Hazardous areas are classified in zones based upon the frequency of the appearance and the duration of an explosive gas atmosphere as follows:
6.1.4 Classification of Hazardous Area
To determine the type of electrical installation appropriate to a particular situation, the hazardous area have been divided into three zones, namely, Zone 0, Zone 1 and Zone 2, according to the degree of probability of the presence of hazardous atmosphere.
Typical examples of such classifications are given below:
6.1.4.1 Zone 0 areas
Examples are vapour space above closed process vessels, storage tanks or closed containers, areas containing open tanks of volatile, flammable liquid.
6.1.4.2 Zone 1 areas
Zone 1 locations may be distinguished when any of the following conditions exits:
a) Flammable gas or vapour concentration is likely to exist in the air under normal operating conditions;
b) Flammable atmospheric concentrations is likely to occur frequently because of maintance, repairs or leakage;
c) Failure of process, storage or other equipment is likely to cause an electrical system failure simultaneously with the release of flammable gas or liquid;
d) Flammable liquid or vapour piping system (containing valves, meters or screwed or flanged fittings) is in an inadequately ventilated area; and
e) The area below with surrounding elevation or grade is such that flammable liquids or vapours may accumulate therein.
This classification typically includes:
a) Imperfectly fitting peripheral seals on floating roof tanks;
b) Inadequately ventilated pump rooms for flammable gas or for volatile, flammable liquids;
697
c) Interiors of refrigerators and freezers in which volatile flammable materials are stored in lightly stoppered or easily raptured containers;
d) API separators;
e) Oily waste water sewer/basins;
f) LPG cylinder filling and cylinder evacuation area: and
g) Areas in the immediate vicinity of vents and filling hatches.
6.1.4.3 Zone 2 areas
Zone 2 locations may be distinguished when any one of the following conditions exist:
a) The system handling flammable liquid or vapour is in an adequately ventilated area and is so designed and operated that the explosive or ignitable liquids, vapours or gases will normally be confined within closed containers or closed systems from which they can escape only during abnormal conditions, such as accidental failure of a gasket or packing;
b) The flammable vapours can be conducted to the location as through trenches, pipes or ducts;
c) Locations adjacent to zone 1 area; and
d) In case of use of positive mechanical ventilation, as the failure or abnormal operation of ventilating equipment can permit atmospheric vapour mixtures to build up to flammable concentrations.
6.1.4.4 Areas not classified
In general the following locations are considered safe from the point of view of electrical installations:
a) Areas where the piping system is without valves, fittings, flanges or similar appurtenances;
b) Areas where flammable liquids or vapours are transported only in suitable containers or vessels;
c) Areas where permanent ignition sources are present like area where combustion gases are present, for example flare tips, flare pits, other open flames and hot surfaces;
d) Enclosed premises in which a plenum or purging stream of safe atmosphere is continuously maintained, so that no opening there in may be a point of ingress of gases or vapours coming from an external source of hazard;
e) Gas turbine installation meeting requirements of IS 16724;
f) Rooms/sheds for housing internal combustion engine, having adequate ventilation; and
g) Oil/gas fired boilers installations. Consideration should be given, however, to potential leak sources in pumps, valves, etc. or in waste product and fuel lines feeding flame or heat producing equipment to avoid instillation electrical devices which could then become primary ignition sources for such leaks.
1 A protected fired vessels is not considered a source of ignition and the surrounding area is classified the same as for a hydrocarbon pressure vessel.
2 The area around the fired components and exhaust outlets of unprotected fired vessels need not be classified from the standpoint of installation of electrical equipment.
3 The area around a flare tip or flare pit need not be classified from the stand point of installation of electrical equipment. However, the area classification for the associated equipment (for example, knock out drum blow down pump etc.) located a grade level shall be followed as applicable.
4 Lack of classification around unprotected fired vessels and flare tips does not imply the safe placement of fired vessels and flare tips in the proximity to others production equipment because these are themselves sources of ignition.
5 Electrical equipment may be exposed to flammable gas during a purge cycle of a fired heater or furnace.