part 1/Sec 14 of this Code shall apply. The choice of lighting fittings and general lighting design together with power requirements shall be planned based on the recommended values of illumination and limiting values of glare index given in Table 1 [see also IS 3646 (Part 2) and SP 72].
Table 1Recommended Values of Illumination and Glare Index for Hotels (Clause 6.7.1.1)
Sl No.
Building
Illumination, lux
Limiting Glare Index
(1)
(2)
(3)
(4)
i)
Entrance halls, lobby
150
-
ii)
Reception and accounts
300
-
iii)
Dining rooms (tables)
100
-
iv)
Lounges
150
-
v)
Bedrooms:
a) General
100
b) Dressing tables, bed heads, etc.
200
-
vi)
Writing tables
300
vii)
Corridors
70
-
viii)
Stairs
100
-
ix)
Laundries
200
25
x)
Kitchens
200
25
xi)
Goods/passenger lifts
70
-
xii)
Cloakrooms/toilets
100
-
xiii)
Bathrooms
100
-
xiv)
Shops/stores
150-300
22
NOTE — The lighting of some of these locations is determined primarily by aesthetic considerations and the above values should be taken as a guide only.
6.7.1.2 In guest bedrooms, it shall be possible to switch the general lighting not only from the entrance but also from the bedside (see also 8.4.2).
6.7.1.3 In bathrooms, the lights should be mounted at head level on both sides of the mirror. Care shall be taken to ensure that there is no glare.
6.7.1.4 Lighting in banquet halls shall be given special consideration in view of its multipurpose utility, such as fairs, dances, fashion shows, conferences, exhibition or concerts. Sufficient number of controlled socketoutlet circuits shall be combined in a switching station from which the entire hall shall be visible.
6.7.1.5 In designing outdoor lighting installations, care shall be taken to ensure that disturbing glare does not reach the rooms of the guests.
6.7.2 Air-conditioning
The provisions of Part 1/Sec 15 of this Code shall apply.
6.7.3 Lifts and Escalators
6.7.3.1 The general rules laid down in Part 1/Sec 15 of this Code shall apply. However, the design of lifts shall take into account the following recommendations.
SP 30 : 2023
6.7.3.2 Occupant load
For hotel buildings, an occupant load of 12.5 gross area, in m2 per person is recommended.
6.7.3.3 Passenger handling capacity
The passenger handling capacity expressed in percent of the estimated population that has to be handled in the 5 min peak period shall be 5 percent for hotel buildings.
6.7.3.4 Car speed — This shall be as follows:
Occupancy
Floors Served
Car Speed m/s
Passenger lifts for low and medium class lodging houses
-
0.5
Hotels
4-5
0.5-0.75
6.7.3.5 For hotel buildings, it is desirable to have at least a battery of two lifts at convenient points of a building. If this is not possible, it is advisable to have at least two lifts side by side at the main entrance, and one lift at different sections of the building for intercommunication.
7 TESTING OF INSTALLATION
The various tests on the installation shall be carried out as laid down in 6 of IS 732.
8Miscellaneous Provisions
8.1 Call System
The general provisions for electrical bells and call system shall conform to those laid down in Part 1/Sec 15 of this Code. The call system should be a wired electrical system whereby customer may signal for attendance from his room. Two types of systems are recommended:
a) A simple one-watt signal system which connects the room side call stations with a signal at the attendant station. It simultaneously lights a dome light over the door of the room from which the call is originated. The signal at the attendant station may be in the form of an annunciator with a buzzer or a light with a buzzer.
b) A central control panel shall, be set up preferably on the ground floor incorporating a set of indicating panels according to the number of wings. Each indicating panel should have a set of small lamps according to the number of rooms. After-attending the customer, the attendant presses the resetting button which puts the whole equipment to the original condition.
8.2 Telephones
A centralized EPABX System with sufficient P&T lines shall be installed for internal and external communications with the help of operator’s assistance as well as directly through this system. These may be connected on a dial system which permits internal communication through the hotel switchboard without the assistance of the operator. At all the rooms, telephone jacks shall be installed so that a telephone may be plugged in any time at any convenient location. Parallel telephones may be provided in the bedrooms. Each room shall also be provided with jacks for broad band multi service facility/internet facility.
8.3 Clock Systems
The general provisions for clock systems shall conform to those laid down in Part 1/Sec 15. The following locations may be provided with clocks:
a) Guest rooms,
b) Main lobby,
c) Telephone switchboard,
d) Dining room,
e) Banquet halls,
f) Kitchen, and
g) Restaurant and bar rooms.
8.4 Emergency Supply
See also Part 2 of this Code.
8.4.1 In the event of a failure of supply, a large standby power supply usually a diesel driven generating set could be used to partly or entirely supply the loads in the hotel. Emergency lighting shall be confined to essential areas, and the standby power supply shall feed essential and safety installations in the hotel.
8.4.2 Part of the kitchen, storage and refrigeration rooms in the hotel shall also be supplied by the emergency supply. A part of the lighting in each room, corridor, staircases and other circulation areas shall be connected to emergency supply.
8.5 Other Special Installations
The list of such installations is given below:
a) TV sets at main assembly areas and in guest rooms,
b) Lighting in banquet halls,
c) Fire-fighting system,
d) Swimming pool (see Annex A),
e) Cold storage,
f) Sauna Heaters (see Annex B), and
g) Broad Band Multi Service facility/internet facility.
8.6 For particular requirements for locations containing a bathtub or shower basin, see Annex A of Part 3/Sec 1 of this Code.
8.7 Luminous Sign
Photo luminescent safety signage should be provided at different strategic locations.
SP 30 : 2023
Annex A(Clause 8.5) Particular Requirements for Swimming Pool
A-1 Scope
This Annex applies to the basins of swimming pools and paddling pools and their surrounding zones where susceptibility to electric shock is likely to be increased by the reduction of body resistance and contact with earth potential.
A-2 Classification of Zones
A-2.1 Reference is drawn to Fig. A-1 and Fig. A-2.
Zone 0 — is the interior of the basin.
Zone 1 — is limited by a vertical plane 2 m from the rim of the basin by the floor or the surface expected to be occupied by persons and the horizontal plane 2.50 m above the floor of the surface.
Zone 2 — is limited by the vertical plane external to Zone 1 and a parallel plane 1.50 m from the former, by the floor or surface expected to be occupied by persons and the horizontal plane 2.50 m above the floor or surface.
NOTE — Where the pool contains diving boards, spring boards, starting blocks or a chute, Zone 1 comprises the zone limited by a vertical plane situated 1.50 m around the diving boards, spring boards and starting blocks, and by the horizontal plane 2.50 m above the highest surface expected to be occupied by the persons.
A-3 Protection for Safety
A-3.1 Where safety extra-low voltage is used, whatever the nominal voltage, protection against direct contact shall be provided by barriers or enclosures affording at least a protection of IP2X, or insulation capable or withstanding a test voltage of 500 V for 1 min.
A-3.2 All extraneous conductive parts in Zones 0, 1 and 2 shall be bonded with protective conductors of all exposed conductive parts situated in these Zones.
A-4 Selection of Equipment
A-4.1 Electrical equipment shall have at least the following degrees of protection:
a) Zone0 : IP X 8
b) Zone1 : IP X 4
c) Zone2 : IP X 2 for inside swimming pools. IP X 4 for outside swimming pools.
A-4.2 For Zone 1 and Zone 2, water jet is likely to be used for clearing purpose : IP X 5
This requirement does not apply to instantaneous water heaters complying with IS 302 (Part 2/Sec 35).
A-5 Wiring Systems
A-5.1 In Zone 0 and Zone 1, wiring systems shall be limited to those necessary to the supply of appliances situated in those zones.
A-5.2 Junction boxes are not permitted in Zone 0 and Zone 1. In Zone 2, they are permitted provided they have the necessary degree of protection as given in A-4.1.
A-5.3 In Zone 0 and Zone 1 no switchgear and accessory shall be installed. In Zone 2 socket-outlets are permitted only if they are either:
a) supplied individually by an isolating transformer,
b) supplied by safety extra low voltage, or
c) protected by a residual current protective device.
A-5.4 If it is not possible to locate socket-outlets may be installed only if they are complying:
a) Outside 1.25 m from the Zone 0 border, and
b) protected by residual current protection device.
A-5.5 The socket-outlets shall comply IS/IEC 60309 (Part 1) and IS/IEC 60309 (Part 2).
A-5.6 An electric heating unit embedded in the floor in Zones 1 and 2 shall incorporate a metallic sheath connected to the local supplementary equipotential bonding and shall be covered by the metallic grid required by A-3.2.
A-5.7 In Zone 2, only water heaters are permitted excepting that other equipment supplied by SELV (Safety Extra Low Voltage) at a nominal voltage not exceeding 12 V may be installed.
Fig. A-1 Zone Dimensions for Basins Above Ground
Fig. A-2 Zone Dimensions of Swimming Pools And Paddling Pools
SP 30 : 2023
Annex B(Clause 8.5)
Particular Requirements for Locations Containing Sauna Heaters
B-1 Scope
The particular requirements of this Annex apply to locations in which hot air sauna heating equipment is installed.
B-2 Classification of Temperature Zones
The assessment of the general characteristics of the location shall take due consideration of the classification of the four temperature zones which are illustrated in Fig. 3.
B-3 Protection for Safety
B-3.1 Where Safety Extra Low Voltage (SELV) is used, irrespective of the nominal voltage, protection against direct contact shall be provided by one or more of the following:
a) insulation capable of withstanding a test voltage of 500 V a.c., rms for 1 min.
b) barriers or enclosures, affording at least degree of protection IP 24.
B-3.2 All extraneous conductive parts shall be bonded with protective conductors of all exposed conductive parts situated in these zones and earthed.
B-4 Selection of Equipment
B-4.1 All equipment shall have at least the degree of protection IP 24.
B-4.2 Equipment should be selected in accordance with the temperature zones as depicted in Fig. B-1 as per the following details:
a) Zone A: only the sauna heater complying with relevant safety standard and equipment directly associated with it shall be installed.
b) Zone B: there is no special requirement concerning heat resistance of equipment.
c) Zone C: equipment shall be suitable for an ambient temperature of 1 2 5 ° C .
d) Zone D: only luminaries and their associated wiring, and control devices for the sauna heater and their associated wiring shall be installed. The equipment shall be suitable for an ambient temperature of 125 °C.
Fig. B-1 Classification of Temperature Zones
B-5 Wiring Systems
B-5.1 Flexible elastomer insulated and mechanically protected cords complying with appropriate standard, suitable for 1 5 0 ° C should be used.
B-5.2 Switchgear not built into sauna heater, other than a thermostat and a thermal cut-out shall be installed outside the hot air sauna.
B-5.3 Except as permitted in B-4.2 and B-5.2 accessories shall not be installed within the hot air sauna.
B-6 Other Fixed Equipment
Luminaries shall be so mounted as to prevent overheating.
Section 21 Requirements for Sports Buildings
557
The design and erection of electrical installation in a sports building have to take into account a multitude of factors that are unique to the type of use to which it is put. In a way the electrical power needs and the external influences in a sports building are quite identical to those for theatres and other multipurpose buildings for cultural events excepting that for international events exacting standards of services and flexibility had to be provided in a multipurpose sports stadia.
Several stadia, especially those of the indoor type are meant for staging a variety of games which between themselves require varying standards of lighting levels. The design of illumination system in a sports building therefore requires consultations with a specialist and the guidelines provided in this Section are purely recommendatory in nature in this respect.
In indoor stadia where, large number of people congregate it is essential to inbuild adequate fire precautions from the point of view of safety. Assessing the need for adequate strength of a standby supply for essential services requires special consideration.
It is to be noted that a sports stadium should preferably be designed for use for other purposes as well, such as the staging of cultural events and this aspect shall be borne in mind while designing the electrical needs of the complex so as to ensure optimum utilization of the facilities.
With the advent of sophisticated stadia in the country as well as keeping in view the accent on sports, this Section of this Code has been set aside to cover such of those specific requirements applicable to sports buildings from the electrical engineering point of view. Taking note of the fact that the type of buildings and their needs for the purposes of sports and games would be quite different between them, only broad guidelines are outlined in this Section. It is recommended that assistance of experts shall be sought in the design of the installation at the early stages itself.
1 SCOPE
This Part 3/Sec 21 of the Code covers requirements for electrical installations in sports buildings and stadia, indoor and outdoor.
2 TERMINOLOGY
For the purpose of this Section, the definitions given in Part 1/Sec 2 of this Code shall apply.
3 CLASSIFICATION OF SPORTS BUILDINGS
3.1 The buildings for the purposes of conducting sports and games are characterized by the criteria that large number of people congregate. Sports complexes not basically meant for exhibition purposes, and not likely to be utilized for other purposes, such as for staging special or cultural events, shall however conform to the special requirements of this Section. The type of building shall therefore be classified as follows:
a) Based on type of building:
Indoor stadia.
4General Characteristics of Sports Buildings
General guidelines on the assessment of characteristics of installations in buildings are given in Part 1/Section 8 of this Code. For the purposes of installations falling under the scope of this Section, the characteristics given below shall apply.
4.1 Environment
4.1.1 The following environmental factors apply to sports buildings:
Environment(1)
Characteristics(2)
Remarks(3)
Presence of water
Submersion, possibility of permanent and total covering by water
Locations, such as swimming pools where electrical equipment is permanently and totally covered with water under pressure greater than 0.1 bar.
Presence of foreign solid bodies
The quantity or nature of dust or foreign solid bodies is not significant
Indoor stadia.
Presence of dust in significant quantify
Outdoor stadia.
Presence of corrosive or polluting substances
Negligible
Covers majority of cases. Stadia and games complexes situated by the sea or industrial zones require special consideration.
Lighting
Negligible
Covers category d(2) (see 3.1) type of installations.
Indirect exposure to lighting, where hazard from supply arrangements exists
Installations supplied by overhead lines.
Direct exposure or hazard from exposure of equipment is present
Lighting towers in outdoor stadia.
4.2 Utilization
The following aspects utilization shall apply:
Utilization(1)
Characteristics(2)
Remarks(3)
Capability of persons
Uninstructed persons
In sports stadia the sportsmen and spectators fall under this category.However, electrical operating areas are accessible to instructed persons only.
Conditions of evacuation in an emergency
Low density occupation, easy conditions of evacuation
Training halls and the like where people do not congregate.
High density occupation, difficult conditions of evacuation
Large multipurpose stadia for exhibition purposes.
Nature of processed of stored material
Existence of fire-risks.
Due to furniture and false floor for playing area.
6.2Branch Circuits
6.2.1 The general provisions for the design of wiring of branch circuits shall conform to those laid down in Part 1/Sec 9 of this Code. However, for special cases such as for communication networks, fire-alarm system, etc, as well as in areas, such as kitchen, laundry, etc, the recommendation of the manufacturer shall apply.
6.2.2 The branch circuit calculations shall be done as laid down in Part 1/Sec 9 of this Code. The specific demands of the lighting, appliance and motor loads, as well as special loads encountered in hotel building shall be taken into account.
6.2.3 In hotel buildings, the interior decor normally includes false ceiling, carpets and curtains. Any wiring laid above the false ceiling should be adequately protected, such as by drawing the wires in metallic conduits and not run in open. Wires shall not be laid under carpets. They shall be run at skirting level and encased for mechanical protection.
6.2.4 Panel Boards and Switch-boards
The provisions of Part 1/Sec 9 of this Code shall apply.
6.2.5 5ocket-outlets and Plugs
6.2.5.1 These should be provided in all places where plug-in service is likely to be required, to reduce the need for alterations and extensions of wiring after the hotel building is completed. Duplex or other suitable outlets should be provided as required in the offices and work places for fans, lamps and appliances. The socket-outlets shall preferably have covers. Corridors and staircases shall be provided with sufficient socket-outlets for floor cleaning appliances. These shall be connected in a circuit separate from the circuits for the guest rooms.
6.2.5.2 If provided, use of a central radio receiving system wired with multi-channels piped music system to each room is recommended so that the occupant may choose one of the broadcasts. For such reception, special aerials and related wiring are required. Aerial outlets at rooms are required for portable radios in areas and buildings where reception is poor but in general the aerial built in the set may be adequate.
6.2.5.3 Special convenience outlets in corridors at suitable locations are desirable for use of portable equipment, such as floor cleaning appliances. They should be of the 3-pin type, suitably rated with one-pin earthed.
Heavy duty sockets should also be provided in pantries, kitchens, toilets and utility rooms for use of appliances. Adequate plug-in sockets at proper locations should be provided in banquet halls and other meeting places for flood lights and other appliances.
6.3 Feeders
The general provisions laid down in Part 1/Sec 9 of this Code shall apply.
6.4 Service Lines
The general provisions laid down in IS 8061 shall apply.
5Supply Characteristics and Parameters
5.1 Exchange of Information
5.1.1 Proper coordination shall be ensured between the architect building contractor and the electrical engineer on the various aspects of the installation design. In addition to the general aspects which require coordination and identified in other sections, the following data shall specifically be obtained:
a) The total electrical power needs of the stadium including the standby power arrangements, which will decide the voltage of supply, number of substations and their preferred locations, capacity of diesel engine generating sets for standby supply, transformers, switchgear, voltage stabilizers, uninterrupted power supply requirements, etc;
b) In case of indoor stadia, whether air-conditioning is required and if so, the capacity and locations of main plants, air-handling units, pumps, ducting, layout, route of chilled water lines, etc. In case of outdoor stadium, the covered portions like offices, restaurants, are to be air-conditioned or not and their details as above;
c) Details of fire fighting system/fire alarm system envisaged;
d) Details of water supply arrangements, storm water drainage, sewage disposals and pump capacities, locations, etc;
e) Locations of substations, switch rooms, distribution boards, etc;
f) Requirements of audio-communication system for the stadium which includes public address system, car calling system, ambulance call, fire service call, intercom stations, wireless paging system, inter-stadia communication facilities, computer-aided results information, etc;
g) Details of score-boards — that is whether and their power etc, centralized manual or automatic, etc, needs, voltage stability, clock system, etc;
h) Special requirements of press, TV, Radio, telecommunication, games federations, etc;
j) Requirements of lighting, the location of lighting luminaries, type of light source, level of illumination required for various stages like training, TV (black and white or colour) coverage, etc;
k) Requirements for power outlets, speaker outlets, microphone outlets, etc., in playing arena and field; and
m) Other miscellaneous items like electrification of ancillary buildings in the sports complex, restaurants, gas/oil requirements for flame and their controls, fountain lighting system, car park, path way and external electrification.
5.1.2 The following drawings are recommended to be prepared before commencing the installations work:
a) Single line diagram for electrical distribution;
559
b) Complete layout drawings indicating type and mounting of luminaries and conduit/cable installations for various services. This shall be prepared in coordination with civil and structural engineers;
c) Wiring diagrams showing switching sequence of luminaries, fire alarm system, public announcement systems, etc;
d) In case of air-conditioning, layout of plants, chilled water piping routes, ducts/grill layout, etc;
e) Layout of public address system envisaged; and
f) Site plan indicating the location of pump houses for storm water drains, water supply, sewage and fire fighting systems, with the proposed source and route of power supply.
5.2 Branch Circuits
5.2.1 The general rules as laid down for other large assembly buildings (see Part 3/Sec 19) and as laid down in Part 1 of this Code shall apply.
5.2.2 Wiring installations for general purpose lighting and ventilation needs of the sports buildings shall conform to the requirements laid down in Part 1/Sec 15 of this Code. It is preferable to avoid temporary wiring in electrical central control room.
Whenever floodlight luminaries of more than 1 000 W are installed, it is preferable to have individual branch, circuits to each of the luminaries after considering the economic aspects.
Junction boxes shall be installed near the luminaries from which connection to the light source may be taken by flexible conduits. This will help maintenance work to be carried out without disturbing the positioning of the lighting fittings.
5.2.3 Panel Boards and Switchboards
The provision of Part 1/Sec 9 of this Code shall apply. In large stadia, the areas covered by the services shall be segregated into zones and the sub distribution and distribution boards shall be so arranged and marked keeping in view their accessibility in times of need.
5.2.4 Socket-outlets and Plugs
For small stadia/halls, the provisions of Part 3/Section 3 of this Code shall apply. The need for special convenience outlets shall be considered for services enumerated in 3.2(e). Utility socket outlets shall be provided at a height of about 0.3 m from the floor except in field/arena. These shall be of weather-proof type.
5.3 Feeders
5.3.1 The utility shall be consulted as to the type of service available, whether primary or secondary, single-phase or three-phase star or delta.
5.3.2 Outdoor floodlighting installations can be made with either overhead or underground distribution feeders. From the point of view of appearance and minimum interference, the underground system is more desirable where large playing areas are involved.
5.3.3 The underground system shall either be cables directly buried or cables in conduits.
5.4 Building Substation
5.4.1 The electrical needs of sports stadia may vary from 30 kVA to 1 000 kVA, according to the size of the installation. Usually HV supply is used for large multipurpose stadia where power demand is in excess of 500 kVA. The design of location of substation and the diesel generating set, if provided, shall conform to the requirements specified in Part 2 of this Code.
5.4.2 The main substation for a sports building shall preferably be located in such a place that does not interfere with the movement of people congregating. All electrical operating areas, and control rooms shall preferably be segregated from public routes for the sporting events.
5.4.3 Some installations may justify a separate transformer on each pole of the floodlighting tower with primary wiring to each tower. In smaller installations, it may be more economical to reduce the number of transformers by serving several locations from a single transformer through secondary wiring.
5.4.4 For buildings staging national and international sports events, it shall be provided with duplicate power supply so that in the event of failure of one power supply, other one can be able to cater the total load intended to serve. The changeover should be automatic.
5.4.5 Emergency power supply by DG set/s shall be provided at strategic locations to keep the general lighting and ventilation of the sport buildings in case of normal ac power failure. The changeover should be automatic.
5.5 System Protection
The general rules for the protection of safety laid down in Part 1/Sec 22 of this Code shall apply.
5.5.1 Sports buildings are classified as ‘assembly buildings’ (Group D) from fire-safety point of view. Besides fire fighting equipment fire-detection and extinguishing system shall be provided as recommended below (see also SP 7 : 2016):
Description(1)
Fire Detection 5ystem(2)
Big halls for over 5 000 personsSmall halls, health clubs, arena, gymnasiums, etc, indoor with or without fixed seats corridors for about 1 000 persons
Automatic sprinkler and alarm system Automatic sprinkler Automatic fire alarm system
Same as above, occupancy for less than 1 000 persons
Same as above
Small indoor games halls for less than 300 personsGrandstands, stadia for outdoor gathering
Automatic fire alarm systemManually operated fire alarm systems, in offices and automatic fire alarm system in stadia, machine room, control room, etc
5.6 Building Services
5.6.1 Lighting
The general rules laid down in Part 1/Section 15 of this Code shall apply (see also SP 72).
561
5.6.1.1 Special design features
Design of sports lighting, especially in large stadia require considerations of not only the objects to be seen, the background brightness, etc, but the observer’s location in the grandstand as well. The following shall be taken into account:
a) Observers have no fixed visual axis or field of view. During the shifting of sight, even the ceiling and luminaries are likely to come into the line of vision.
b) While the game is in play, the objects of regard are not fixed, and mostly moving in a threedimensional space.
c) It is important for observers to be able to estimate accurately the object velocity and trajectory.
5.6.1.2 For the purposes of artificial lighting design, it is recommended to divide the location of sport play into general areas for more than one sport and areas for particular sport.
General areas include field houses, gymnasiums, community centre halls and other multipurpose areas. For the purposes of lighting design, the nature of sports shall be divided as follows:
a) Aerial sports (sports which are aerial in part or whole) — Badminton, basketball, handball, squash, tennis and volleyball.
b) Low level (games which are close to the ground level) — Archery, billiards, bowling, fencing, hockey, swimming and boxing.
2 For football, uniform illumination shall be provided at ground level as well as vertically for 15 m above ground.
1 It is generally conceded that the distance between the spectators and the play is primary consideration for football, as well as the potential seating capacity of the stand. The following classification is therefore described.
Free Standard provided by BIS via BSB Edge Private Limited to self-developer - bengaluru(shivaprasad.safare@tandemloop.in) 49.204.144.146.
SP 30 : 2023
5.6.1.3 Levels of illumination
For some representative types of sport, the recommended values of illumination are as given in Table 1.
Table 1 Recommended Values of Illumination
(Clause 5.5.1.3)
Sl No.
Sport
Illumination, lux
(1)
(2)
(3)
i)
Archery
Target
540
Shooting line
220
Badminton
320
6.5Building Substation
6.5.1 If the load demand is high which requires supply at voltage above 650 V a separate indoor accommodation, as near the main load centre of the hotel as possible shall be provided to accommodate switchgear equipment of supply undertaking and indoor/outdoor accommodation for the transformers. The main distribution equipment of the hotel shall preferably be located next to the substation. Separate feeders shall be provided for major loads like central air-conditioning, kitchen, laundry, swimming pool, lighting of main building and other essential loads.
6.5.2 The supply line should preferably be brought into the building underground to reduce the possibility of interruption of power supply. The accommodation for substation equipment as well as for main distribution panel shall be properly enclosed so as to prevent access to any unauthorized person. It shall be provided with proper ventilation and lighting arrangement.
6.5.3 The location and layout of building sub-station and emergency diesel generating set(s) shall be in conformance with Part 2 of this Code.
6.6 System Protection
6.6.1 General
549
The general rules for protection for safety laid down in Part 1/Sec 22 of this Code shall apply. Reference should be made to SP 7 for guidelines for fire protection of buildings.
6.6.2 For lodging and rooming houses of 3 storey and above, with a floor area more than 200 m2 with central corridor and rooms on either side, besides fire fighting equipment, manually operated electric fire-alarm system shall be provided. Both manually operated and automatic fire-alarm systems shall be provided in large hotels.
IEC 60364 (all parts)
Low-voltage electrical installations
IEC 60364-8-2 : 2018
Low-voltage electrical installations — Part 8-2: Prosumer's low-voltage electrical installations¹⁾
IEC 62955 : 2018
Residual direct current detecting device (RDC-DD) to be used for mode 3 charging of electric vehicle
IEC 61980 (all parts)
Electric vehicle wireless power transfer (WPT) systems
IEC 62196-3 : 2014
Plugs, socket-outlets, vehicle connectors and vehicle inlets — Conductive charging of electric vehicles— Part 3: Dimensional compatibility and interchangeability requirements for d.c. and a.c./d.c. pin and contact-tube vehicle couplers
IEC TS 62196
Plugs, socket-outlets, vehicle connectors and vehicles inlet — Conductive charging of electric vehicles — Part 4: Dimensional compatibility and interchangeability requirements for d.c. pin and contact-tube accessories for class II or class III applications²⁾
Installations of any luminous tube, signs or lamps on a booth, stand or amusement device with an operating voltage higher than 230/400 V a.c. shall comply with the following.
5.5.3.3.106 Location
The sign or lamp shall be installed out of arm’s reach or shall be adequately protected to reduce the risk of injury to persons.
5.5.3.3.107 Installation
The fascia or material behind luminous tube, signs or lamps shall be non-ignitable and protected as required by national regulations.
Controlgear with output voltages higher than 230/400 V a.c. shall be mounted on non-ignitable material.
c) Educational Buildings — These include buildings used for schools, colleges and daycare purposes for more than 8 hours per week involving assembly of people for instruction and education (including incidental recreation), etc.
NOTE — Larger assembly buildings recreational occupancies are covered in Part 3/Sec 20 of this Code.
5 GENERAL CHARACTERISTICS OF INSTALLATIONS
General guidelines on the assessment of characteristics of installations in buildings are given in Part 1/Sec 8 of this Code. For the purpose of installations falling under the scope of this Section the characteristics defined below generally apply.
6.4.6 Switchboards and Panel Boards
All current carrying equipment shall be totally enclosed, dust-and vermin-proof and if mounted outdoor, shall be of weatherproof construction or housed in weatherproof kiosk or cabin. Switchboards shall be of open type or cubicle type. Cubicle type boards shall be with hinged doors interlocked with switch-operating mechanisms. All switches shall bear labels indicating their functions. Switchboards shall be located away from areas likely to be crowded by the public. Suitable IP protected DBs to be use in the installation.
6.4.7 Selection of equipment shall be made according to the guidelines laid down in Part 1/Sec 16 of this Code. For the purposes of office buildings, shopping and commercial centers, miniature circuit-breakers of adequate capacity shall be preferred to switch fuse units. They can also be effectively used in place of fuses in a distribution board.
a) Diversified (mixed) office occupancy 10-15
b) Single purpose office occupancy 15-25
6.7.3.4 Car speed — These shall be as follows:
Sl No.
Occupancy
No. of Floors Served
Car Speed 20 m/s
(1)
(2)
(3)
(4)
i)
Office building
4-5
0.5-0.75
6-12
0.75-1.5
13-20
Above 1.5
ii)
Shops and departmental stores
2-2.5
Table 1Recommended Values of Illumination and Glare Index (Clause 6.6.1.1)
Sl No.(1)
Building(2)
Illumination Lux(3)
Limiting Glare Index(4)
i)
Banks:
a) Counters, typing accounting book areas
300
19
b) Public areas
150
19
ii)
Libraries:
a) Shelves
70-150
-
b) Reading rooms (newspaper, magazines)
150-300
19
c) Reading tables
300-700
22
d) Book repair and binding
300-700
22
e) Cataloging, sorting, stock rooms
150-300
19
iii)
Offices:
a) Entrance halls and reception area
150
-
b) Conference rooms, executive offices
300
19
c) General offices
300
19
d) Business machine operation
450
19
e) Drawing offices
450
16
f) Corridors and lift cars
70
-
g) Stairs
100
-
h) Lift landings
100
-
j) Telephone exchanges;
1) Manual exchange rooms (on desk)
200
16
2) Main distribution frame room
150
25
iv)
Schools and colleges:
a) Assembly halls:
1) General
150
16
2) When used for exams
300
16
3) Platforms
300
16
b) Class and lecture rooms:
1) Desks
300
16
2) Black board
200-300
-
c) Embroidery and sewing rooms
700
10
d) Art rooms
450
16
e) Libraries
(see SI No. ii above.)
16
f) Manual training
[see appropriate trades in IS 3646 (Part 2)]
-
g) Offices
300
19
h) Staff rooms, common rooms
150
19
j) Corridors
70
-
k) Stairs
100
-
v)
Shops and stores¹⁾ :
a) General areas
150-300
22
b) Stock rooms 1)
200
25
Does not cover display (showroom lighting).
6.7.3.5 For office buildings, it is desirable to have at least a battery of 2 lifts at two or more convenient points. If this is not possible, it is advisable to have at least two lifts side by side at the main entrance and one lift each at different sections of the building for inter-communication. When two lifts are installed side by side, the machine room shall be suitably planned. All machines and switchgear may be housed in one machine room.
6.7.3.6 Each lift should be protected by an RCD of 30 mA sensitivity housed in a separate enclosure accessible to Service.
Outdoor stadia: Stadia meant for use in daylight. Stadia meant for use during night under artificial lighting.
b) Based on type of game/sport:
Single game sports hall/stadia.
Multigames hall/stadia.
c) Based on utility:
Stadia meant for games only.
Multipurpose stadia for other amusements as well.
d) Based on audience-factor:
Stadia/halls meant for exhibition purposes — where groups of people congregate.
Stadia/halls meant for training and pastime — where audience may not normally be present.
NOTE — Classification d (1) includes stadia meant for staging tournaments and events, and d (2) includes games halls in educational institutions and the like where normally no exhibition is intended.
3.1.1 Reference should be made to 5.5.1.2 for classification from lighting consideration.
3.2 The electrical installation needs in sports buildings would therefore be governed by the type of use indicated in 3.1(a) to (d). A large sports complex may include the following sub-units:
a) Supply intake/voltage of supply;
b) Main substation and satellite substations, if any;
c) Central control room/switch rooms;
d) Electrification of restaurant, health clubs; hospitals, offices and other support structures;
e) Communication facilities (telephone, telex, telegraph, data processing TV, radio and press facilities);
f) Fire protection services;
g) External electrification of gardens and parking lots, service routes, lake fountains (if any);
h) Emergency electric supply system including uninterrupted power requirements;
j) Audio systems, public address/security;
k) De-watering arrangements, sewage disposal, water supply systems;
m) Gas/oil arrangements for sports flame if required; and
n) Miscellaneous requirements for power socket, microphone outlets, score-boards, etc.
Basketball
540
Billiards (on table)
540
Boxing and wrestling
540
ii)
Football (see Notes 1 and 2)
Class I
1 100
II
540
III
320
IV
220
iii)
Gymnasiums
Matches
540
General exercising
320
Hockey (field)
220
iv)
Racing
Bicycle
320
Horse
220
v)
Rifle (outdoor)
Targets
540 (vertical)
Firing point
110
Range
54
vi)
Swimming
a) Indoor Exhibition
540
Underwater ¹⁾
100 W/m ² of surface area
b) Outdoor Exhibition
220
Underwater
60 percent of indoor
Tennis (laws) Indoor
540
Outdoor
320
Table tennis
540
Volleyball
220
1) Levels recommended are for incandescent lamps. For discharge lamps W/m2would be reduced depending upon the efficiency of light source. In order that the installed flux.
5.6.1.4 Selection of light sources
For sports lighting, the following light sources are advantageous together with the considerations indicated against each:
a) Incandescent lamps (including tungsten halogen) — Where necessary, over-voltage operation can be used to advantage especially as in sports installations, the lighting systems are used for less than 500 h a year.
563
b) Fluorescent lamps — Advantageous where mounting heights are low and short projection distances are acceptable, for example tennis, bowling, trampoline and a variety of indoor sports.
c) High intensity discharge lamps — These are characterized by long life and high human efficiency. However, the inherent time delay for full glow when first energized or when there is power interruption may necessitate use of incandescent lighting system to provide emergency standby illumination in spectator areas.
For sports events, where colour rendition is important, use of fluorescent mercury lamps is recommended.
5.6.1.5 Miscellaneous considerations for lighting
a) While selecting and installing high intensity discharge or fluorescent lamps in multipurpose stadia, it is necessary to connect lamps on alternate phases of supply to avoid flicker on rapidly moving objects. Where a quite surrounding is required in order to avoid ballast hum, remote mounting of ballasts shall be considered.
b) Efforts shall be required to coordinate the lighting design for sports events with the illumination requirements for TV or film coverage. A horizontal illumination in excess of 300 lux is considered adequate for operation of black and white TV and film recording. Colour recording calls for more stringent requirements. Colour filming may also need lamps having correlated colour temperature of between 3 000 K to 7 000 K. For film/TV coverage, data on the following shall be necessary:
Camera sensitivity,
Exposure time, and
Effective aperture.
c) Group switching — Group switching of luminaries is recommended to have maximum energy saving, after considering the following factors as well:
Separate switching for lighting outside the stadia,
Requirement of lighting for training purpose,
Requirement of lighting for tournaments with film and TV coverage, and
Separate switching for playing arenas.
5.6.2 Air-conditioning
5.6.2.1 The requirements for air-conditioning and ventilation as laid down in Part 1/Sec 15 of this Code shall apply.
5.6.3 Lifts and Escalators
The general rules laid down in Part 1/Sec 15 of this Code shall apply.