Part 4Electrical Installations in Industrial Buildings
Electrical installation in industrial buildings requires special attention in design with a basic consideration for ‘safety at work-places’, quality and continuity of supply, energy conservation.
The layout of electrical installation should facilitate maintenance with ease and free access. Distribution shall be designed so that fault localization is possible targeting lowest down time.
Keeping in view the tariff structures depending on Time of Day (ToD), as also an economic necessity; conserving power, maintaining power factor nearest to unity, limiting harmonic effects shall be considered as important aspects.
For reliability and continuity of supply for essential/continuous operations, standby and emergency supply sources/networks shall be designed.
Locations in industrial buildings which are by their nature hazardous, require special treatment in respect of design of electrical installations therein. Such special rules for hazardous areas are covered in Part 7 of the Code and these shall be complied with in addition to the general rules specified in that Part.
In 4 of this Part, an attempt has been made to classify industrial installations depending on the specified criteria therein. Such a classification, it is hoped would help identify the specific nature of each industry and the locations therein, assisting the design engineer in the choice of equipment and methods of installation.
1Scope
1.1 This Part of the Code (Part 4) covers the guidelines for design and construction of electrical installations in industrial buildings.
1.2 This Part does not cover specific areas in industrial sites, such as office buildings, workers rest rooms, medical facilities, canteen annexe, etc, for which requirements stipulated in the relevant sections of Part 3 of the Code apply.
1.3 This Part also does not cover locations in industrial sites that are by nature hazardous for which the provisions of Part 7 of the Code apply.
4Classification of Industrial Buildings
Industry by definition includes manufacturing, processing, service sectors under which IT sector is also considered as Industry. However, for the purpose of this section industry basically include any building or part of building or structure, in which products or materials of all kinds and properties are stored, fabricated, assembled, manufactured or processes. For example, assembly plants, laboratories, dry cleaning plants, pumping stations, refineries, dairies, saw mills, chemical plants, workshops, distilleries, steel plants, etc.
Industrial installations are of various types. Single industrial site may comprise electrical loads of varying types and requirements. Classification of Industries is based on three criteria as given in 4.1 to 4.3.
4.1 Classification Based on Fire Safety
4.1.1 Industrial buildings are classified into Group G from the fire safety point of view in SP 7. Buildings under Group G are further subdivided as follows:
a) Subdivision G-1 — Buildings used for low hazard industries — Includes any building in which the contents are of such low combustibility and the industrial processes or operations conducted therein are of such a nature that there are no possibilities for any self-propagating fire to occur and the only consequent danger to life and property may arise from panic, fumes or smoke, or fire from some external source.
b) Subdivision G-2 — Buildings used for moderate hazard industries — Includes any building in which the contents or industrial processes of operations conducted therein are liable to give rise to a fire which will burn with moderate rapidity and give off a considerable volume of smoke but from which neither toxic fumes nor explosions are to be feared in the event of fire.
c) Subdivision G-3 — Buildings used for high hazard industries — Includes any building in which the contents or industrial processes or operations conducted therein are liable to give rise to a fire which will burn with extreme rapidity or from which poisonous fumes or explosions are to be feared in the event of fire.
NOTE — SP 7 includes Group J buildings for such location where storage, handling, manufacture or processing of highly combustible or explosive materials or products are being carried out. Such installations including such high hazard locations in Group G classification shall comply with the special rules of Part 7 of the Code.
SP 30 : 2023
4.1.2 Typical list of industries for different class of fire hazard are given in Annex B.
4.2 Classification Based on Power Consumption
Industrial buildings may also be classified depending on the quantum of electric power requirements for its services as given in Table 1.
Loads within the industrial site could be divided depending on their nature and size. For guidance, the classification given in Table 2 shall be referred to.
4.3 Classification Based on Pollution
For the propose of evaluating creepage distances and clearances, the following four degrees of pollution in the micro-environment are established:
a) Pollution degree 1 — No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
b) Pollution degree 2 — only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation is to be expected.
c) Pollution degree 3 — Conductive pollution occurs, or dry non-conductive pollution occurs which becomes conductive due to condensation — which is to be expected.
d) Pollution degree 4 — Continuous conductivity occurs due to conductive dust, rain or other wet conditions.
1 Clearances and creepage distances according to the different pollution degrees are given in Tables 13 and 15 of IS/IEC 60947-1. Unless otherwise stated by the relevant product standard, equipment for industrial applications is generally for use in pollution degree 3 environment. However, other pollution degrees may be considered to apply depending upon applications or the micro-environment.
a) The pollution degree of the micro-environment for the equipment may be influenced by installation in an enclosure. Means may be provided to reduce pollution at the insulation under consideration by effective use of enclosures, encapsulation or hermetic sealing. Such means to reduce pollution may not be effective when the equipment is subject to condensation or if, in normal operation, it generates pollutants itself.
b) Pollution will become conductive in the presence of humidity. Pollution caused by contaminated water, soot, metal or carbon dust is inherently conductive. Small clearances can be bridged completely by solid particles, dust and water and therefore minimum clearances are specified where pollution may be present in the micro-environment.
Table 1 Classification Based on Power Consumption
(Clause 4.2)
Sl No.
Description¹⁾
Average Power Requirement
Examples
(1)
(2)
(3)
(4)
i)
Light industries
Up to 50 kVA
Hosiery, tailoring and jewellery
ii)
Average industries
Above 50 kVA up to 2 000 kVA
Machinery, engine fitting, motor cars, aircraft, light pressings, furniture, pottery, glass, tobacco, electrical manufacturing and textile (see Note)
iii)
Heavy industries
Above 2 000 kVA
Heavy electrical equipment, rolling mills, structural steel works, tube making, foundries, locomotives, ship-building and repairing, chemical factories, factories for metal extraction from ores, etc.
5General Characteristics of Industrial Buildings
General guidelines on the assessment of characteristics of installations in buildings are given in (Part 1/Sec 8) of the Code. For the purposes of installations falling under the scope of this Part 4, the characteristics given below shall apply.
5.1 Environment
The following environmental factors shall apply to industrial installations:
Environment
Characteristics
Remarks
(1)
(2)
(3)
Presence of water
Presence of water negligible, or possibilities of free falling drops or sprays, moisture
Depends on the location. For further details see (Part 1/Sec 8) of the Code
Presence of foreign solid bodies
These conditions include possibilities of presence of foreign solid bodies of various sizes likely to affect electrical equipment
Depends on the location. For further details see (Part 1/Sec 8) of the Code
Presence of corrosive polluting substances
Atmospheric where the presence of corrosive or polluting substances is significant
Industrial installations, situated by the sea, chemical works, cement works where the pollution arises due to abrasive, insulating or conducting
Intermittent or accidental subjection to corrosive or polluting chemical substances being used or produced
Dust factory laboratories boiler rooms, etc.
Continuous pollution
Chemical works
Mechanical stresses
Impact and vibration of low severity impact/ vibration of high severity
Household and similar conditions industrial installations subject to severe conditions
Seismic effect and lightning
-
Depends on the location of the buildings
(1)
(2)
(3)
Contact of persons with earth potential
Persons are frequently in touch with extraneous conductive parts or stand on conducting surfaces Persons are in permanent contact with metallic surroundings and for whom the possibility of interrupting contact is limited
Locations with extraneous conducting parts, either numerous or large area metallic surrounding, such as boilers and tanks
Conditions of evacuation
Low density occupation, easy conditions of evacuation
This category applies to buildings of normal or low height
Nature of processed or stored material
Existence of fire-risks, where there is manufacturing, processing or storage of flammable materials, including presence of dust/smoke
Wood-working shop, paper factories, textile mills, etc
Processing or storage of low-flash-point materials including presence of explosive dust
Oil refineries, hydrocarbon stores
5.2 Compatibility
In industrial installations, an assessment shall also be made of any characteristics of equipment likely to have harmful effects upon other equipment or other services (see Part 1/Sec 8 of the Code).
5.3 Maintainability
Assessment shall also be made of the frequency and quality of maintenance of the installation (see Part 1/Sec 8 of the Code).
NOTE — Average factory installations are set apart from heavy industries in that the former has no conditions requiring specialized or exceptional treatment.
¹⁾ Terminology based on IS 732. Where different degrees of hazard occupancy exist in different parts of building, the most hazardous of those shall govern the classification for the purpose.
Table 2Load Groups in Industrial Buildings (Clause 4.2)
Sl No.
Groups
Type to Load
Examples
Corrected Power Factor
(1)
(2)
(3)
(4)
(5)
i)
1
Small and large loads fairly evenly distributed over the whole area and loaded constantly during the working day (precision mechanical engineering)
Loads evenly distributed over the whole area, but varying loads and with peak load at different times (for example, metal working industry)
Tool making
do
Press shop
do
Machine shop
do
Welding shop
do
iii)
3
Loads having very high power requirement in conjunction with smaller loads of negligible size compared to the total load (for example, raw material, industry)