For the purpose of this Part, the following definitions shall apply.
3.1 Flammable Material — A flammable material is a gas, vapour, liquid and/or mist which can react continuously with atmospheric oxygen and which may therefore, sustain fire or explosion when such reaction is initiated by a suitable spark, flame or hot surface.
3.2 Flammable Gas-Air Mixture — A mixture of flammable gas, vapour or mist with air, under atmospheric conditions, in which after ignition, combustion spreads throughout the unconsumed mixture.
3.3 Hazard — The presence, or the risk of presence, of a flammable gas-air mixture.
3.4 Explosive Gas Atmosphere — Mixture with air, under atmospheric conditions, of flammable substances in the form of gas or vapour, which, after ignition, permits self-sustaining flame propagation.
3.5 Hazardous Area — Area in which an explosive gas atmosphere is present, or may be expected to be present, in quantities, such as to require special precautions for the construction, installation and use of equipment.
3.6 Explosive (Flammable) Limits — The extreme values for the concentration of a flammable gas or vapour in air under atmospheric conditions, under which flammable gas-air mixture can be ignited by an electrical arc or spark. These limits are called the ‘lower explosive limit’ (LEL) and the ‘upper explosive limit’ (UEL).
3.7 Flammability Range — The range of gas or vapour mixtures with air between the flammable limits over which the gas mixtures are continuously explosive.
3.8 Flammable Gas or Vapour — Gas or vapour which, when mixed with air in certain proportions, will form an explosive gas atmosphere.
3.9 Flammable Liquid — A liquid capable of producing a flammable vapour, gas or mist under any foreseeable operating conditions.
3.10 Flammable Mist — Droplets of flammable liquid, dispersed in air, so as to form an explosive gas atmosphere.
3.11 Liquefied Flammable Gas — Flammable gas which, under normal ambient pressures and temperatures, is in gaseous state but which is handled in a liquid state under the applied conditions of pressure and/or temperature.
3.12 Flash Point — The temperature at which the liquid gives so much vapour that this vapour, when mixed with air, forms an ignitable mixture and gives a momentary flash on application of a small pilot flame under specified conditions of test.
3.13 Boiling Point — The temperature of a liquid boiling at an ambient pressure of 101.3 kPa.
NOTE — For liquid mixtures the initial boiling point shall be considered. ‘Initial boiling point’ is used for liquid mixtures to indicate the lowest value of the boiling point for the range of liquids present.
3.14 Ignition Temperature — The lowest temperature at which ignition occurs in a mixture of explosive gas and air when the method specified in ISO/IEC 80079-20-1 is followed.
3.15 Source of Release — A source of release is a point or location from which a gas, vapour, mist or liquid may be released into the atmosphere so that an explosive gas atmosphere could be formed.
3.16 Restricted Release — A release (normal or abnormal) of flammable gas or vapour which can be diluted below the lower flammable limit.
3.17 Unrestricted Release — A release (normal or abnormal) of flammable gas or vapour which cannot be diluted below the lower flammable limit.
3.18 Adequate Ventilation — Adequate ventilation is that which is sufficient to prevent accumulations of significant quantities of gas-air mixtures in concentration over one-fourth of the lower flammable limit.
Adequately ventilated area could be naturally ventilated or artificially ventilated.
3.19 Relative Density of Gas or Vapour — The density of a gas or a vapour relative to the density of air at the same pressure and the same temperature.
3.20 Non-hazardous (Safe) Area — Area in which an explosive gas atmosphere is not expected to be present in quantities such as to require special precautions for the construction, installation and use of equipment.
3.21 Electrical Apparatus for Hazardous Areas — Electrical apparatus which will not ignite the surrounding flammable atmosphere in which it is used.
3.22 Ignition Capable Apparatus — Apparatus which in normal operation produces sparks, hot surfaces, or a flame which can ignite a specific flammable mixture.
3.23 Safety Measures — Measures taken to ensure that electrical apparatus cannot cause an explosion.
695
3.24 Type of Protection — Specific measures applied to electrical equipment to avoid ignition of a surrounding explosive atmosphere.
3.25 Maximum Surface Temperature — Highest temperature which is attained in service under the most adverse operating conditions (but within recognized tolerances) by any part or surface of the electrical equipment, which would be able to produce an ignition of the surrounding explosive atmosphere.
NOTES
1 The most adverse conditions include recognized overloads and fault conditions recognized in the specific standard for the type of protection concerned.
2 The relevant surface temperature may be internal and/or external depending upon the type of protection concerned.
3.26 Flame Arrester — A device for releasing gas from an enclosure in such a way that in case of an internal explosion there is no appreciable increase in internal pressure and the released gas will not ignite the surrounding flammable atmosphere.
3.27 Inert Gas — A gas which cannot be ignited when mixed with a flammable gas or vapour in any concentration.