While installing conditions mentioned under 6.3.1 to 6.3.5 below shall be considered.
6.3.1 Indoor/Outdoor/Rooftop
At planning stage, it is necessary to decide location so that necessary arrangements can be done related to Architectural, Structural, Civil Work requirements. Future additions, augmentation shall also be considered. Required clearances around and in between gen-sets shall be as per OEM’s recommendations so that operation and serviceability of generating set shall be easy. If installation is within room, door sizes shall be of adequate size considering size of removable/replaceable parts. Necessary provisions in respect with cables, Fuel lines, breather vent, coolant/lube-oil drain, coolant, storage of consumables, spares shall be considered.
NOTES:
1 Where Gen set is meant to provide supply to critical services for which supply integrity is important, location shall be so chosen that in case of emergency like fire, functioning of the Gen-set will not get affected. This location may be at safe place away from building.
2 In case of roof top Gen-sets, OEM shall be informed in advance and the recommended pre-installation check list shall be followed.
6.3.2 Foundation
For foundation design requirements of OEM shall be followed. Generally, M20 grade CC foundation is suitable to sustain static and dynamic load, however design and depth of foundation may vary depending on safe bearing capacity of soil. Anti-Vibration mounting (AVM) pads shall be used to compensate dynamic loading if required. Length and breadth shall be 150 to 300 mm more than the base rail/outer dimensions of acoustic canopy. Height from ground level shall not be less than 150 mm. Required curing time shall be allowed for foundation to set. Surface shall be flat to the accuracy of + 0.5 percent.
NOTE — Improper foundation may lead to alignment and vibration problems resulting into premature failure of Gen-set components and service life.
6.3.3 Orientation
393
Orientation of generating set shall be such that natural wind flow shall not be obstructed. Ideally direction of wind shall be such that it shall enter from alternator end and exit from radiator end. In case it is not possible to maintain, barriers may be provided in consultation with OEM. It shall be seen that hot air is not re-circulated.
6.3.4 Ventilation
To maintain parameters related to permissible temperature rise within limit, adequate cross ventilation is important. Orientation as mentioned under 6.3.3, will help achieve the requirement in respect of ventilation. If OEM recommends additional forced measures, same shall be provided. Generally maximum allowable temperature rise within room/enclosure shall not be more than 10°C above ambient up to 40°C and 5°C above ambient if it exceeds 40°C or as specified by OEM. Improper ventilation may affect fuel efficiency, performance, rubber components, exhaust, alternator winding. Under adverse conditions, it may be possible to consider de-rating of the set.
6.3.5 Fuel
6.3.5.1 Diesel
In case diesel engines, fuel tanks where they are not part of factory assembled unit, following points shall be considered:
a) Supply and return line allowable pressure, segregation, length;
NOTE — Higher pressure may lead to low power, late stopping, engine die down
b) Level of fuel tank above/below with respect to engine and fuel pump;
c) Minimum requirement of fuel by gravity if any, in respect of Gen-sets with AMF panels;
d) Arrangements shall be done for condensate drain, breather, fill neck to allow expansion;
e) Capacity; shall be to suffice requirement for continuous use for the assessed critical period but shall not exceed norms mentioned under petroleum rules; and
f) Galvanised tank, piping shall not be used for diesel.
Separate storage arrangement for fuel refilling may be done depending on need and nearby availability. Storage of fuel above 1 000 l requires approval from the authority. This arrangement should comply with applicable Petroleum Rules.
Notes:
1 Diesel consumption
Fuel efficiency is an important factor for considering running cost. It is measured at 50 percent, 75 percent and 100 percent loading. Specific fuel consumption is measured in gm/bhp/hour or l/hr. Specific gravity of Diesel is 0.845 as per ISO 3046. It is always desirable to have optimal fuel consumption over broad range of loading. All manufacturers provide fuel consumption charts. It shall be noted that actual consumption may vary depending on ventilation, observance of maintenance schedule, percentage loading, and occasional overloading.
2 Diesel shall comply specifications as per IS 1460.
3 In case of Fuel Tank of Gen-sets on roof top, Specific Rules mandatory as per Local Fire Authority and Petroleum Rules shall be followed in respect of placement and capacity.
6.3.5.2 Gas
Depending on availability of natural gas it can be a good option considering environmental aspects. OEM recommendations shall be referred in respect of installation of various components such as shut-off valves, regulators, carburettor, filter etc; of fuel supply system.
NOTE — Before commissioning pre-installation check from the manufacturer shall be done in which specific requirements in respect of Gas fuel shall be to the satisfaction.