a) Affect operation of sensitive equipment like control and monitoring devices;
b) Distortion of telephone signals;
c) Harmonics cause additional losses (Joule effect) in conductors and equipment;
d) Derating of power sources (generators, transformers and UPSs) leading to over-sizing;
e) Oversizing of conductors on account of the flow of harmonic currents due to skin effect;
f) Reduced service life of equipment; and
g) Nuisance tripping of breakers and installation shutdown.
There are multiple ways to reduce the effect of harmonics by using separate source for non-linear loads, use of reactors, use of transformers with special connections and active harmonic filters (AHF). Among these, active harmonic filter offers a flexible, scalable solution for harmonic mitigation. AHF sense the current by means of CTs mounted on the mains/load. It calculates the harmonic current requirement of the load and produce a harmonic current which will be in phase opposition. This way it will reduce the harmonic current drawn from the utility.