3.3.1 Accessory — A device, other than current-using equipment, associated with such equipment or with the wiring of an installation.
3.3.2 Aerial Conductor — Any conductor which is supported by or suspended on insulators above the ground and is directly exposed to the weather.
NOTE — The following four classes of aerial conductors are recognized:
a) Bare aerial conductors;
b) Covered aerial conductors;
c) Insulated aerial conductors;
SP 30 : 2023
d) Weatherproof neutral-screened cable; and
e) Aerial bunched cable.
3.3.3 Back-up Protection — Protection which is intended to operate when a system fault is not cleared or abnormal condition not detected in the required time, because of failure or inability of other protection to operate or failure of appropriate circuit-breaker(s) to trip.
3.3.4 Barrier — A part providing a defined degree of protection against contact with live parts, from any usual direction of access.
3.3.5 Basic Insulation — Insulation of hazardous-live-parts which provides basic protection.
NOTE — This concept does not apply to insulation used exclusively for functional purposes.
3.3.6 Basic Protection — Protection against electric shock under fault-free condition.
3.3.7 Bonding Conductor — A protective conductor providing equipotential bonding.
3.3.8 Bonding Network (BN) — A set of interconnected conductive parts that provide a path for current at frequencies from direct current (d.c.) to radio frequency (RF) intended to divert, block or impede the passage of electromagnetic energy.
3.3.9 Bonding Ring Conductor (BRC) — A bus earthing conductor in the form of a closed ring.
NOTE — Normally the bonding ring conductor, as part of the bonding network, has multiple connections to the common bonding network (CBN) that improves its performance.
3.3.10 Bunched — Cables are said to be ‘bunched’ when two or more are contained within a single conduit, duct or groove or, if not enclosed, are not separated from each other.
3.3.11 Buried Direct — A cable laid in the ground in intimate contact with the soil.
3.3.12 Busbar Trunking System — A type-tested assembly, in the form of an enclosed conductor system comprising solid conductors separated by insulating materials. The assembly may consist of units such as:
a) Busbar trunking units, with or without tap-off facilities;
b) Tap-off units where applicable; and
c) Phase-transposition, expansion, building- movement, flexible, end-feeder and adaptor units.
3.3.13 Bypass Equipotential Bonding Conductor — Bonding conductor connected in parallel with the screens of cables.
3.3.14 Wire — Flexible cylindrical conductor, with or without an insulating covering, the length of which is large with respect to its cross-sectional dimensions.
NOTE — The cross-section of a wire may have any shape, but the term “wire” is not generally used for ribbons or tapes.
3.3.15 Cable — A length of single-insulated conductor (solid or stranded), or two or more such conductors, each provided with its own insulation, which are laid up together. The insulated conductor or conductors may or may not be provided with an overall mechanical protective covering.
3.3.16 Cable, Armoured — A cable provided with a wrapping of metal (usually in the form of tape or wire) serving as a mechanical protection.
3.3.17 Cable, Flexible — A cable containing one or more cores, each formed of a group of wires, the diameters of the cores and of the wires being sufficiently small to afford flexibility.
3.3.18 Cable Bracket — A cable support consisting of single devices fixed to elements of building or plant construction.
3.3.19 Cable Channel — An enclosure situated above or in the ground, open or ventilated or closed, and having dimensions which do not permit the access of persons but allow access to the conductor and/or cables throughout their length during and after installation.
NOTE — A cable channel may or may not form part of the building construction.
3.3.20 Cable Cleat — A component of a support system which consists of elements spread at intervals along the length of the cable or conduits and which mechanically retains the cable or conduit.
3.3.21 Cable Coupler — A means enabling the connection, at will, of two flexible cables. It consists of a connector and a plug.
3.3.22 Cable Ducting — A manufactured enclosure of metal or insulating material, other than conduit or cable trunking, intended for the protection of cables which are drawn-in after erection of the ducting, but which is not specifically intended to form part of a building structure.
3.3.23 Cable Ladder — Cable support consisting of a series of transverse supporting elements rigidly fixed to main longitudinal supporting members.
3.3.24 Cable Tray — Cable support consisting of a continuous base with raised edges but no covering.
NOTE — A cable tray may be perforated or mesh.
3.3.25 Cable Trunking — System of closed enclosures comprising a base with a removable cover, intended for the complete surrounding of insulated conductors, cables, cords and/or for the accommodation of other electric equipment including information technology equipment.
3.3.26 Cable Tunnel — Corridor whose dimensions allow persons to pass freely throughout the entire length, containing supporting structures for cables and joints and/or other elements of wiring systems.
3.3.27 Cartridge Fuse Link — A device comprising a fuse element or several fuse elements connected in parallel enclosed in a cartridge usually filled with an arc-extinguishing medium and connected to terminations. The fuse link is the part of a fuse which requires replacing after the fuse has operated.
3.3.28 Circuit, Final, Sub — An outgoing circuit connected to one-way distribution fuse-board and intended to supply electrical energy at one or more points to current-using appliances, without the intervention of a further distribution fuse-board other than a one-way board. It includes all branches and extensions derived from that particular way in the board.
3.3.29 Cold Tail — Part for connecting the heating resistor and the wire from power supply and conceiving no obvious heating.
3.3.30 Combustible — Capable of burning.
3.3.31 Common Equipotential Bonding System, Common Bonding Network — Equipotential bonding system providing both protective equipotential bonding and functional equipotential bonding
3.3.32 Conductor, Bare — A conductor not covered with insulating material.
3.3.33 Conductor, Earthed — A conductor with no provision for its insulation from earth.
NOTE — A protective conductor in a TN-S system.
3.3.34 Conductor, Insulated — A conductor adequately covered with insulating material of such voltage grade and thickness as to prevent danger.
3.3.35 Conductor for Portable Appliances — A combination of a plug and socket arranged for attachment to a portable electrical appliance or to a flexible cord.
3.3.36 Confined Conductive Location — A location having surfaces which are mainly composed of extraneous conductive parts and which are of such dimensions that movement is restricted to such an extent that contact with surfaces is difficult to avoid (for example in a boiler).
3.3.37 Connector — The part of a cable coupler or of an appliance coupler which is provided with female or male contact and is intended to be attached for a temporary duration to the other part of the flexible cable connected to the supply.
3.3.38 Connector Box or Joint Box — A box forming a part of wiring installation provided to contain joints in the conductors of cables of the installation.
3.3.39 Consumer Unit (may also be known as a Consumer Control Unit or Electricity Control Unit) — A particular type of distribution board comprising a type-tested coordinated assembly for the control and distribution of electrical energy, principally in domestic premises, incorporating manual means of double-pole isolation on the incoming circuit(s) and an assembly of one or more fuses, circuit-breakers, residual current
operated devices or signaling and other devices proven during the type-test of the assembly as suitable for such use.
3.3.40 Consumer’s Terminals — The ends of the electrical conductors situated upon any consumer’s premises and belonging to him at which the supply of energy is delivered from the service line.
3.3.41 Cord, Flexible — A flexible cable having conductor of small cross-sectional area. Two flexible cords twisted together are known as ‘Twin Flexible Cord’.
NOTE — For the maximum diameter and minimum number of wires for flexible cord, see IS 8130.
3.3.42 Cut-out — Any appliance for automatically interrupting the transmission of electricity through the conductor when the current rises above a pre-determined amount and shall also include fusible cut-out.
3.3.43 Dead — At or about earth potential and/or disconnected from any live system.
3.3.44 Direct Contact — Electric contact of persons or animals with live parts.
3.3.45 Discrimination — Ability of a protective device to operate in preference to another protective device in series.
3.3.46 Distribution Circuit (of Buildings) — Electric circuit supplying distribution boards.
3.3.47 Distribution Fuse-board — An assemblage of parts including one or more fuses arranged for the distribution of electrical energy to final sub-circuits.
3.3.48 Double Insulation — Insulation comprising both basic insulation and supplementary insulation.
13
3.3.49 Duct — A closed passage way formed under ground or in a structure and intended to receive one or more cables which may be drawn in.
3.3.50 Ducting (see 3.3.49)
3.3.51 Earth — The conductive mass of the earth, whose electric potential at any point is conventionally taken as zero.
3.3.52 Earth (local) — Part of the Earth which is in electric contact with an earth electrode and the electric potential of which is not necessarily equal to zero.
3.3.53 Earthing Arrangement — All the electric connections and devices involved in the earthing of a system, an installation and equipment.
3.3.54 Earth Electrode — Conductor or group of conductors in intimate contact with and providing an electrical connection to earth.
3.3.55 Earthing — Connection of the exposed conductive parts of an installation to the main earthing terminal of that installation.
3.3.56 Earthed Concentric Wiring — A wiring system in which one or more insulated conductors are completely surrounded throughout their length by a conductor, for example a sheath, which acts as a PE or PEN conductor.
3.3.57 Earthing Conductor — A protective conductor connecting the main earth terminal (or equipotential bonding conductor of an installation when there is no earth bus) to an earth electrode or to other means of earthing.
3.3.58 Earth Electrode Network — Part of an earthing arrangement comprising only the earth electrodes and their interconnections.
3.3.59 Electric Shock — Physiological effect resulting from an electric current passing through a human or animal body.
3.3.60 Electrical Installation (of a Building) — Assembly of associated electric equipment having co-ordinated characteristics to fulfil specific purposes.
3.3.61 Electrically Independent Earth Electrodes — Earth electrodes located at such a distance from one another that the maximum current likely to flow through one of them does not significantly affect the potential of the other(s).
3.3.62 Electrical Source for Safety Services — Electrical source intended to be used as part of an electrical supply system for safety services.
3.3.63 Electrical Supply System for Safety Services — A supply system intended to maintain the operation of essential parts of an electrical installation and equipment:
a) For health and safety of persons and livestock; and
b) To avoid damage to the environment and to other equipment.
NOTE — The supply system includes the source and the circuit(s) up to the terminals of the electrical equipment.
3.3.64 Emergency Switching — Opening operation of a switching device intended to remove electric power from an electrical installation to avert or alleviate a hazardous situation.
3.3.65 Equipotential Bonding — Electrical connection putting various exposed conductive parts and extraneous conductive parts at a substantially equal potential.
NOTE — In a building installation equipotential bonding conductors shall interconnect the following conductive parts:
a) Protective conductor;
b) Earth continuity conductor; and
c) Risers of air-conditioning system and heating systems (if any).
3.3.66 Exposed Conductive Part — A conductive part of electrical equipment, which can be touched and which is not normally live, but which may become live under fault conditions.
NOTE —Typical exposed conductive parts are walls of enclosures, operating handles, etc.
3.3.67 External Influence — Any influence external to an electrical installation which affects the design and safe operation of that installation
3.3.68 Flammable — A material capable of being easily ignited.
3.3.69 Extraneous Conductive Part — A conductive part not forming part of the electrical installation and liable to introduce an electric potential, generally the electric potential of a local earth.
3.3.70 Factory Built Assembly (of LV Switchgear and Controlgear) — See IS/IEC 61439-2.
3.3.71 Earth Fault — Occurrence of an accidental conductive path between a live conductor and the exposed conductive part or a protective conductor or earthing arrangement.
NOTE — The conductive path can pass through a faulty insulation, through structures (for example, poles, scaffoldings, cranes, ladders), or through vegetation (for example trees, bushes) and can have a significant impedance.
3.3.72 Flammability — Ability of a material or product to burn with a flame under specified test condition.
3.3.73 Fitting, Lighting — A device for supporting or containing a lamp or lamps (for example, fluorescent or incandescent) together with any holder, shade, or reflector, for example, a bracket, a pendant with ceiling rose, or a portable unit.
3.3.74 Functional Bonding Conductor — Conductor provided for functional equipotential bonding.
3.3.75 Functional Earthing — Earthing a point or points in a system or in an installation or in equipment for purposes other than electrical safety.
3.3.76 Gas Installation Pipe — Any pipe, not being a service pipe or pipe comprised in a gas appliance, for conveying gas for a particular consumer and including any associated valve or other gas fitting.
3.3.77 Indirect Contact — Electric contact of persons or animals with exposed-conductive-parts which have become live under fault conditions.
NOTE — Extraneous conductive parts are generally at earth potential.
3.3.78 Insulation — All the materials and parts used to insulate conductive elements of a device.
NOTE — See also the definitions for basic insulation, double insulation, reinforced insulation and supplementary insulation.
3.3.79 Insulation Co-ordination — Selection of the dielectric strength of equipment in relation to the operating voltages which can appear on the electric power system for which the equipment is intended, and taking into account the service environment and the characteristics of the available preventing and protective devices.
3.3.80 Ignitability — Measure of the ease with which a specimen can be ignited due to the influence of an external source, under specified test condition.
3.3.81 Ignition — Initiation of combustion.
3.3.82 Installations — Assembly of associated electric equipment having coordinated characteristics to fulfil specific purposes.
3.3.83 Isolation — Function intended to make dead for reasons of safety all or a discrete section of the electrical installation by separating the electrical installation or section from every source of electric energy
3.3.84 Live or Alive — Electrically charged so as to have a potential difference from that of earth.
3.3.85 Local Earthing — Part of the Earth which is in electric contact with an earth electrode and the electric potential of which is not necessarily equal to zero.
3.3.86 Line Conductor — Conductor which is energized in normal operation and capable of contributing to the transmission or distribution of electric energy but which is not a neutral or mid-point conductor.
NOTE — Also, called as Phase conductor (in a.c. systems) which is a deprecated term now a days.
3.3.87 Main Earthing Terminal — Terminal or bus bar which is part of the earthing arrangement of an installation and enabling the electric connection of a number of conductors to achieve equipotential bonding.
3.3.88 Meshed Bonding Network (MESH-BN) — Bonding network in which all associated equipment frames, racks and cabinets and usually the d.c. power return conductor are bonded together as well as at multiple points to the CBN and may have the form of a mesh.
3.3.89 Minimum Illumination — Illumination for emergency lighting at the end of rated operating time.
15
3.3.90 Minor Works — Additions and alterations to an installation that do not extend to the provision of a new circuit
3.3.91 Mechanical Maintenance — The replacement, refurbishment or cleaning of lamps and non-electrical parts of equipment, plant and machinery.
3.3.92 Multiple Earthed Neutral System — A system of earthing in which the parts of an installation, specified to be earthed are connected to the general mass of earth and, in addition, are connected within the installation to the neutral conductor of the supply system.
NOTE — This definition is applicable only for voltages up to 1000 Va.c.
3.3.93 Neutral or Neutral Conductor (Symbol N) — A conductor connected to the neutral point of a system and capable of contributing to the transmission of electrical energy.
The term also means the equivalent conductor of an IT or d.c. system unless otherwise specified in the regulations and also identifies either the mid-wire of a three-wire d.c. circuit or the earthed conductor of a two- wire earthed d.c. circuit.
3.3.94 Non-flame Propagating Component — Component which is liable to ignite, as a result of an applied flame, but in which the flame does not propagate and which extinguishes itself within a limited time after the flame is removed.
3.3.95 Origin of an Electrical Installation — The point at which electrical energy is delivered to an electrical installation.
NOTE — An electrical installation may have more than one origin.
3.3.96 Overcurrent — A current exceeding the rated value. For conductors, the rated value is the current carrying capacity.
3.3.97 Overcurrent Detection — A method of establishing that the value of current in a circuit exceeds a predetermined value for a specified time
3.3.98 PEL Conductor — A conductor combining the function of both a protective earthing and a line conductor.
3.3.99 PEM Conductor — A conductor combining the function of both a protective earthing conductor and a midpoint conductor.
3.3.100 PEN Conductor — A conductor combining the functions of both protective earthing conductor and neutral conductor.
3.3.101 Parallel Earth Continuity Conductor — Conductor usually laid along the cable route to provide a continuous low impedance metallic earth connection between the earthing systems at the ends of the cable route.
3.3.102 Phase Conductor — Phase conductor (in a.c. systems) is replaced with Line conductor.
3.3.103 Point (in Wiring) — A termination of the fixed wiring intended for the connection of current using equipment.
3.3.104 Powertrack — A system component, which is generally a linear assembly of spaced and supported busbars, providing electrical connection of accessories.
3.3.105 Powertrack System (PT System) — An assembly of system components including a powertrack by which accessories may be connected to an electrical supply at one or more points (predetermined or otherwise) along the power track.
NOTE — The maximum current rating of a power track system is 63 A.
3.3.106 Protective Conductor — A conductor used for some measures of protection against electric shock and intended for connecting together any of the following parts:
a) Exposed conductive parts;
b) Extraneous conductive parts;
c) The main earthing terminal; and
d) The earthed point of the source, or an artificial neutral.
3.3.107 Protective Earthing — Earthing a point or points in a system or in an installation or in equipment, for purposes of electrical safety.
3.3.108 Protective Euqipotential Bonding — Equipotential bonding for the purpose of safety.
3.3.109 Protective Multiple Earthing (PME) — An earthing arrangement, found in TN systems, in which the earthing conductor (either PEN or PE) is connected to local earthing for the purpose of reducing fault loop impedance and in case of PEN conductor, to limit potential of line conductor to earth during neutral disconnection.
3.3.110 Protective Separation — Separation of one electric circuit from another by means of:
a) Double insulation;
b) Basic insulation and electrically protective screening; or
c) Reinforced insulation.
3.3.111 Service — The conductors and equipment required for delivering energy from the electric supply system to the wiring system of the premises served.
3.3.112 Socket-outlet and Plug — Socket-outlet is an accessory having socket-contacts designed to engage with the pins of a plug and having terminals for the connection of cables or cords. Plug is connector attached to a cable.
3.3.113 Reinforced Insulation — Insulation of hazardous-live-parts which provides a degree of protection against electric shock equivalent to double insulation.
NOTE — Reinforced insulation may comprise several layers which cannot be tested singly as basic insulation or supplementary insulation.
3.3.114 Resistance Area (for an Earth Electrode only) — The surface area of ground (around an earth electrode) on which a significant voltage gradient may exist.
3.3.115 Response Time — the time from a sudden change of a control quantity until the corresponding change of an output quantity has reached a specified fraction of its final value.
3.3.116 Ring Final Circuit — A final circuit arranged in the form of a ring and connected to a single point of supply.
3.3.117 Safety Service — An electrical system for electrical equipment provided to protect or warn persons in the event of a hazard, or essential to their evacuation from a location.
3.3.118 Simple Separation — Separation between electric circuits or between an electric circuit and local earth by means of basic insulation.
3.3.119 Space Factor — The ratio (expressed as a percentage) of the sum of the overall cross-sectional areas of cables (including insulation and sheath) to the internal cross-sectional area of the conduit or other cable enclosure in which they are installed. The effective overall cross-sectional area of a non-circular cable is taken as that of a circle of diameter equal to the major axis of the cable.
3.3.120 Spur — A branch cable connected to a main line at a point on its route.
3.3.121 Standby Supply System — A system intended to maintain supply to the installation or part thereof, in case of interruption of the normal supply, for reasons other than safety of persons.
NOTE — Standby supplies are necessary, for example, to avoid interruption of continuous industrial processes or data processing.
3.3.122 Supplementary Insulation — Independent insulation applied in addition to basic insulation for fault protection.
3.3.123 System — An electrical system consisting of a single source or multiple sources running in parallel of electrical energy and an installation. Types of system are identified as follows, depending upon the relationship of the source, and of exposed-conductive parts of the installation, to Earth:
a) TN system — A system having one or more points of the source of energy directly earthed, the exposed conductive-parts of the installation being connected to that point by protective conductors.
17
b) TN-C system — A system in which neutral and protective conductor functions are combined in a single conductor throughout the system.
c) TN-S system — A system having separate protective conductor throughout the system.
d) TN-C-S system — A system in which neutral and protective conductor functions are combined in a single conductor in part of the system.
e) TT system — A system having one point of the source of energy directly earthed, the exposed-conductiveparts of the installation being connected to the earth electrodes electrically independent of the earth electrodes of the source.
f) IT system — A system in which all live parts are isolated from earth or one point connected to earth through an impedance. The exposed-conductive-parts of the electrical installation are earthed independently or collectively or to the earthing of the system.
NOTE — The types of systems depending upon the relationship to the source and of the exposed conductive parts of the installation to earth are defined in IS 3043.