Efforts should be made to select electrical installations and systems which are energy efficient, while complying with the Indian Standards for the same which provide apart from efficiency, the various other important requirements including relating to performance and safety.
The requirements for energy efficient design of electrical installations in buildings are classified under the following four categories:
a) Minimizing losses in the power distribution system,
b) Reduction of losses and energy wastage in the utilization of electrical power,
c) Reduction of losses due to the associated power quality problems,
d) Appropriate metering and energy monitoring facilities, and
e) Reduction in losses due to usage of inefficient/ old motor, replacing motors with IE2/IE3 motors as per accepted standard [11(34)].
The active energy efficiency measures include making use of energy saving equipment, low energy lighting, efficient motors, low loss transformers, efficient appliances, suitable power carrying devices and optimized electrical distribution. These active measures along with high efficiency standby emergency generating plants using diesel, natural gas, alternate fuel, etc coupled with high efficiency uninterruptible power supply (UPS) systems contribute towards sustainable development.
Passive features include good practices like simple switching off (to turn off a device when not in use), paying attention to vampire electric loads (associated with electronic appliances like computers), etc.
Some of the recommended design criteria that may be adopted are as follows:
-
The transformer selection may be done in accordance with minimum efficiency performance standard (MEPS).
-
Higher voltage distribution systems should be employed for high-rise buildings to suit the load centres at various locations.
-
The locations of distribution transformers and main LV switch boards should preferably be sited at their load centres.
70
-
To reduce energy losses in the conductors of cable and bus-bar trunking, their appropriate selection should be done based on voltage drop calculations.
-
Reduction of energy losses in the conductors of cables and bus-bar trunking may be kept in mind in the choice of conductor cross-section.
-
Use of bus ducts/rising mains (stacked configuration) in place of multiple runs of cables and use of dual-bus design with bus coupler is recommended for better fault current withstanding capacity, avoidance of fire hazard, and ensuring higher reliability with low energy loss in the main power distribution system.
-
The loss of every main circuit connecting the distribution transformer and the main incoming circuit breaker of a LV switchboard should be minimised.
-
The effective current-carrying capacity of neutral conductors should have ratings not less than those for the corresponding phase conductors.
-
The maximum loss in every feeder circuit/sub-main circuit should not exceed 1.5 percent of the total active power transmitted along the circuit conductors at rated circuit current.
-
The maximum loss for every single-phase or three-phase final circuit/sub-main circuit over 32A should not exceed 1.0 percent of the total active power transmitted along the circuit conductors at rated circuit current.
-
Any motor control centre (MCC) or motor for air conditioning installations, having an output power of 5 kW or greater, with or without variable speed drives, should also be equipped, if necessary, with appropriate power factor correction or harmonic filtering devices to improve the power factor to a minimum of 0.85 at motor and restrict the total harmonic distortion (THD). This may be achieved through use of capacitor banks.
-
All electrically driven equipment and motors forming part of a vertical transportation system should preferably comply with the energy efficiency requirements for lift and escalator installations.
-
Every motor having an output power of 5 kW or greater may be sized by not more than 125 percent of the anticipated maximum system load unless the load characteristic requires especially high starting torque or frequent starting.
-
A variable speed drive (VSD) shall be
employed for motor in a variable flow application.
-
Motor users should insist on appropriate rewinding practices for any rewound motors.
-
Fix type capacitor should be used in capacitor bank to compensate inductive load of transformer.
-
The total power factor for any circuit should not be less than 0.85.
-
The power factor correction device should preferably be installed at the source motor control centre or distribution board just upstream of the circuit in question.
-
Office equipment and electrical appliances should have desired energy efficiency levels complying with relevant Indian Standards.
-
Consumers should be encouraged to select and purchase office machinery/equipment, for example personal computers, monitors, printers, photocopiers, facsimile machines, etc, complete with power management/energy saving feature.
-
Consumers should be encouraged to select energy efficient electrical appliances such as refrigerators, room coolers, washing machines, etc, complying with relevant Indian Standards.
-
Designers are encouraged to incorporate into their design all available latest demand side management (DSM) programmes in order to reduce the maximum demand and the electrical energy consumption in buildings.
-
All single-phase loads, especially those with non-linear characteristics, in an electrical installation with a three-phase supply should be evenly and reasonably distributed among the phases.
-
A system approach to measure and verify energy savings in the electrical distribution installations in buildings (especially high rise and commercial ones) should be adopted.
-
Wherever conventional fossil fuel based captive generation systems are deployed scoping for heat recovery systems, including tri-generation, may be explored.
-
To achieve peak demand avoidance programmable logic controller (PLC) controlled automatic electrical distribution systems should be opted for.
-
Consumers should be encouraged to use IE2/IE3 motors in line with accepted standard [11(34)] and replace old inefficient motors with the mentioned standard. They should be
encouraged to replace the motors rewound more than 4 times.
- Air handling units should use energy efficient motors.