10.1 It is necessary to have uniformity in the definition, measurement, processing and expression of vibration and noise signals that comprise escalator and moving walk ride quality. The aim of such uniformity is to benefit escalator and moving walk users by reducing variability in the results of ride quality measurements caused by differences in the methods of acquiring and quantifying the signals. Experience indicates that passenger perception and sound pressure levels measured while travelling on an escalator or moving walk can be influenced by the presence of extraneous noise and vibration sources and by acoustic characteristics of the environment in which the unit is installed and operated. Additionally, the proximity of the escalator or moving walk to strong reflecting surfaces such as walls, ceilings or diagonally opposite units can also influence the sound pressure level measured. These influences can cause a sound pressure level measurement to significantly overestimate the sound level emitted exclusively by the unit. In order to address this issue, this Subsection defines the methodology for measuring vibration and sound pressure level that corresponds to passenger perception and additionally defines the methods that should be used, if further understanding of the result is required in order to quantify vibration and noise emitted by the
unit as compared to the background or environmental contributions.
10.2 Measurement of Escalator and Moving Walk Ride Quality
Escalator and moving walk should be measured in both running directions except where the unit is designed to operate in one direction only. The measurements should be carried out under following conditions where, escalator and moving walk shall,
a) be assembled completely, adjusted and operating in accordance to the requirement;
b) have reached normal operating temperature;
c) be measured in unloaded condition;
d) be measured after starting sequence has been completed. If the unit operates at different speeds, all the speeds shall be measured;
e) have finished star/delta changeover, if used, before starting the measurement;
f) have vibration measurements made by aligning the axis of transducer to the axis of entire escalator or moving walk; and
g) have the noise measured at measuring distance to the floor/surface of steps and pallets of 1.55 ± 0.075 m.