4.4.1 The protective measure ensure:
a) during an earth fault, the voltages between exposed conductive parts and extraneous conductive parts in the location is minimized; and
b) rapid disconnection of the faulty circuit.
271
4.4.2 In order to reduce voltage appearing between exposed and extraneous conductive parts, protective equipotential bonding zones are created by connecting exposed and extraneous conductive parts to the Main earth terminal (MET or earth busbar) of the zone.
4.4.3 An installation may consist of number of zones. For instance, when an installation supplies number of buildings, equipotential bonding is necessary in each building so that each constitutes a zone with a reference point to which the exposed conductive parts of the circuits and extraneous conductive parts in that building are connected. Large buildings shall have several zones with in the building
4.4.4 Rapid disconnection of the circuit subjected to earth fault is met by limiting value of the earth fault loop impedance of each circuit determined by the type and current rating of the protective device such that disconnection occurs before the prospective touch voltage reaches a harmful value.
4.4.5 It is recommended that the maximum sustained voltage developed under fault conditions between exposed metal required to be earthed and the consumer’s earth terminal shall not exceed 50 V rms.
4.5 TN System (Earth Fault Loop Impedance is important for Automatic Disconnection of supply during Earth Fault)
4.5.1 The characteristics of the protective devices and the cross-sectional area of conductors shall be chosen such that if a fault of negligible impedance occurs anywhere between a phase conductor and a protective conductor or exposed conductive part, automatic disconnection of the supply occurs within the minimum possible safe time. The time of operation depends on the magnitude of the contact potential. Generally, 65 V may be cleared within 10 s and voltages of the order of 240 V and above shall be cleared instantaneously
This requirement is met if:
Z s × I a < U o
Where,
Z s = fault loop impedance,
I = current ensuring the automatic operation of disconnecting device, and
Uo = conventional voltage limits.
4.5.2 In order to provide thermal protection to the protective conductor and considering the requirements of IS 732, automatic disconnection of supply shall take place if the fault loop impedance is
Where,
Z s ( m ) = the measured impedance of the fault current loop starting and ending at the point of fault (Ω);
U o : = the line conductor to earthed neutral voltage (V); and
I a = the current causing the automatic operation of the protective device within the stipulated disconnection time.
4.5.3 Where the measured value of the fault loop impedance exceeds 2 × U_0 / 3 × I_a precise assessment of compliance with IS 732 is recommended.
4.5.4 Recommended Maximum Earth Fault Loop Impedance Values for MCB : zs(m) (see Table 2)
| MCB rating in Amps | 6 | 10 | 16 | 20 | 25 | 32 | 40 | 50 | 63 | 80 | 100 | 125 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Z<sub>S</sub> in Ω (Type B MCB) | 5.11 | 3.07 | 1.92 | 1.53 | 1.23 | 0.96 | 0.77 | 0.61 | 0.49 | 0.38 | 0.31 | 0.25 |
| Z<sub>S</sub> in Ω (Type C MCB) | 2.56 | 1.53 | 0.96 | 0.77 | 0.61 | 0.48 | 0.38 | 0.31 | 0.24 | 0.19 | 0.15 | 0.12 |
| Z<sub>S</sub> in Ω (Type D MCB) | 1.28 | 0.77 | 0.48 | 0.38 | 0.31 | 0.24 | 0.19 | 0.15 | 0.12 | 0.10 | 0.08 | 0.06 |