Earth and earthing system shall conform IS 3043 and Part 1/Sec 18 of this code. Schematic drawing of earthing system shall be prepared and updated version be maintained.
6.4.1 In factories and workshops all metal conduits, trunking, cable sheaths, switchgear, distribution boards, starters, motors and all exposed conductive parts and extraneous conductive parts shall be bonded together and connected to earth system efficiently.
6.4.2 Earth Electrodes
Selection, number and location(s) of Earth electrode(s) shall be as per soil resistivity, design requirement in respect of limiting value of earth fault loop impedance. In case of multiple earth electrodes grid may be formed. System shall be so designed that testing of individual earth electrode is possible and resistance shall be such to conform degree of shock protection and facilitate operation of protective systems within the set duration.
6.4.3 Earth-continuity Conductor
6.4.3.1 Earth-continuity conductors and earth wires not contained in the cables
The size of the earth-continuity conductors should correlate both in magnitude and duration adequate to accept ground fault current to suite over current protective system, without creating adverse thermal effect to result in to fire hazard. For phase conductor of size up to 16 mm2, minimum size of earth-continuity conductors shall equal to that of phase conductor (same metal), for above 16mm2 and up to 35 mm2, shall be 16 mm2 and for above 35mm2size shall be calculated as per clause 17.2.2.1 of IS 3043. It shall be noted that rate of corrosion of steel in soil is six times as fast as copper. To prevent corrosion of steel zinc coating of minimum 150 microns shall be done.
6.4.3.2 Earth-continuity conductors and earth wires contained in the cables
For flexible cables, the size of the earth-continuity conductors should be equal to the size of the current-carrying conductors and for metal sheathed, when used as earth continuity conductor, every joint shall of capacity not less than current carrying capacity of metal sheath.
Conduits may be used as earth-continuity conductors provided they are permanently and securely connected to the earth system. However, where by nature of the process, metal conduits cannot be used as earth-continuity conductor on account of corrosion, etc, the tough rubber or PVC sheathed cables may be used in which case they shall incorporate an earth-continuity conductor. Flexible conduits shall not be used as earth-continuity conductors. A separate earth wire shall be provided either inside or outside the flexible conduits which shall be connected by means of earth clips to the earth system at one end and to the equipment at the other end.
6.4.4 Earth Leakage Protection
Use residual current operating devices (RCDs) shall be made to prevent earth leakages exceeding limiting values set for direct and indirect contacts.
RCDs having sensitivity 30mA or less gives protection against direct contact and those above 30 mA are intended to give protection against indirect contact. RCDs 300 mA are recommended for risk against fire arising due to leakage currents.
Some degree of discrimination may, in certain cases, be introduced with advantage by providing the delay in the operation of an earth-leakage trip, so that earth faults on smaller subsidiary circuits protected by fuses have time to clear and prevent the opening of the circuit-breaker, controlling a larger part of the installation.
Good electrical continuity between the body of a portable appliance and the earth-continuity conductor shall always be maintained.
It shall be ascertained that the fixed wiring at the appliance inlet terminals has been done correctly and in accordance with relevant Indian Standard.
A single pole switch shall not be connected in the earth conductor.
No twisted or taped joints shall be used in earth wires.
Additional security may be obtained by arranging the earth-continuity conductor in the flexible cable between the socket outlet and the portable appliance in the form of a loop through which a light circulating current provided by a small low-voltage transformer is passed when the appliance is in use. Any discontinuity in this loop will interrupt the circulating current and can thus be caused to operate a relay and disconnect the supply from the portable appliance.
In all types of machine tools, the body of all motors and bed plate of the machine shall be earthed at two places by means of a strip or conductors of adequate cross-sectional area. The strip or conductor shall be securely fastened to the bed plate by means of bolts.
6.4.7 Earthing of Equipment
All components of electric arc welding equipment shall be effectively bonded and connected to earth. The transformers and separate regulators forming multi-operator sets and capacitors for power factor correction, if used, shall be included in the bonding.
All terminals on the output side of a motor generator set shall be insulated from the car case and control panel, as the generator is not connected electrically to a motor and therefore the welding circuit is electrically separate from the supply circuit including the earth.
In case of transformer sets, which for welding purpose are double wound, an ‘earth and work’ terminal shall be provided. In single phase sets this terminal shall be connected to one end of the secondary winding and in case of three-phase sets this shall be connected to the neutral point of the secondary winding.
6.4.8 Earthing of Industrial Electronic Apparatus
The earthing of these apparatus shall follow normal practice, but attention shall be paid to the points discussed below.
For any industrial electronic apparatus, which incorporates small capacitors connected between the supply and the metal case of the instrument to cut down interference, capacitor shall be securely earthed.
When an oscilloscope is being used to examine the wave-form of a high frequency source, the oscilloscope shall be earthed by a conductor entirely separate from that used by the source of high frequency power. However, when an oscilloscope is being used on a circuit where the negative is above earth potential and also connected to its metallic case, the earthing of the oscilloscope is not possible. Precautions shall be taken that in such a case the oscilloscope is suitably protected from other apparatus.
High frequency induction heating apparatus shall be earthed by means of separate earth wire by as direct a route as possible.
Dielectric loss heating equipment work at frequencies between 10 MHz to 60 MHz according to its use. These should not be directly earthed. At 30 MHz, for example, a quarter wavelength is nearly 250 cm and an earth wire of this length or odd multiples of it is capable of being at earth potential at one end but several hundred volts at the other end. This is due to the presence of standing waves on the earth conductors which besides being dangerous
can result in energy being radiated to the detriment of communication services. In such a case it is recommended to mount the equipment on a large sheet of copper or copper gauze, the earth conductor being connected to it at several points.
In case where direct earthing may prove harmful rather than provide safety, for example, high frequency and mains frequency coreless induction furnaces, special precautions are necessary. The metal of the furnace charge is earthed by electrodes connected at the bottom of the charge, and the furnace coils are connected to the mains supply but are unearthed. A relay is connected by a detection circuit which itself is earthed to the coils. The object is to prevent dangerous break-through of hot metal through the furnace lining, the earth detection circuit giving a continuous review of the conditions for the furnace lining. When leakage current attains a certain set maximum it becomes necessary to take the furnace out of service and to re-line.