Part 4Electrical Installations in Industrial Buildings
Electrical installation in industrial buildings requires special attention in design with a basic consideration for ‘safety at work-places’, quality and continuity of supply, energy conservation.
The layout of electrical installation should facilitate maintenance with ease and free access. Distribution shall be designed so that fault localization is possible targeting lowest down time.
Keeping in view the tariff structures depending on Time of Day (ToD), as also an economic necessity; conserving power, maintaining power factor nearest to unity, limiting harmonic effects shall be considered as important aspects.
For reliability and continuity of supply for essential/continuous operations, standby and emergency supply sources/networks shall be designed.
Locations in industrial buildings which are by their nature hazardous, require special treatment in respect of design of electrical installations therein. Such special rules for hazardous areas are covered in Part 7 of the Code and these shall be complied with in addition to the general rules specified in that Part.
In 4 of this Part, an attempt has been made to classify industrial installations depending on the specified criteria therein. Such a classification, it is hoped would help identify the specific nature of each industry and the locations therein, assisting the design engineer in the choice of equipment and methods of installation.
1Scope
1.1 This Part of the Code (Part 4) covers the guidelines for design and construction of electrical installations in industrial buildings.
1.2 This Part does not cover specific areas in industrial sites, such as office buildings, workers rest rooms, medical facilities, canteen annexe, etc, for which requirements stipulated in the relevant sections of Part 3 of the Code apply.
1.3 This Part also does not cover locations in industrial sites that are by nature hazardous for which the provisions of Part 7 of the Code apply.
4Classification of Industrial Buildings
Industry by definition includes manufacturing, processing, service sectors under which IT sector is also considered as Industry. However, for the purpose of this section industry basically include any building or part of building or structure, in which products or materials of all kinds and properties are stored, fabricated, assembled, manufactured or processes. For example, assembly plants, laboratories, dry cleaning plants, pumping stations, refineries, dairies, saw mills, chemical plants, workshops, distilleries, steel plants, etc.
Industrial installations are of various types. Single industrial site may comprise electrical loads of varying types and requirements. Classification of Industries is based on three criteria as given in 4.1 to 4.3.
4.1 Classification Based on Fire Safety
4.1.1 Industrial buildings are classified into Group G from the fire safety point of view in SP 7. Buildings under Group G are further subdivided as follows:
a) Subdivision G-1 — Buildings used for low hazard industries — Includes any building in which the contents are of such low combustibility and the industrial processes or operations conducted therein are of such a nature that there are no possibilities for any self-propagating fire to occur and the only consequent danger to life and property may arise from panic, fumes or smoke, or fire from some external source.
b) Subdivision G-2 — Buildings used for moderate hazard industries — Includes any building in which the contents or industrial processes of operations conducted therein are liable to give rise to a fire which will burn with moderate rapidity and give off a considerable volume of smoke but from which neither toxic fumes nor explosions are to be feared in the event of fire.
c) Subdivision G-3 — Buildings used for high hazard industries — Includes any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with extreme rapidity or from which poisonous fumes or explosions are to be feared in the event of fire.
NOTE — SP 7 includes Group J buildings for such location where storage, handling, manufacture or processing of highly combustible or explosive materials or products are being carried out. Such installations including such high hazard locations in Group G classification shall comply with the special rules of Part 7 of the Code.
SP 30 : 2023
4.1.2 Typical list of industries for different class of fire hazard are given in Annex B.
4.2 Classification Based on Power Consumption
Industrial buildings may also be classified depending on the quantum of electric power requirements for its services as given in Table 1.
Loads within the industrial site could be divided depending on their nature and size. For guidance, the classification given in Table 2 shall be referred to.
4.3 Classification Based on Pollution
For the propose of evaluating creepage distances and clearances, the following four degrees of pollution in the micro-environment are established:
a) Pollution degree 1 — No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
b) Pollution degree 2 — only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected.
c) Pollution degree 3 — Conductive pollution occurs, or dry non-conductive pollution occurs which becomes conductive due to condensation — which is to be expected.
d) Pollution degree 4 — Continuous conductivity occurs due to conductive dust, rain or other wet conditions.
1 Clearances and creepage distances according to the different pollution degrees are given in Tables 13 and 15 of IS/IEC 60947-1. Unless otherwise stated by the relevant product standard, equipment for industrial applications is generally for use in pollution degree 3 environment. However, other pollution degrees may be considered to apply depending upon applications or the micro-environment.
a) The pollution degree of the micro-environment for the equipment may be influenced by installation in an enclosure. Means may be provided to reduce pollution at the insulation under consideration by effective use of enclosures, encapsulation or hermetic sealing. Such means to reduce pollution may not be effective when the equipment is subject to condensation or if, in normal operation, it generates pollutants itself.
b) Pollution will become conductive in the presence of humidity. Pollution caused by contaminated water, soot, metal or carbon dust is inherently conductive. Small clearances can be bridged completely by solid particles, dust and water and therefore minimum clearances are specified where pollution may be present in the micro-environment.
Table 1 Classification Based on Power Consumption
(Clause 4.2)
Sl No.
Description¹⁾
Average Power Requirement
Examples
(1)
(2)
(3)
(4)
i)
Light industries
Up to 50 kVA
Hosiery, tailoring and jewellery
ii)
Average industries
Above 50 kVA up to 2 000 kVA
Machinery, engine fitting, motor cars, aircraft, light pressings, furniture, pottery, glass, tobacco, electrical manufacturing and textile (see Note)
iii)
Heavy industries
Above 2 000 kVA
Heavy electrical equipment, rolling mills, structural steel works, tube making, foundries, locomotives, ship-building and repairing, chemical factories, factories for metal extraction from ores, etc.
6.1Industrial Substations
The general requirements for substation installations given in Part 2 of the Code shall apply in addition to those given below.
If the load demand is high, which may necessitate supply above 650 V or if conditions of supply of local Electric supply Company requires so, a separate substation should be set up. For an outdoor substation, general guidelines as given in Part 2 of the Code shall apply. For bringing the supply into the factory building, a separate indoor accommodation, as close as possible to the main load centre, should be provided to house the switchgear equipment.
The supply conductors should preferably be brought into the building underground to reduce the possibility of interruption of power supply. The accommodation for substation equipment as well as for main distribution panel shall be properly chosen to prevent access by any unauthorized person. It shall be provided with proper ventilation and lighting. In cases where the load currents are high (400 A and above) and the transformers are located just outside the building, a busbar trunking system may be desirable. These trunkings should, however, be straight and short as far as possible.
6.1.1 Location of Transformers and Switchgear
Location of transformer shall preferably at load centre subject restrictions related hazards such as fire. Special attention shall be given to mandatory provisions related to oil filled transformers. Use of K class insulating liquids having fire point > 300° C may be considered.
Requirement of indoor or outdoor transformer sub-station may depend on site, type of industry, environmental conditions and other factors of external influences. Location of control switchgears its accessibility from the point of view of operation shall be precisely designed.
Protection on primary and secondary side of transformer shall conform requirements mandated under CEA (Measures related to Safety and Electric Supply) Regulations, 2010 (latest amended version).
Restricted areas shall be precisely marked and suitably locked so that unauthorised person shall not have an access within.
6.1.2 For small substations up to 1 600 kVA capacity, it is also possible to locate the substation at the load centre, without a separate room. This yields considerable economies in cost. In such cases, the transformer shall be of dry type.
6Supply Characteristics and Parameters
6.0 General
The arrangement of the electrical system in industrial plants and the selection of electrical equipment depends largely on the type of manufacturing process, the reliability of supply and adequate reserve of electrical capacity are the most important factors to avoid interruption of supply.
All electrical installation shall be suitable for the voltage and frequency of supply available.
Depending on load single/three phase or higher supply voltage band may be considered. Though the use of high voltage supply entails the provision of space and the capital cost of providing a suitable transformer substation on the consumer’s premises, the following advantages are gained:
a) Advantage in tariff,
b) More effective earth fault protection for heavy current circuits,
c) Elimination of interference with supplies to other consumers permitting the use of large size motors, welding plant, etc., and
d) Better control of voltage regulation and more constant supply voltage.
In very large industrial buildings where heavy electric demands occur at scattered locations, the economics of electrical distribution at high voltage from the main substation to other subsidiary transformer substations or to certain items of plant, such as large motors, furnaces, etc, should be evaluated. The relative economy attainable by use of medium or high voltage distribution and high voltage plant is a matter for expert judgement and individual assessment in the light of experience by a professionally qualified electrical engineer.
5General Characteristics of Industrial Buildings
General guidelines on the assessment of characteristics of installations in buildings are given in (Part 1/Sec 8) of the Code. For the purposes of installations falling under the scope of this Part 4, the characteristics given below shall apply.
5.1 Environment
The following environmental factors shall apply to industrial installations:
Environment
Characteristics
Remarks
(1)
(2)
(3)
Presence of water
Presence of water negligible, or possibilities of free falling drops or sprays, moisture
Depends on the location. For further details see (Part 1/Sec 8) of the Code
Presence of foreign solid bodies
These conditions include possibilities of presence of foreign solid bodies of various sizes likely to affect electrical equipment
Depends on the location. For further details see (Part 1/Sec 8) of the Code
Presence of corrosive polluting substances
Atmospheric where the presence of corrosive or polluting substances is significant
Industrial installations, situated by the sea, chemical works, cement works where the pollution arises due to abrasive, insulating or conducting
Intermittent or accidental subjection to corrosive or polluting chemical substances being used or produced
Dust factory laboratories boiler rooms, etc.
Continuous pollution
Chemical works
Mechanical stresses
Impact and vibration of low severity impact/ vibration of high severity
Household and similar conditions industrial installations subject to severe conditions
Seismic effect and lightning
-
Depends on the location of the buildings
(1)
(2)
(3)
Contact of persons with earth potential
Persons are frequently in touch with extraneous conductive parts or stand on conducting surfaces Persons are in permanent contact with metallic surroundings and for whom the possibility of interrupting contact is limited
Locations with extraneous conducting parts, either numerous or large area metallic surrounding, such as boilers and tanks
Conditions of evacuation
Low density occupation, easy conditions of evacuation
This category applies to buildings of normal or low height
Nature of processed or stored material
Existence of fire-risks, where there is manufacturing, processing or storage of flammable materials, including presence of dust/smoke
Wood-working shop, paper factories, textile mills, etc
Processing or storage of low-flash-point materials including presence of explosive dust
Oil refineries, hydrocarbon stores
5.2 Compatibility
In industrial installations, an assessment shall also be made of any characteristics of equipment likely to have harmful effects upon other equipment or other services (see Part 1/Sec 8 of the Code).
5.3 Maintainability
Assessment shall also be made of the frequency and quality of maintenance of the installation (see Part 1/Sec 8 of the Code).
6.2Distribution of Power
6.2.1 From the point of supply, power is distributed to loads in steps depending on quantum of load and expanse. Main control panel, sub-distribution and local distributions panels shall have appropriate control switchgears to isolate and break supply as desired. Settings shall be done with appropriate discrimination to maintain sequence of tripping. Local isolation in case of fault shall be important aspect of design.
6.2.2 Electrical panels/switch-boards may be floor or wall mounted and designed conforming IS/IEC 61439. Access routes shall always be maintained free without hindrances. Clear space around/arc-flash distances as mentioned under Part 1 Section 22 shall be maintained. Provision of separate room and adequate ventilation/ positive pressure may be necessary to protect panels from external influences like dust, corrosive smokes, etc.
Switch-boards shall be so designed and installed so that provisions considering possibilities of internal arc fault are adequate and tested (IEC/TR 61641). Where necessary, internal arc-fault mitigation system (IAMS) may be adopted.
6.2.3 Cables, bus-duct routes shall be well planned and maintained considering risk factors. Cables at difference voltage levels should be laid with separation at least 250 mm and clearly identified. Cables at voltages above 1 000 V should be laid at the lowest level in trenches, and at the highest level on walls. Use of cable ladder, trey helps structured cabling work. Earth continuity shall be properly maintained in such work. All entry points shall be properly sealed with fire resistant material. Method of construction shall be as per IS 1255.
6.2.4 All switchgear equipment used in industrial installations shall have appropriate ingress protection. selection shall also be done considering appropriate range and setting facility of overload, short-circuit currents and other add-on protections. All switchgear equipment used in industrial installations shall be metal enclosed. Switchgear shall not be mounted on woodwork.
6.2.5 In certain installations where supply is from remote transformer substations, it may be necessary to protect main circuits with circuit-breakers operated by earth leakage trips, in order to ensure effective earth fault protection.
6.2.6 Where large electric motors, furnaces or other heavy electrical equipment is installed, the main circuits shall be protected by circuit-breakers or contactors of air-break or oil-immersed type fitted with suitable instantaneous and time delay over current devices together with earth leakage and back-up protection where necessary.
6.2.7 It may be necessary to provide for connection of capacitors for power-factor correction; and when capacitors are to be installed advice of capacitor and switchgear manufacturers shall be sought.
6.2.8 Sufficient additional space shall be provided for modifications, alterations, anticipated future extensions.
SP 30 : 2023
6.4Earthing in Industrial Premises
Earth and earthing system shall conform IS 3043 and Part 1/Sec 18 of this code. Schematic drawing of earthing system shall be prepared and updated version be maintained.
6.4.1 In factories and workshops all metal conduits, trunking, cable sheaths, switchgear, distribution boards, starters, motors and all exposed conductive parts and extraneous conductive parts shall be bonded together and connected to earth system efficiently.
6.4.2 Earth Electrodes
Selection, number and location(s) of Earth electrode(s) shall be as per soil resistivity, design requirement in respect of limiting value of earth fault loop impedance. In case of multiple earth electrodes grid may be formed. System shall be so designed that testing of individual earth electrode is possible and resistance shall be such to conform degree of shock protection and facilitate operation of protective systems within the set duration.
6.4.3 Earth-continuity Conductor
6.4.3.1 Earth-continuity conductors and earth wires not contained in the cables
The size of the earth-continuity conductors should correlate both in magnitude and duration adequate to accept ground fault current to suite over current protective system, without creating adverse thermal effect to result in to fire hazard. For phase conductor of size up to 16 mm2, minimum size of earth-continuity conductors shall equal to that of phase conductor (same metal), for above 16mm2 and up to 35 mm2, shall be 16 mm2 and for above 35mm2size shall be calculated as per clause 17.2.2.1 of IS 3043. It shall be noted that rate of corrosion of steel in soil is six times as fast as copper. To prevent corrosion of steel zinc coating of minimum 150 microns shall be done.
6.4.3.2 Earth-continuity conductors and earth wires contained in the cables
For flexible cables, the size of the earth-continuity conductors should be equal to the size of the current-carrying conductors and for metal sheathed, when used as earth continuity conductor, every joint shall of capacity not less than current carrying capacity of metal sheath.
Conduits may be used as earth-continuity conductors provided they are permanently and securely connected to the earth system. However, where by nature of the process, metal conduits cannot be used as earth-continuity conductor on account of corrosion, etc, the tough rubber or PVC sheathed cables may be used in which case they shall incorporate an earth-continuity conductor. Flexible conduits shall not be used as earth-continuity conductors. A separate earth wire shall be provided either inside or outside the flexible conduits which shall be connected by means of earth clips to the earth system at one end and to the equipment at the other end.
6.3Wiring System
The selection of a wiring system to be adopted in a factory shall depend upon the factors enumerated in Part 1/Sec 9 of the Code. The wiring system available for general use are listed in Annex C. Selection from a group of alternative systems shall be made in accordance with Annex C, keeping in view the points mentioned under 6.3.1.
6.3.1 Design and selection of wiring system and material shall be done considering:
a) Situation, such as location, structure, etc.;
b) External influences, such as climatic conditions, environment, etc.;
c) Hazard classification;
d) Scope for modifications, future expansions. For example, overhead busbar trunking with tap-offs facilitates modification in machine shops;
e) Compatibility to face emergency situation; and
f) Type and class of operators, users, occupants.
6.3.2 Electrical installation for lifts, hoists shall be done in consultation with the manufacturer and circuit supplying lift equipment shall distinct and separate.
7Emergency/standby Power Supplies
The provisions of Part 2 of the Code shall apply.
NOTE — Average factory installations are set apart from heavy industries in that the former has no conditions requiring specialized or exceptional treatment.
¹⁾ Terminology based on IS 732. Where different degrees of hazard occupancy exist in different parts of building, the most hazardous of those shall govern the classification for the purpose.
Table 2Load Groups in Industrial Buildings (Clause 4.2)
Sl No.
Groups
Type to Load
Examples
Corrected Power Factor
(1)
(2)
(3)
(4)
(5)
i)
1
Small and large loads fairly evenly distributed over the whole area and loaded constantly during the working day (precision mechanical engineering)
Loads evenly distributed over the whole area, but varying loads and with peak load at different times (for example, metal working industry)
Tool making
do
Press shop
do
Machine shop
do
Welding shop
do
iii)
3
Loads having very high power requirement in conjunction with smaller loads of negligible size compared to the total load (for example, raw material, industry)
Heat treatment shop, steel works, rolling mills
do
6.4.4 Earth Leakage Protection
Use residual current operating devices (RCDs) shall be made to prevent earth leakages exceeding limiting values set for direct and indirect contacts.
RCDs having sensitivity 30mA or less gives protection against direct contact and those above 30 mA are intended to give protection against indirect contact. RCDs 300 mA are recommended for risk against fire arising due to leakage currents.
Some degree of discrimination may, in certain cases, be introduced with advantage by providing the delay in the operation of an earth-leakage trip, so that earth faults on smaller subsidiary circuits protected by fuses have time to clear and prevent the opening of the circuit-breaker, controlling a larger part of the installation.
6.4.5 Earthing of Portable Appliances and Tools
Good electrical continuity between the body of a portable appliance and the earth-continuity conductor shall always be maintained.
It shall be ascertained that the fixed wiring at the appliance inlet terminals has been done correctly and in accordance with relevant Indian Standard.
A single pole switch shall not be connected in the earth conductor.
No twisted or taped joints shall be used in earth wires.
Additional security may be obtained by arranging the earth-continuity conductor in the flexible cable between the socket outlet and the portable appliance in the form of a loop through which a light circulating current provided by a small low-voltage transformer is passed when the appliance is in use. Any discontinuity in this loop will interrupt the circulating current and can thus be caused to operate a relay and disconnect the supply from the portable appliance.
6.4.6 Earthing of Electrically Driven Machine Tools
In all types of machine tools, the body of all motors and bed plate of the machine shall be earthed at two places by means of a strip or conductors of adequate cross-sectional area. The strip or conductor shall be securely fastened to the bed plate by means of bolts.
6.4.7 Earthing of Equipment
All components of electric arc welding equipment shall be effectively bonded and connected to earth. The transformers and separate regulators forming multi-operator sets and capacitors for power factor correction, if used, shall be included in the bonding.
All terminals on the output side of a motor generator set shall be insulated from the car case and control panel, as the generator is not connected electrically to a motor and therefore the welding circuit is electrically separate from the supply circuit including the earth.
In case of transformer sets, which for welding purpose are double wound, an ‘earth and work’ terminal shall be provided. In single phase sets this terminal shall be connected to one end of the secondary winding and in case of three-phase sets this shall be connected to the neutral point of the secondary winding.
6.4.8 Earthing of Industrial Electronic Apparatus
The earthing of these apparatus shall follow normal practice, but attention shall be paid to the points discussed below.
For any industrial electronic apparatus, which incorporates small capacitors connected between the supply and the metal case of the instrument to cut down interference, capacitor shall be securely earthed.
When an oscilloscope is being used to examine the wave-form of a high frequency source, the oscilloscope shall be earthed by a conductor entirely separate from that used by the source of high frequency power. However, when an oscilloscope is being used on a circuit where the negative is above earth potential and also connected to its metallic case, the earthing of the oscilloscope is not possible. Precautions shall be taken that in such a case the oscilloscope is suitably protected from other apparatus.
High frequency induction heating apparatus shall be earthed by means of separate earth wire by as direct a route as possible.
Dielectric loss heating equipment work at frequencies between 10 MHz to 60 MHz according to its use. These should not be directly earthed. At 30 MHz, for example, a quarter wavelength is nearly 250 cm and an earth wire of this length or odd multiples of it is capable of being at earth potential at one end but several hundred volts at the other end. This is due to the presence of standing waves on the earth conductors which besides being dangerous
can result in energy being radiated to the detriment of communication services. In such a case it is recommended to mount the equipment on a large sheet of copper or copper gauze, the earth conductor being connected to it at several points.
In case where direct earthing may prove harmful rather than provide safety, for example, high frequency and mains frequency coreless induction furnaces, special precautions are necessary. The metal of the furnace charge is earthed by electrodes connected at the bottom of the charge, and the furnace coils are connected to the mains supply but are unearthed. A relay is connected by a detection circuit which itself is earthed to the coils. The object is to prevent dangerous break-through of hot metal through the furnace lining, the earth detection circuit giving a continuous review of the conditions for the furnace lining. When leakage current attains a certain set maximum it becomes necessary to take the furnace out of service and to re-line.