6.1 No person, unless is the employ of the gas company or having permission from the gas company, shall turn on the gas at a service shut-off valve or at any valve that controls the supply of gas to more than one consumer.
6.2 Gas shall not be turned on at any meter valve without specific permission from the gas company or other authority if any of the following conditions exists:
a) If the gas piping appliances or meter supply through the meter valve are known to leak or otherwise to be defective (see 10).
b) If required inspection of the piping or appliance has not been made.
c) If the gas company or other authority has requested that the gas be left turned off.
d) If the meter valve is found shut-off for some reason not known to the gas fitter.
The gas shall not be turned on in the event of fire.
6.3 Gas shall not be turned on at any branch line valve if any of the conditions specified in 6.2 prevails. Where a branch line valve is found closed, a gas fitter shall again turn the gas on at such valve only if proper precautions to prevent leakage are taken and no other unsafe conditions are created thereby.
6.4 Gas shall not be turned on at either the meter valve or service line unless all gas keys or valves provided on all outlets in the piping system are closed or all outlets in the piping system are capped or plugged.