7.1 The gas fitter shall put the gas off to any appliance, pipe or piping system and shall leave the gas turned off, until the causes for interrupting the supply has been removed in any one of the following cases:
a) If ordered to do so by the Authority.
b) If leakage of gas is noted, which appears to be sufficient to cause fire, explosion or asphyxiation.
c) If an installation of some gas appliance is found to be such as to cause a serious hazard to persons or property.
NATIONAL BUILDING CODE OF INDIA 2016
d) If any condition exists which threatens interruption of gas supply which may cause burner outage or otherwise prove dangerous.
7.2 It shall be the duty of the installing agency when the gas supply is to be turned off to notify all affected consumers.
7.3 Before turning off the gas at the meter, for the purpose of installation, repair, replacement or maintenance of piping or appliance, all burner and pilot valves on the premises supplied with gas through the meter shall be turned off and the meter test hand observed for a sufficient length of time to ascertain that there is no gas passing through the meter. Where there is more than one meter on the premises, precaution shall be exercised to ensure that the concerned meter is turned off.