8.1 General
Protection measures may be adopted in order to reduce the risk according to the type of damage.
8.2 Protection Measures to Reduce Injury of Living Beings by Electric Shock
Possible protection measures include:
a) adequate insulation of exposed conductive parts;
b) equi-potentialization by means of a meshed earthing system;
c) physical restrictions and warning notices; and
d) lightning equipotential bonding (EB).
8.3 Protection Measures to Reduce Physical Damage
Protection is achieved by the lightning protection system (LPS) which includes the following features:
a) air-termination system;
b) down-conductor system;
c) earth-termination system;
d) lightning equipotential bonding (EB); and
e) electrical insulation (and hence separation distance) against the external LPS.
8.4 Protection Measures to Reduce Failure of Electrical and Electronic Systems
The electrical and electronic system protection measures (SPM) include:
a) Earthing and bonding measures;
b) Magnetic shielding;
c) Line routing;
d) Isolating interfaces; and
e) Coordinated SPD system.
These measures may be used alone or in combination.
8.5 Protection Measures Selection
The protection measures listed above together form the overall lightning protection.
Selection of the most suitable protection measures shall be made by the designer of the protection measures and the owner of the structure to be protected according to the type and the amount of each kind of damage, the technical and economic aspects of the different protection measures and the results of risk assessment.