Plugs and sockets normally used for the connection of household equipment to low voltage a.c. power supply shall not be used in PV arrays.
Plugs and socket connectors mated together in a PV system shall be of the same type from the same manufacturer (NOT equivalent type from another manufacturer). In other words, a plug from one manufacturer and a socket from another manufacturer or vice versa shall not be used to make a connection.
It is recommended to use appropriate MC4 plug and socket connectors for PV module terminations, string interconnections and string terminations onto SCBs and/or string inverters. Connectors safety requirements and tests shall be compliant with IS 16781 and corresponding connection shall be done in compliance with IS 16221 (Part 2). It is recommended to use MC4 equivalent connectors which connects both plug and socket of the same type from the same manufacturer. Extra precaution is required in matching type and manufacturer of terminations for PV modules, PV strings, SCBs and inverters.
Plugs, sockets and connectors shall comply with following requirements:
a) Comply with IS 16221 (Part 2);
b) Voltage rating equal to or greater than the PV array maximum voltage determined 5.8.1;
c) Shrouded/protected from contact with live parts in connected and disconnected state
d) Rated current according to 11.4;
e) Capable of accepting the cable used for the circuit to which they are fitted (typ. 2.5, 4 and 6 mm2 Cu);
f) Shall be of the latching/locking type where two independent actions and deliberate force are required to disconnect (use of tool is recommended for disengagement);
g) Rating suitable for installation location;
h) If multi-polar, be polarized and non-interchangeable with receptacles in other electrical systems installed at the location;
j) Comply with Class II for systems operating above DVC-A voltages (50 Vd.c.);
k) UV-resistant and min. IP65 rated form outdoor use;
m) Shall be installed with min. strain on the connectors (for example, supporting the cable on either side of the connector);
727
n) The protective earth connection shall be the first to make and the last to break contact with the mating connector;
p) Busbar terminations internal to inverters shall comply with IS 16221 (Part 2) for safety requirements.