Generating set consists of a prime mover, RIC (Reciprocating Internal Combustion) engine which produces mechanical energy which is converted to electrical energy by generator coupled to engine, control gear and switchgear and auxiliaries.
4.1 Prime Mover
Prime mover characteristics are considered by its fuel, fuel consumption, exhaust, noise, speed, mass, dimensions, surge capacity, maintenance requirements etc.
4.2 Generator
Generator characteristics are considered by output voltage behaviour during normal steady operation and fluctuating/variable load, power factor, short circuit behaviour, efficiency, parallel operation behaviour, maintenance, etc.
4.3 Controlling, Switching
Controlling, switching, operation, monitoring and protecting the set under condition of fault are main characteristics of control gear and switchgear.
4.4 Auxiliaries
Characteristics of auxiliaries are to provide essential service for smooth, proper and safe functioning. It comprises starting system, air intake and exhaust system, cooling system, lubricating system, fuel system, auxiliary electrical power supply, etc.
4.5 Start-up Time/Changeover Time
There may be certain time lag in changeover from one power source to another. This elapse of time is important consideration especially for safety services which may require certain provisions to be made in system. The automatic supply changeover classified as given in the Table 1.
Table 1 Classification of Automatic Supply System in Accordance with Maximum Changeover Time (Refer IEC 60364-5-56)
(Clause 4.5)
| Class | Changeover time in Seconds | Remarks |
|---|---|---|
| A | Nil | No-break |
| B | Within 0.15 s | Very short break |
| C | Within 0.5 s | Short break |
| D | Within 5 s | Average break |
| E | Within 15 s | Medium break |
| F | More than 15 s | Long break |
4.6 Performance Classes
Gen-set are classified in to 4 types; G1, G2, G3 and G4; depending on performance with respect to voltage and frequency. G1 type is considered suitable for general purpose lighting load, G2 suitable to operate with public utility electric power system, G3 where equipment requires precise level of stability in respect of voltage, frequency and waveform, for example telecommunication and thyristor-controlled loads and G4 where precision is required at exceptionally high level, for load like data centres, computer systems.