4.3.1 Disconnection time for earth fault: The maximum allowed disconnection time (t in seconds) during fault derived from IS 3043 are given in Table 1 below. Figure 7 also can be referred.
| Table 1 Maximum Allowed Disconnection Times(Clause 4.3.1) | |||||||
| Sl No. | Prospective Touch Voltage Uc (V) | Condition 1 (DRY) | Condition 2 (WET) | ||||
| Z₁ (Ω) | I(mA) | t(s) | Z₂ (Ω) | I(mA) | t(s) | ||
| (1) | (2) | (3) | (4) | (5) | (6) | (7) | (8) |
| i) | 50 | 1725 | 29 | 5.000 | 925 | 54 | 0.470 |
| ii) | 110 | 1535 | 72 | 0.360 | 730 | 151 | 0.180 |
| iii) | 220 | 1375 | 160 | 0.170 | 575 | 383 | 0.035 |
| NOTES | |||||||
| 1 Dry or moist locations, dry skin and significant floor resistance. | |||||||
| 2 Wet locations, wet skin and low floor resistance. | |||||||