This Code (Part 8/Section 4) covers requirements and guidelines regarding planning against noise, acceptable noise levels and the requirements for sound insulation in buildings with different occupancies.
For the purpose of this Section, the definitions given below shall apply.
2.1 Ambient Noise — The sound pressure levels associated with a given environment. Ambient noise is usually a composite of sounds from near and far sources, none of which are particularly dominant.
2.2 Audible Frequency Range — The range of sound frequencies normally heard by the human ear. The audible range spans from 20 Hz to 20 000 Hz.
2.3 A-Weighted Sound Pressure, pA — Value of overall sound pressure, measured in pascal (Pa), after the electrical signal derived from a microphone has been passed through an A-weighting network.
NOTE — The A-weighting network modifies the electrical response of a sound level meter with frequency in approximately the same way as the sensitivity of the human hearing system.
2.4 A-Weighted Sound Pressure Level, LpA — The quantity of A-weighted sound pressure, in decibel (dB), as given by the following formula:
where
pA = A-weighted sound pressure, in pascals (Pa); and
p₀ = reference sound pressure (20µ Pa)
NOTE — Measurements of A-weighted sound pressure level can be made with a meter and correlate roughly with subjective assessments of loudness, and are usually made to assist in judging the effects of noise on people. The size of A-weighting in 1/3 octave bands, is shown in Annex A (see A-5). An increase or decrease in level of 10 dBA corresponds roughly to a doubling or halving of loudness.
2.5 Background Noise — The sound pressure levels in a given environment from all sources excluding a specific sound source being investigated or measured.
2.6 Break-In — Unwanted sound transmission into a duct or a quiet environment, from outside.
2.7 Break-Out — Unwanted sound transmission from the inside of a duct or a noisy enclosure, to the outside.
2.8 Broad Band Noise — Spectrum consisting of a large number of frequency components, none of which is individually dominant.
2.9 Cross-Talk — Unwanted sound transmission between one room and another room or space, via a duct.
2.10 Ctr — Correction term applied against the sound insulation single-number values ( Rw , Dw , and DnT,w ) to provide A-weighting against low frequency performance.
NOTE — The reference values used within the Ctr calculation are based on urban traffic noise.
2.11 Decibel — Ten times the logarithm (to the base 10) of the ratio of two mean square values of sound pressure, sound power or sound intensity. The abbreviation for decibel is dB.
2.12 Effective Perceived Noise Level, in Decibel (EPN dB) — The number for rating the noise of an individual aircraft flying overhead is the effective perceived noise level in decibel (EPN dB). The effective perceived noise decibel value takes into account the subjectively annoying effects of the noise including pure tones and duration. In principle, it is a kind of time-integrated loudness level.
2.13 Equivalent Continuous A-Weighted Sound Pressure Level, LAeq.T — Value of the A-weighted sound pressure level in decibel (dB) of a continuous, steady sound, that within a specified time interval, T, has the same mean squared sound pressure as the sound under consideration that varies with time, and is given by the formula:
where
pA(t) = instantaneous A-weighted sound pressure, in pascal (Pa); and
p₀ = reference sound pressure (20 μPa).
NOTE — Equivalent continuous A-weighted sound pressure level is mainly used for the assessment of environmental noise and occupational noise exposure.
2.14 Equivalent Sound Absorption Area of a Room, A — Hypothetical area of a totally absorbing surface without diffraction effects, expressed in square metre (m²) which, if it were the only absorbing element
in the room, would give the same reverberation time as the room under consideration.
2.15 Façade Level — Sound pressure level measured 1 m to 2 m in front of the façade.
NOTE — Façade level measurements of LpA are usually 2 dB to 3 dB higher than corresponding free-field measurements.
2.16 Free-Field Level — Sound pressure level measured outside, far away from reflecting surfaces.
NOTE — Measurements made 1.2 m to 1.5 m above the ground and at least 3.5 m away from other reflecting surfaces are usually regarded as being free-field measurements. To minimise the effect of reflections the measuring position should be at least 3.5 m to the side of the reflecting surface (that is, not 3.5 m from the reflecting surface in the direction of the source). Estimates of noise from aircraft overhead usually include a correction of 2 dB to allow for reflections from the ground.
2.17 Frequency — The number of cyclical variations per unit time. Frequency is generally expressed in cycles per second (cps) and is also denoted as Hertz (Hz).
2.18 Impact Sound Pressure Level, Li — Average sound pressure level in a specific frequency band in a room below a floor, when it is excited by a standard tapping machine.
2.19 Indoor Ambient Noise — Pervasive noise in a given situation at a given time, usually composed of noise from many sources, inside and outside the building, but excluding noise from activities of the occupants.
2.20 Insertion Loss ( LIL ) — Insertion loss is generally defined as the difference, in decibels, between two sound pressure levels (or power levels or intensity levels) which are measured at the same point in space before and after a muffler or any other noise control device is inserted between the measurement point and the noise source.
2.21 Noise — Unwanted sound which may be hazardous to health, interferes with communications or is disturbing.
2.22 Noise Exposure Forecast (NEF) — The noise exposure forecast at any location is the summation of the noise levels in EPN dB from all aircraft types, on all runways, suitably weighted for the number of operations during day time and night time.
2.23 Noise Criteria — Numerical indices used to define design goals for the maximum allowable noise in a given space.
2.24 Noise Rating (NR) — Graphical method for rating a noise by comparing the noise spectrum with a family of noise rating curves.
NOTE — Noise rating is described in Annex C.
2.25 Noise Reduction Coefficient (NRC) — A single figure descriptor of the sound absorption property of a material. It is the arithmetic mean of the sound absorption coefficients at 250, 500, 1 000 and 2 000 Hz rounded off to the nearest multiple of 0.05.
2.26 Normalized Impact Sound Pressure Level, Ln — Impact sound pressure level normalized for a standard absorption area in the receiving room.
NOTE — Normalized impact sound pressure level is usually used to characterize the insulation of a floor in a laboratory against impact sound in a stated frequency band (see Annex B).
2.27 Octave Band — Band of frequencies in which the upper limit of the band is twice the frequency of the lower limit.
2.28 Percentile Level, LAN,T — A-weighted sound pressure level obtained using time-weighting 'F', which is exceeded for N percent of a specified time interval.
Example:
LA90,1h is the A-weighted level exceeded for 90 percent of 1h.
NOTE — Percentile levels, determined over a certain time interval cannot accurately be extrapolated to other time intervals. Time-weighting ‘F’ or ‘S’ can be selected on most modern measuring instruments and used to determine the speed at which the instrument responds to changes in the amplitude of the signal. Time-weighting ‘F’ is faster than ‘S’ and so its use can lead to higher values when rapidly changing signals are measured.
2.29 Pink Noise — Sound with an uninterrupted frequency spectrum and a power which is steady within frequency band and proportional to centre frequency. An example is constant power level per octave band.
2.30 Pure Tone — A sound emitted at a single frequency.
2.31 Rating Level, LAr, Tr — Equivalent continuous A-weighted sound pressure level of the noise, plus any adjustment for the characteristic features of the noise.
NOTE — This definition is used for rating industrial noise, where the noise is the specific noise from the source under investigation.
2.32 Reverberation Time, T — Time that would be required for the sound pressure level to decrease by 60 dB after the sound source has stopped.
NOTE — Reverberation time is usually measured in octave or third octave bands. It is not necessary to measure the decay over the full 60 dB range. The decay measured over the range 5 dB to 35 dB below the initial level is denoted by T₃₀ , and over the range 5 dB to 25 dB below the initial level by T₂₀ .
2.33 Sound — A vibrational disturbance, exciting hearing mechanisms, transmitted in a predictable manner determined by the medium through which it propagates. To be audible the disturbance shall have to
fall within the frequency range of 20 Hz to 20 000 Hz.
2.34 Sound Exposure Level, LAE — Level of a sound, of 1 s duration, that has the same sound energy as the actual noise event considered.
NOTES
1 The LAE of a discrete noise event is given by the formula:
where
pA(t) = instantaneous A-weighted sound pressure, in pascal (Pa);
t₂-t₁= stated time interval in seconds (s) long enough to encompass all significant sound energy of the event;
p₀ = reference sound pressure level (20µ Pa) ; and
t₀ = reference time interval (1 s).
2 LAE is also known as LAX (single-event noise exposure level).
2.35 Sound Level Difference, D — Difference between the sound pressure level in the source room and the sound pressure level in the receiving room.
NOTE — D is given by the following formula:
D = L ₁ - L ₂
where
L₁ = average sound pressure level in the source room; and
L₂ = average sound pressure level in the receiving room.
2.36 Sound Power — The acoustic power of a sound source, expressed in Watt.
2.37 Sound Power Level ( Lw ) — The acoustic power radiated from a given sound source as related to a reference power level (typically 10-12 watt) and expressed in decibel as :
where
W = acoustic power, in watt.
By definition, 1W therefore corresponds to 120 dB for Lw.
2.38 Sound Pressure, p — Root-mean-square value of the variation in air pressure measured in pascal (Pa), above and below atmospheric pressure, caused by the sound.
2.39 Sound Pressure Level, Lp — Quantity of sound pressure, in decibel (dB), given by the formula:
where
p = root mean square sound pressure in pascals (Pa); and
p₀ = reference sound pressure (20µ Pa)
NOTE — The range of sound pressures for ordinary sounds is very wide. The use of decibels gives a smaller, more convenient range of numbers. For example, sound pressure levels ranging from 40 dB to 94 dB correspond to sound pressures ranging from 0.002 Pa to 1 Pa. A doubling of sound energy corresponds to an increase in level of 3 dB.
2.40 Sound Receiver — One or more observation points at which sound is evaluated or measured. The effect of sound on an individual receiver is usually evaluated by measurements near the ear or close to the body.
2.41 Sound Reduction Index, R — Laboratory measure of the sound insulating properties of a material or building element in a stated frequency band.
NOTE — For further information see Annex B.
2.42 Sound Source — Equipment or phenomena which generate sound. Source room is the room containing sound source.
2.43 Spectrum — A quantity expressed as a function of frequency, such as sound pressure versus frequency curve.
2.44 Standardized Impact Sound Pressure Level, LnT' — Impact sound pressure level normalized to that in a receiving room having a reverberation time of 0.5 s.
NOTE — Standardized impact sound pressure level is used to characterize the insulation of floors in buildings against impact sound in a stated frequency band (see Annex B).
2.45 Speech Interference Level (SIL) — A descriptor for rating steady noise according to its ability to interfere with conversation between two people. SIL is the arithmetic average of the sound pressure levels in the three octave bands with centre frequencies at 500, 1 000 and 2 000 Hz.
2.46 Standardized Level Difference, DnT — Difference in sound level between a pair of rooms, in a stated frequency band, normalized to a reverberation time of 0.5 s.
NOTE — Standardized level difference takes account of all sound transmission paths between the rooms (see Annex B).
p) Examples of common types of wall and floor construction with sound insulation have been reviewed and modified, wherever required.
q) Provisions have been updated to take care of the requirements of persons with disabilities.
There are two types of noises, that is, airborne and structure-borne noise. To reduce the intensity of airborne noise, sound absorbent materials may be used. An absorbent material is one which reduces the intensity of sound reflected from its surface. It may be applied to walls, floors, ceilings or used as furnishings to reduce the sound level by absorption. However, the materials selected for sound absorption shall be consistent with fire safety requirements of the buildings.
To reduce the transmission of airborne noise, sound insulating materials may be used. Sound insulating materials block the passage of noise through them by virtue of their mass and physical properties. The extent of noise reduction provided by a single homogeneous panel is proportional to the logarithm of mass per unit area. For high values of sound insulation, normally heavy panels are required. Thin sheets of materials do not have adequate mass for providing any appreciable sound transmission loss by themselves. However, when thin sheet materials are used in a double panel construction with an intervening air cavity, this special construction can give extremely high sound transmission loss values considering the mass of the partition, if designed properly. Porous materials lack the mass required to provide any appreciable sound transmission loss, and readily allow sound at most frequencies to be transmitted through them.
To reduce the transmission of structure-borne noise (such as noise generated by impacts) special construction methods and elastic discontinuity in the structure may be used. Structure-borne noise reduction is effected by corner joints, changes in cross-section, changes in materials, etc, in construction. The reduction by these construction methods is, however, not appreciable especially when a large amount of noise reduction is required over a short distance. In such cases, introduction of an elastic discontinuity in the structure can result in a very large amount of noise reduction. The noise transmission is affected only above a certain lower frequency which depends on the material thickness and the elastic properties of the material. Bonded fibrous materials, rubber elastomers, cork, etc. are suitable for curtailing structure-borne noise transmission.
This Section is largely based on the following standards:
IS 1950 : 1962 Code of practice for sound insulation of non-industrial buildings
IS 3483 : 1965 Code of practice for noise reduction in industrial buildings
IS 4954 : 1968 Recommendations for noise abatement in town planning
IS 11050 (Part 1): Rating of sound insulation in buildings and of building elements: Part 1 Airborne sound insulation in buildings and of interior building elements 1984
IS 11050 (Part 2): Rating of sound insulation in buildings and of building elements: Part 2 Impact sound insulation 1984
BS 8233 : 2014 Code of practice for sound insulation and noise reduction for buildings
All standards, whether given herein above or cross-referred to in the main text of this Section, are subject to revision. The parties to agreement based on this Section are encouraged to investigate the possibility of applying the most recent editions of the standards.
4
NOTE — When elements of a structure vibrate they radiate noise and, if the vibration is high enough, this noise can be audible. Ground-borne and structure-borne noises are rarely an issue outside buildings or structures.
2.47.1 Ground-Borne Noise — Audible noise caused by the vibration of elements of a structure, for which the vibration propagation path from the source is partially or wholly through the ground.
NOTE — Common sources of ground-borne noise include railways and heavy construction work on adjacent construction sites.
2.47.2 Structure-Borne Noise — Audible noise caused by the vibration of elements of a structure, the source of which is within a building or structure with common elements.
NOTE — Common sources of structure-borne noise include building services plant, manufacturing machinery and construction or demolition of the structure.
2.48 Transient Sound — Sound which is audible for a limited period of time, for example, sound from over flight of an airplane.
2.49 Third Octave Band — Band of frequencies in which the upper limit of the band is 2(1)/(3) times the frequency of the lower limit.
2.50 Threshold of Hearing — The lowest continuous sound pressure level which will create an auditory sensation for the average human ear. Any sound below these levels will be inaudible and any sound above the threshold will vary in loudness dependent on intensity.
2.51 Vibration Isolation — Reduction of force or displacement transmitted by a vibratory source, often attained by use of a resilient mount.
2.52 Wavelength — The length in space of one complete cycle of a sound wave given by:
2.53 Weighted Level Difference, Dw — Single-number quantity that characterizes airborne sound insulation between rooms but which is not adjusted to reference conditions.
NOTE — Weighted level difference is used to characterize the insulation between rooms in a building as they are; values cannot normally be compared with measurements made under other conditions {see good practice [8-4(1)]}.
2.54 Weighted Sound Reduction Index, Rw — Single number quantity which characterizes the airborne sound insulating properties of a material or building element over a range of frequencies.
NOTE — The weighted sound reduction index is used to characterize the insulation of a material or product that has been measured in a laboratory (see Annex B).
2.55 Weighted Standardized Impact Sound Pressure Level, L'nT,w — Single number quantity used to characterize the Impact sound insulation of floors over a range of frequencies.
NOTE — Weighted standardized impact sound pressure level is used to characterize the insulation of floors in buildings (see Annex B).
2.56 Weighted Standardized Level Difference, DnT,w — Single-number quantity, which characterizes the airborne sound insulation between rooms
NOTE — Weighted standardized level difference is used to characterize the insulation between rooms in a building (see Annex B).
2.57 Weighted Normalized Impact Sound Pressure Level, L'n,w — Single number quantity used to characterize the impact sound insulation of floors over a range of frequencies.
NOTE — Weighted normalized impact sound pressure level is usually used to characterize the insulation of floors tested in a laboratory (see Annex B).
2.58 White Noise — A noise whose spectrum (level) density is substantially independent of frequency over a specified range and has equal power for any range of frequencies of constant band width.
3 PLANNING AND DESIGN AGAINST OUTDOOR NOISE
Planning against noise should be an integral part of town and country planning proposals, ranging from regional proposals to detailed zoning, and three-dimensional layouts and road design within built-up areas. Noise nuisance should be fully recognized in zoning regulations.
3.1.1 Noise is either generated by traffic (road, air, and surface and underground railway) or it arises from zones and buildings within built-up areas (industry, commerce, offices and public buildings), and from public gatherings and social activities. For planning, the noise survey should examine all the possible causes of noise and consider the various factors causing actual nuisance.
3.1.2 Noise by night, causing disturbance of sleep, is more of a nuisance than noise by day. For this reason, housing colonies that adjoin areas with heavy traffic movement during the night are liable to cause serious complaints. Also, the factories that work by night are liable to cause serious complaints if housing estates adjoin them. While planning, care should be taken that housing colonies are adequately set back from busy airports, state and national highways, factories, main railway lines and marshalling yards.
3.1.3 There are two aspects of defence by planning. The first is to plan so as to keep the noise at a distance. Under this aspect comes the separation of housing from traffic noise by interposing buffer zones, and the protection of schools and hospitals by green belts, public gardens, etc. The second is the principle of shading or screening. This consists of deliberately
interposing a less vulnerable building to screen a more vulnerable one or by providing a solid barrier, such as a wall, between the source and the location to be protected.
For guidance, approximate noise levels due to various types of aircrafts, measured on ground, when the aircrafts fly overhead at a height of 450 m, are given in Table 1.
| Table 1 Typical Noise Levels of Some Aircraft Types(Clause 3.2.1) | ||
| Sl No. | Type of Aircraft | Flyover Noise Levels at 450 m with Take-off Thrust EPN dB |
| (1) | (2) | (3) |
| i) | Boeing 737 | 107 |
| ii) | Boeing 747-200 | 103 |
| iii) | Airbus A300 | 101 |
Noise levels of some typical railway traffic are given in Table 2.
| Table 2 Typical Noise Levels of Railway Trains(Clause 3.2.2) | ||
| Sl No. | Type of Train | Noise Level at 30 m, Measured on the Side or in the Direction of Train |
| (1) | (2) | dBA(3) |
| i) | Steam train, 60 km/h | 85 |
| ii) | Diesel train, 60 km/h | 83 |
| iii) | Electric train, 60 km/h | 77 |
The level of noise generated by road traffic depends upon such factors as the number of vehicles passing per hour, the type of traffic, the preponderance of heavy vehicles, average speed, gradient and smoothness of traffic flow. The smoothness of traffic flow also affects variability of the noise and is governed by such features as roundabouts and traffic lights, and the volume of traffic and pedestrian movement with their effects on stopping, starting, overtaking and honking. The level of traffic noise fluctuates continuously and the way it does, has a considerable effect on the nuisance caused. For assessing traffic noise, noise is measured in dBA. Because of the fluctuating nature of traffic, noise levels due to different volumes of traffic flow with a varying mix of vehicles are given in Table 3.
| Sl No. | Type of Traffic | L₁₀ 30 m from Edge of Road dBA |
| (1) | (2) | (3) |
| i) | 5 000 vehicles per 18 hour day(10 percent heavy vehicles), 50 km/h | 65 |
| ii) | 10 000 vehicles per 18 hour day(20 percent heavy vehicles), 60 km/h | 70 |
| iii) | 10 000 vehicles per 18 hour day(40 percent heavy vehicles), 80 km/h | 75 |
| iv) | 20 000 vehicles per 18 hour day(40 percent heavy vehicles), 80 km/h | 77 |
| NOTE — The values are applicable to free flowing traffic without honking. | ||
The outdoor noise regulations in force from time to time shall be complied with (see also Annex D).
Near airports two sources of aircraft noise should be considered.
a) Flyover noise — Flyover noise is that which occurs under flight paths close to airports and is the most serious and common problem. As the aircraft passes overhead the noise level at any particular location rises to a peak and then decreases.
b) Ground noise — The noise emitted by an aircraft during ground operations is less variable in direction than flyover noise, but is usually of a longer duration.
3.4.1.1 Aircraft noise may disturb sleep, rest and communication, and as such may be considered potentially harmful to health. It is important that no new development is carried out within areas where the expected noise levels will cause mental and physical fatigue or permanent loss of hearing. In case development in such areas is essential, adequate sound insulation shall be provided for the building.
3.4.1.2 As the problems caused by aircraft noise have become more acute, a number of methods have been devised for evaluating noise exposure in the vicinity of airports. They all combine many factors into a single number evaluation. A commonly used criterion is the noise exposure forecast (NEF). The NEF is used primarily to develop noise contours for areas around airports. It has been accepted generally that noise exposure forecast levels greater than NEF 40 are
unacceptable to people while levels less than NEF 25 are normally acceptable. Levels between NEF 25 and 40 may lead to subjective complaints.
3.4.1.3 While it is theoretically possible to provide sufficient insulation to achieve an acceptable indoor noise environment in the area of very high outdoor noise, there is a level above which aircraft noise seriously affects living conditions no matter how much sound insulation has been applied to the dwelling unit. For this reason it is recommended that no residential development be allowed beyond the NEF 35 level.
3.4.1.4 During summer months, the windows are normally kept open for adequate ventilation. In view of this, no matter how much sound insulation is provided for the building structure, the noise level inside the room can never be less than 10 dB below the outdoor noise level. For very critical buildings, such as buildings necessary for maintaining and supplementing the airport services, and for commercial development, such as hotels, it is possible to provide sealed windows and to centrally air condition the entire building. However, it is not feasible for most of the residential developments in the country. In such cases proper zoning regulations and siting of vulnerable buildings away from aircraft noise are of vital importance.
This is a very serious source of noise in built-up areas, both by day and by night. Railway cuttings reduce the spread of noise, whereas embankments extend it. The elevated railway on viaducts or embankment is very common in built-up areas. The elevation increases exposure to noise but in addition the construction of the viaduct may affect the propagation of noise. In this respect solid embankments are preferable to built-up arches, which tend to act as sound boxes. Worst of all are the steel bridges, which greatly magnify the noise due to vibration. Uphill gradients are another feature tending to increase noise, especially of heavy goods trains.
3.4.2.1 Wherever possible, no residential or public building zone should abut onto railway lines, especially on the marshalling yards which is particularly objectionable because of the shrill, clanging and intermittent noise they generate, often at night. The appropriate zones alongside railway lines are industrial and commercial buildings other than office buildings. Where these precautions are not practicable and housing has to abut on to railway lines, every attempt may be made to house as few people as possible in the vicinity of the railway lines.
3.4.2.2 Underground transportation system can be a major cause of disturbance for the neighbouring community. Very high noise levels are propagated to
long distances by the underground high speed railway, as a result of wheel-rail interaction. Both airborne noise and ground or structure-borne vibrations are potential sources of complaints. Noise control measures, therefore, need to be considered for the following:
a) In stations, where high noise levels are produced at the arrival and departure of trains;
b) In tunnels, during high speed train movement;
c) Where an underground rail transit system passes close to existing structures or high rise buildings, adequate attention should also be paid to the problem of ground vibration transmitted to the building, and proper isolation should be provided for critical areas;
d) Wherever elevated railway tracks are provided, adequate measures should be taken to avoid the spread of noise in the surrounding built up areas; and
e) In transit cars, where sound insulation is of vital importance to provide comfortable conditions for the commuters.
3.4.3.1 Convoys of long distance heavy trucks at night moving past through built-up areas cause serious noise complaints. On busy roads, the noise of continuous traffic may be a worse nuisance than that of railways. At least the same precautions may, therefore, be taken in the planning of dwellings in relation to arterial and trunk roads as with railways. Care may be taken that local housing roads do not provide short cuts for heavy traffic through residential areas. Hilly roads present the additional noise of gear changing. Trees with heavy foliage planted on both sides of carriageway help slightly to muffle the noise, provided the foliage extends for a considerable distance (30 m or above).
3.4.3.2 Road traffic may give rise to serious nuisance particularly on busy thoroughfares, between continuous high buildings in main streets, at the traffic lights, near bus stops, on steep slopes and in parking spaces and enclosed yards.
3.4.3.3 For zoning and planning of new buildings in urban areas, it is recommended that external LA10 be limited to a maximum of 70 dBA when the dwellings are proposed to have sealed windows and 60 dBA when the dwellings are proposed to have open windows. Indeed it is desirable to confine major new residential development to locations subject to LA10 levels substantially lower than those given above.
It is recognized, however, that within the large urban areas, the use of sites where the external LA10 is greater than 60-70 dBA cannot always be avoided. In that case it is suggested to utilize such design solutions as barrier
blocks in order to reduce external LA10 noise levels to at least 60-70 dBA at any point 1.0 m from any inward looking façade. When the orientation of site and the density of development are such that this cannot be fully achieved some form of dwelling insulation will have to be provided. It should be appreciated that where open windows are necessary, the occupants would have to put up with discomfort if the above conditions are not met.
3.4.3.4 Certain other methods can often be utilized to provide economical and effective protection from noise, as follows:
a) Methods should be adopted to improve the smoothness of flow and reduce number of stopping and starting. This leads to an improvement even, if it leads to increased flows. Flow linking of traffic lights, for example, may reduce noise nuisance.
b) Use of roads passing through residential areas should be prohibited to heavy commercial vehicles. An alternative would be to limit use by commercial vehicles to certain times of the day.
c) Use of honking shall be prohibited near sensitive buildings, such as hospitals and the like.
d) Barriers shall be provided to shield sites from noise.
3.4.4.1 Construction activities relating to building and infrastructure facilities cause noise disturbance to occupants in existing built facilities located around the site.
Construction noise involves both stationary and mobile sources. Common activities and sources of concern in case of construction noise include excavation and site clearing activities, blasting, piling, operation of batching plants, concrete mixers, pumping, running of diesel generators, drilling and chipping, loading/unloading activities, and truck and other vehicular movement.
The source noise intensity and spectrum is primarily characterized by the type of construction activity, equipment used, ground conditions and associated vehicular movement. Apart from the source characteristics, community noise impact is influenced by the time and sequence of construction related activities.
3.4.4.2 Noise control can be done at the source or in the noise propagation path. While it is preferable to adopt noise control at the source, it may not be practically possible to implement it for some of the
construction equipment. Given the diversity of noise sources, mitigation strategies in case of construction noise have to be dealt with appropriately depending on the spectral characteristics of sources.
Source noise control strategies include providing acoustic enclosures for sources like diesel generators, choosing less noisy construction machinery and selecting alternative construction practices which involve lesser noise generation.
Noise control in the propagation paths primarily involves provision of noise barriers around the construction sites.
Positioning of major fixed construction equipment/ installations such as batching plants and diesel generators have a significant impact on the noise spectrum and its impact. Also, time of operation and duration of noisy construction activities have significant impact on the resultant annoyance.
3.4.4.3 Due consideration for environmental noise regulation should be given while scheduling and sequencing noisy construction activities.
The zoning of the different cities shall be done by the town planning authorities, taking into account besides other aspects, the noise levels from different occupancies. Wherever necessary, experts in the field may be consulted. For detailed information on noise reduction for town planning schemes, reference may be made to good practice [8-4(2)].
Where relief from noise is to be provided by means of green belts these may be of considerable width and be landscaped. (In case of railway tracks, a minimum distance of 50 m to 70 m may be provided between the buildings and the tracks). The extent of relief that may be derived from the above may be estimated only after considering other environmental factors. Only thick belts of planting (greater than 30 m) are of real value. Strong leafy trees may be planted to act as noise baffles. Shrubs or creepers may also be planted for additional protection between tree trunks; artificial mounds and banks should be formed where practicable. As little hard paving and as much grass as possible may be used. The creation of green belt is particularly advisable on the perimeter of aerodromes, along railway lines and arterial roads, through or past built-up areas and adjoining noisy industrial zones.
Barriers are often the most effective means of reducing traffic noise around residential areas. They have the
great advantage that they generally protect most or all of the site. In nearly all situations, a well-designed barrier of even a modest height (say 3 m) can at least ensure that all areas of open space are free from excessive noise levels.
There are two types of barriers that can be built to protect sites; one which are built solely for the purpose of reducing noise and the other which form part of the building complex (barrier blocks). Free standing walls and artificial mounds are typical examples of the first type while single and multi-storeyed utility buildings and garages are the most common form of the second.
Of the two types, laying out barrier blocks of a complex in an appropriate fashion is a better option because they are cheaper and also tend to form a more effective barrier overall because of their greater height and width. Barrier walls or mounds are more limited in their effect than barrier blocks for they protect little more than the area of the site close to ground level essentially because of the lack of height, as continuous walls much higher than 3 m are often difficult to construct.
The purpose of noise control is to ensure that people are neither harmed nor disturbed by noise. In addition to provisions given in this Section, special advice may be required for more complex situations, such as those listed in Annex E.
The generally acceptable noise levels inside buildings are given in Table 4.
(Clause 4.1)
| Sl No.(1) | Location(2) | Noise LeveldBA(3) |
|---|---|---|
| i) | Auditoria and concert halls | 20-25 |
| ii) | Radio and TV studios | 20-25 |
| iii) | Cinemas | 25-30 |
| iv) | Music rooms | 25-30 |
| v) | Hospitals | 35-40 |
| vi) | Apartments, hotels and homes | 35-40 |
| vii) | Conference rooms, small offices and libraries | 35-40 |
| viii) | Court rooms and class rooms | 40-45 |
| ix) | Large public offices, banks and stores | 45-50 |
| x) | Restaurants | 50-55 |
Some buildings or parts of buildings are especially
vulnerable to noise, for example, recording and radio studios, hospitals and research laboratories. These should not be sited near loud noise sources. Most vulnerable buildings contain some areas which are themselves noisy and in such buildings the less vulnerable elements should be planned to act as noise buffers. Most noisy buildings also contain quiet accommodation, which equally may be planned to act as a buffer between the noisy part of the building and adjoining vulnerable buildings.
4.3 The details of site and internal planning and insulation requirements are covered under individual occupancies (see 5 to 12) as applicable to the respective character and sources of noise in different buildings.
People with hearing impairments have particular difficulty in making out sounds and words in noisy environments. Therefore, adequate sound insulation would minimise noise from both outside and inside the building. Also, low reverberation times are more suitable for hearing impaired persons and should thus be planned while designing the size and shape of the room.
Persons using hearing aids may require quiet areas with induction loops in very noisy information counters or where announcements are made. Induction loops may also be provided in all areas where there are verbal inputs provided, such as conference halls, auditoria, class rooms and cinema halls.
The desired (acceptable) noise levels and the recommended insulation values for the various areas may be achieved by providing sound insulation treatments by constructional measures. The details of the same are given in Annex F. The recommendations given in Annex F are applicable to non-industrial buildings like residences, educational buildings, hospitals and office buildings.
4.5 Special Problems Requiring Expert Advice — See 3.8 and Annex E.
The main sources of outdoor noise in residential areas are traffic (aeroplane, railways, roadways), children playing, hawkers, services deliveries, road repairs, blaring loud-speakers, various types of moving machinery in the neighbourhood and building operations, and captive power generation machinery.
12
5.1.2.1 As far as indoor noises are concerned, conversation of the occupants, footsteps, banging of doors, shifting of the furniture, operation of the cistern and water closet, playing of radio, television, music system, cooling and ventilation machinery, etc, contribute most of the noise emanating from an adjacent room or an adjacent building. Noise conditions vary from time to time and noise which may not be objectionable during the day may assume annoying proportions in the silence of the night when quiet conditions are essential.
5.1.2.2 In the case of flats the main sources of noise are from other flats and from stairs, lifts and access balconies. Plumbing noise is another cause. In semi-detached buildings, outdoor noises from streets are noticed more than indoor noises from neighbours.
The most desirable method is to locate the residential buildings in a quiet area away from the noisy sources like the industrial areas, rail tracks, aerodromes, roads carrying heavy traffic, etc.
5.2.1.1 To minimise ground reflection, the dwellings should be surrounded by the maximum amount of planting and grassed areas and the minimum amount of hard surfacing. This applies particularly to high density areas. Where for maintenance reasons a large amount of hard paving is necessary, it should be broken up by areas of planting and grassing. Narrow hard paved courts should be avoided between adjacent tall buildings.
5.2.1.2 Roads within a residential area should be kept to a minimum both in width and length, and should be designed to discourage speeding. Area-wise planning, with zones from which vehicular traffic is altogether excluded will greatly help to reduce noise. Roads with through traffic should be excluded from residential areas, but where sites have to be developed adjacent to existing major roads the same principles should be observed in the siting of blocks as with railway lines as covered under 3.4.2.1.
5.2.1.3 Play areas for older children should be sited as far away from dwellings as possible. Special care should be taken with old peoples' dwellings. They should not be placed immediately adjacent to service entries, play spaces, or to any entrances where children may tend to congregate.
The orientation of buildings in a locality should be
planned in such a way as to reduce the noise disturbance from neighbourhood areas. The non-critical areas, such as corridors, kitchens, bathrooms, elevators and service spaces may be located on the noisy side and the critical areas, such as bedrooms and living space, on the quiet side.
Windows and doors should be kept away from the noisy side of the building as given below, wherever possible:
a) When windows of a building, particularly those of bedrooms in apartments or flats, face roads carrying heavy traffic or other noises where the external noise is of the order of 80 to 90 dBA, the building should be located at a distance of about 30 m from the road, but a distance of 45 m or more, where possible, should be aimed at for greater relief from noise;
b) When the windows are at right angles to the direction of the above type of noise, the distance from the road should be arranged to be about 15 to 25 m; and
c) In case another building, boundary wall or trees and plantations intervene between the road traffic and the house/flat further noise reduction is achieved and in such cases the above distances may be reduced suitably.
It is desirable that rooms adjoining party walls and above/below party floors should be of similar use. By this means, bedrooms are not exposed to noise from adjoining living rooms, and there is less risk of disturbance of sleep.
In semi-detached houses, the staircase, hall and kitchen should adjoin each other on each side of the party wall, thus providing a sound baffle between rooms requiring quiet conditions.
Bedrooms should not be planned alongside access balconies, and preferably not underneath them. Where the approach is by an internal corridor, a sound baffle may usefully be provided by arranging internal passages and bathrooms between the corridor and the living room or bedrooms.
Kitchens and water closets should not be planned over living rooms and bedrooms, whether within the same dwelling or over other dwellings. Soil pipes should not be carried in ducts which adjoin living rooms or bedrooms unless the side of the duct next to these rooms is a solid wall containing no inspection openings. Refuse chutes should not be planned next to living rooms or bedrooms.
The weighted sound reduction index, Rw , of partitions between individual rooms or apartments of a building unit shall be as given in Table 5. These values may, however, be suitably increased, where required, for critical areas.
| Sl No.(1) | Situation(2) | Rw dB(3) |
| i) | Between the living room in one house or flat and the living room and bed-rooms in another | 50 |
| ii) | Elsewhere between houses or flats | 45 |
| iii) | Between one room and another in the same house or flat | 35 |
| NOTES | ||
| 1 Where communicating doors are provided, all doors should be so designed as to provide recommended insulation between the rooms. | ||
| 2 There are cases when a set of houses or flats have to be built for the people who work at night and sleep during the day. It is desirable to consider the design of at least one such room in each of the houses or flats which will provide an insulation of about 45 dB in that room. | ||
| 3 The insulation values referred to are applicable with doors and windows shut. | ||
All items of equipment that are potentially noisy should be selected with care. Water closet cisterns should not be fixed on partitions next to bedrooms or living rooms. Plumbing pipes should be isolated from the structures. Lift motors should be mounted on resilient supports. Access doors from machine rooms to internal staircases should be well fitting and of solid construction. Special noise control measures may be required for electrical and mechanical services such as diesel generators, outdoor air conditioning units, cooling towers, etc.
Reduction of airborne noise requires the use of rigid and massive walls, or acoustically designed dry walls, without any openings. Openings are the major cause of penetration of noise through a barrier. While designing it should be borne in mind that all components should provide a sound transmission compatible with that of the rest of the barrier so that an equivalent amount of sound energy is transmitted through each portion of the barrier.
The outdoor sources of noise produced on school premises, which cause disturbance within the school, include the noise arising from playgrounds, playing fields and open-air swimming pools. Though playgrounds are used mainly during break periods, they are also used for games and physical education at times when teaching is in progress in the adjoining class rooms.
Indoor sources of noise are as follows:
a) Singing, instrumental and reproduced music which may take place in class rooms and in dining and assembly halls particularly in primary schools. In secondary schools, specialized music rooms are generally provided;
b) Movement of chairs, desks and tables at the end of one period may disturb a class engaged in a lesson in a room below;
c) Shutting and openings of doors and windows which may occur at any time during teaching periods;
d) Audio-visual presentations in class rooms;
e) Wood and metal workshops, machine shops
(engineering laboratories), typing rooms, etc, that produce continuous or intermittent sound of considerable loudness;
f) Practical work carried out in general teaching areas;
g) Gymnasia and swimming pools;
h) School kitchens and dining spaces where food preparation and the handling of crockery and utensils persist for the greater part of the school day;
j) Corridors and other circulation spaces; and
k) Plumbing and mechanical services.
Where outdoor noise nuisance exists from local industry, busy roads, railway, airfields, sport grounds or other sources beyond the control of the school authority, school buildings should be sited as far away from the sources of noise, as possible.
6.2.1.1 Rooms should be planned in a manner so that the minimum amount of glazing is placed on the side facing the external noise.
6.2.1.2 Noises arising from the activities of a school and from the use of the buildings after school hours may constitute a nuisance to occupants of surrounding property; therefore, it is desirable to place playgrounds, workshops, swimming pools, music rooms, assembly halls and gymnasia as far away as possible from buildings which require a quiet environment.
The following principles should be observed in the detailed planning of educational buildings:
a) Grouping — Noisy rooms should be separated from quiet ones, if possible. In general, it is desirable that rooms should be grouped together in accordance with the classification given in 6.2.4.1.
b) Windows and ventilators — Windows of noisy and quiet rooms should not open on to the same courtyard or be near to one another. Skylights and ventilators over noisy rooms should be avoided, if they are likely to be a source of nuisance to adjacent upper floors.
c) Doors — Swing doors into rooms should only be used where no problem of sound transmission exists. Reduction of insulation between rooms and corridors due to doors shall be borne in mind. The type and method of fitting of doors is important and necessary care shall be paid in this respect.
d) Sliding partitions, if used, should be acoustic operable partitions. Pass-through doors, if provided, should be acoustic doors with drop seals.
e) Open planning and circulation areas — Where open planning is used to permit spaces, such as assembly halls, dining rooms or entrance halls to be used in association with each other or for circulation, the degree of disturbance caused by interfering noise to teaching areas needs careful consideration; traffic through such areas should be strictly controlled; full use should be made of sound absorbent treatments to reduce the spread of noise from one space to another (see 6.2.3).
If rooms have large glazed panels or ventilation openings facing directly on the circulation areas, human traffic passing by the rooms should be controlled. Preferably baffled ventilation system or double windows should be used. Fan-lights over doors should be fixed and glazed.
f) Furniture — In all educational buildings, regardless of the character of the floor finish, rubber buffers should be fitted to the legs of chairs and tables.
Sound absorbent materials play a useful part in reducing the built-up or airborne noise at source. In rooms, such as classrooms, assembly halls and music rooms, a fairly short reverberation time under occupied conditions is one of the requirements of the acoustic design. The maximum reverberation times permissible for this purpose are usually short enough to give adequate noise control but in addition, the reverberation time should not be excessive under empty conditions, because noise may occur in these rooms with very few occupants. Table 6 gives the reverberation times often arranged in occupied rooms for acoustic reasons and the maximum times recommended in the empty rooms for noise reduction; the times given are for a frequency of 500 Hz, but they should not be greatly exceeded at any frequency. When rooms are used for a variety of purposes, the reverberation period appropriate to the major use should be adopted.
6.2.3.1 Special attention should be given to noise reduction in schools for the hearing impaired and schools for the visually impaired. Hearing impaired children are taught by means of hearing aids which cannot be used satisfactorily in high noise levels or in reverberant conditions. Visually impaired children depend on good hearing for understanding speech and for detecting changes in environment. In both these types of schools, noise levels should be kept low and
6.2.4.2 The recommended minimum sound reduction (Dw) between rooms of the same class is as follows:
reverberation times short. As an example, the reverberation times in empty classrooms should not exceed 1.0 s in schools for the visually impaired or 0.5 s in schools for the hearing impaired.
| Table 6 Reverberation Times in Schools(Clause 6.2.3) | |||
| Sl No. | Room | Reverberation Time | |
| Usual for Acoustic Reasons (Full) | Maximum¹⁾ for Noise Control (Empty) | ||
| (1) | (2) | (3) | (4) |
| i) | Assembly halls | 1.0-1.25 according to size | 1.5-2.0 according to volume of hall |
| ii) | Music teaching rooms | 0.75-1.25 | 1.5 |
| iii) | Gymnasia and indoor swimming pools | — | 1.5 |
| iv) | Dining rooms | — | 1.25 |
| v) | Classrooms | 0.6 | 1.1 |
| vi) | Headmasters room and staff rooms | 0.5-1.00 | 1.0 |
| ¹⁾ Shorter reverberation times are desirable for noise control, whenever possible. | |||
For purposes of sound insulation, rooms in educational buildings may be classified as follows:
| Class A | Noise producing | a) Workshopsb) Kitchensc) Dining roomsd) Gymnasiumse) Indoor swimming pools |
|---|---|---|
| Class B | Noise producing but needing quiet at times | a) Assembly hallsb) Lecture hallsc) Music roomsd) Typing rooms |
| Class C | Average | a) General classroomsb) Practical roomsc) Laboratoriesd) Offices |
| Class D | Rooms needing quiet | a) Librariesb) Studies |
| Class E | Rooms needing privacy | a) Medical roomsb) Staff rooms |
| a) | Class A | : | 25 dB |
|---|---|---|---|
| b) | Class C or D | : | 35 dB |
| c) | Class B or E | : | 45 dB |
6.2.4.3 Where a room is likely to have a dual use, for example, a dining room to be used as a classroom, the higher sound insulation value should be used.
6.2.4.4 The recommended minimum sound reduction (Dw) between rooms in different classes is 45 dB subject to the following:
a) In schools or institutes with a technical bias where noisy activities, such as sheet metal work, plumbing and woodwork, are likely to be practised extensively in normal hours, workshops should be regarded as a special category requiring more than 45 dB isolation ( Dw ) from rooms of any other class.
b) Assembly halls and music rooms are special cases in that, as well as producing noise, they also require protection from it and may need more than 45 dB isolation ( Dw ) from rooms in Class A, if the latter are very noisy.
c) Circulation spaces may vary from a long and frequented corridor to a small private lobby and it is therefore difficult to give precise recommendations to cover them. For partitions between rooms in Class C and most corridors, an Rw of 35 dB for the partition itself is adequate. For partitions between rooms in other classes and corridors, more or less insulation may be necessary, depending upon the specific usage.
d) The problem of noise in circulation areas is as a rule greatly mitigated in schools by the fact that classes usually change rooms together at regular times. In colleges and evening institutes, however, this is much less true and in such buildings particular attention should be paid to insulation between rooms and corridors.
Problems of noise control vary from hospital to hospital but the principles outlined below apply to all types. A quiet environment in hospitals is desirable for patients who are acutely ill. Staffs require quiet conditions for consultations and examinations and also in their living and sleeping quarters. There have been rapid rises in noise levels in hospitals due to the higher levels of outdoor noise, increasing use of mechanical and mobile equipment (some of which is now brought much nearer to the patient in order to facilitate nursing procedure) and the introduction of loudspeaker, radio, television and call systems. Noise control in the hospital is made much more difficult by the extensive use of hard washable surfaces which reflect and intensify the noise. In most hospitals, windows to the open air and fanlights to corridors are usually open for the purpose of ventilation, admitting noise from outside and allowing it to spread through the building.
This may be classified into two main categories:
a) Noise from sources outside the hospital premises, for example, traffic and industrial noises; and
b) Noise from sources outside the building but usually within the control of the hospital authority, for example, ambulances, motor-cars and service vehicles, fuel and stores deliveries, laundries, refuse collection, trucks and trolleys.
A hospital is a complex building with many services and the numerous internal sources of structure-borne and airborne noises are grouped into three main categories:
a) Noise consequent upon hospital routines. This category includes sources which transmit noise through both structure-borne and airborne paths, many of which may be quite near to patients particularly those in wards, such as the following:
Wheeled trolleys of various kinds, for food and medical supplies;
Sterilizing equipment;
Sluice room equipment including bedpan washers;
Ward kitchen equipment;
Footsteps;
Doors banging;
Handling of metal or glass equipment;
Noises caused during maintenance and overhaul of engineering services; and
Vacuum cleaners, mechanical polishers, etc.
b) Loudspeaker, radio or television, audible call system, telephone bells and buzzers, and other airborne noises, such as loud conversation; and
c) Noises from fixed or mobile equipment and services not directly concerned with hospital routines. These include all the fixed services as given below:
Plumbing and sanitary fittings;
Steam hot and cold water and central heating pipes;
Ventilation shafts and ducts;
Fans
Boilers;
Pumps;
Air compressors;
Pneumatic tubes;
Electrical and mechanical motors and equipment;
Lifts;
Laundry equipment; and
Main kitchen equipment (refrigerators, mixers, steam boilers, etc).
Hospital sites with their high degree of sensitivity to outside noise should be as far away from outside sources as may be compatible with other considerations, such as accessibility and availability of services. The building should be so arranged on the site that sensitive areas like wards, consulting and treatment rooms, operating theatres and staff bedrooms are placed away from outdoor sources of noise, if possible, with their windows overlooking areas of acoustic shadow.
There is a very large number of unit and room classification in hospital design and in planning the units in relation to each other and to the common services, (such as X-ray departments, operating theatre suits and main kitchens), noise reduction in the sensitive areas should be weighed carefully against other design factors. Special care in overall planning and internal planning against noise is required in the planning within the building of units which are themselves potential noise sources, for example, children's wards and
outpatients' departments, parts of which require protection against noise.
7.3.2.1 Unloading bays, refuse disposal areas, boiler houses, workshops and laundries are examples of service units which should be as far from sensitive areas as possible.
7.3.2.2 The kitchen is a constant source of both airborne and structure-borne noise and should preferably be in a separate building away from or screened from the sensitive areas. If this is not possible and the main kitchens shall form part of a multi-storeyed building, noise control is easier if they are placed below and not above the wards and other sensitive rooms so as to facilitate the insulation of the equipment and machinery in order to reduce the transmission of structure-borne noise to a minimum.
7.3.2.3 In ward units, the kitchens, sluice rooms, utility rooms, sterilizing rooms and other ancillary rooms, need to be placed quite near to the beds if they are to fulfil their purposes, which are all sources of noise. Some form of noise baffling between open wards and rooms of this kind will be needed.
In view of the difficulty of suppressing noise in hospital buildings, it is important to eliminate noise at its source, wherever possible.
Mats of rubber or other resilient material on draining boards and rubber-shod equipment will greatly reduce noise from utility rooms, sluice rooms and ward kitchens. The use of plastics or other resilient materials for sinks, draining boards, utensils and bowls would also reduce the noise. Many items of equipment especially mobile equipment, such as trolleys, beds and movable furniture, may be silenced by means of rubber-tyred wheels and rubber bumper and the provision of resilient floor finishes (see 7.3.4.1). The latter also reduces footstep noise. Silent type curtain rails, rings and runners should be used. Lift gates and doors should be fitted with buffers and silent closing gear. Fans and other machinery should be mounted on suitable resilient mountings to prevent the spread of noise through the structure.
Modern office buildings are often noisier than older buildings due to the use of thinner and more rigid forms of construction, harder finishes, more austere furnishings and use of business machines.
Main sources of indoor noise include the following:
a) Office machines, such as keyboards, typewriters, and printers;
b) Telephonic conversation;
c) Noise from the public admitted to the building;
d) Footsteps, voices and slamming of doors in circulation spaces, lift doors and gates;
e) Sound reproduction in staff training rooms, conference rooms and recreation rooms, etc;
f) Handling of crockery and utensils in canteens and kitchens; and
g) HVAC and lift machinery.
Rooms demanding quiet conditions should be placed on the quiet side of the site. Even on quiet thoroughfares, these rooms should also not be planned at street level. They should also not be planned on enclosed yards used for parking of cars, scooters, etc. Where, however, the problems cannot be resolved by planning, the provision of double windows may be necessary.
The reverberation time should not exceed 1.0s in all
general offices of the types listed in 8.3.2.2 to 8.3.2.6. In small private offices, the reverberation time should not exceed 0.75s, in very large offices the reverberation time may be increased to 1.0s. For canteens, the recommended maximum reverberation time is 1.0s.
NOTE — All reverberation times are specified for a frequency of 500 Hz.
The grouping of departments and machines together in one room should be avoided, wherever possible. Where supervision is necessary the provision of glazed screens carried up to the ceiling should be considered. If it is essential to the work of an office for machine operators and clerks to work side by side in the same room, the machines should be enclosed by panels or low screens lined with absorbent material and the ceiling should be sound absorbent. In addition, the machines should be as quiet as possible in operation and mounted on suitable resilient mountings.
NOTE — A quiet area should be planned for prolonged telephonic conversation.
Modern construction methods and economy dictate the use of light weight construction for many office buildings. While the lightweight materials lead to fast fabrication and erection and also effect considerable economy in the building structure, they may lead to tremendous sound insulation problems between adjacent offices and areas. Light weight construction is also frequently employed for the subdivision of large space into executive cabins and secretarial areas. Where such construction is considered desirable, efforts should be made to provide a double-skin panel. The panels should be isolated from each other as far as possible either by the use of separate framing or by the use of elastic discontinuities in the construction, and a sound absorbing material may be introduced in the air cavity between the panel. The partitions should be of full height up to the bottom of the roof above and any openings required for air movement should be provided with sound attenuators compatible with the rest of the partition.
When light weight floors are provided in multi-use buildings, adequate attention shall be paid to the question of airborne and structure-borne noise transmission from the upper floors to the floors below. For effective reduction of airborne noise, a double panel hollow floor construction may be employed with some heavy sound damping material introduced between the panels and the panel isolated from each other. The sound damping material could be sand, mineral wool, etc. In case impact noise isolation is also required, the upper panel should be effectively isolated from the rest
of the floors and building structure. The choice of the isolation layer would of course depend upon the lowest frequency of interest.
Another point to be kept in mind when going in for light weight construction is to ensure that the light weight panels are not in resonance with the natural frequencies of any mechanical equipment installed inside the building. Light weight materials have high natural frequencies well within the audio range and may resonate or vibrate due to an applied vibratory force. This vibratory force is caused by mechanical equipment, road traffic, rail traffic, etc. Special measures also need to be taken to isolate either the source or the building so as to reduce the amount of vibration transmitted to the building structure.
A new concept in office planning is the use of open plan offices. Large open floor spaces are converted into an office area with senior executives, junior executives and secretarial staff all seated within the same area without the use of any partitions or walls. While this method of planning is appreciated, it leads to a problem of inadequate acoustical privacy between adjacent work spaces. Speech privacy in open plan offices is defined by the speech interference level of intruding noise. Speech privacy between two adjacent rooms or spaces is, therefore, a function of two key parameters; noise reduction of the intervening partition and background noise levels.
Special design measures are, therefore, required to reduce the level of intruding sounds at work places to acceptable low value so that people are not disturbed and adequate privacy is maintained. Some special measures which might be considered for such open plan offices are the use of an acoustical ceiling together with partial height barriers between work spaces, all designed to provide adequate privacy between adjacent work spaces. In addition use may have to be made of an electronic background masking noise system which provides a constant level of a generally acceptable background noise in the entire office area. The masking noise system is a very useful concept in open plan office design because by raising the background level at every workplace, intruding noises are made less disturbing. A background music system cannot serve as a noise masking system because the music does not have a constant spectrum or sound level. In fact the background noise masking system shall be introduced gradually without the knowledge of employees. The air-conditioning system can also be used to generate background masking noise, if the noise level from the fans, ducts and grills is suitably tailored to generate the desired frequency spectrum. However, it is not simple to predict the noise level of air conditioning
components accurately. On the other hand, the electronic system enables both the level and the spectrum of the background noise to be accurately adjusted to suit individual job requirements.
It is important that machines like keyboards, typewriters, printer, etc, should be quiet in themselves and also be fitted with resilient pads, to prevent the floors or tables on which they stand from acting as large radiating panels. It is desirable to locate machines further apart and to apply sound absorbent treatment to the ceiling.
If banking halls are large and lofty, noise nuisance tends to be aggravated. It is advisable to avoid high reflective ceilings. The worst effects may be reduced by segregating the noise from the quiet operations and screening one from the other and by applying sound absorbent materials to the surfaces of the ceilings, screens and nearby walls. Resilient flooring is also recommended.
Noise nuisance may be minimised by the provision of resilient flooring, sound absorbent ceilings and heavy full height screens between the public space and the clerical office.
The provision of a sound absorbent ceiling, resilient flooring and the use of plastics trays and tables with quiet tops are recommended.
The effective length of long corridors should be limited by providing swing doors at intervals. Hard floor finishes and board and batten floors in corridors should be avoided. The provision of a sound absorbent ceiling in corridors is recommended. Floor ducts should be planned on one side of corridors.
The noise from slamming of doors may be reduced by fitting automatic quiet action type door closers. Door buffers are useful but may reduce insulation of airborne sound due to the inevitable gaps between buffers. Continuous soft, resilient strip let into the door frames is preferable. The use of quiet action door latches is recommended.
Staircases and lifts should be isolated from quiet rooms and should have silent type doors.
With open window (single or double) the sound reduction (Dw) will be 5-10dB, and with sealed double
windows it will be 40-45 dB. Intermediate values are obtainable with closed openable windows (single or double) but only, of course, at such times as ventilation may be dispensed with. Having to choose between ventilation and noise exclusion is a serious handicap to efficient working in offices. In large office blocks on noisy sites, consideration should be given to the provision of sealed double windows and mechanical ventilation at least in the offices on the sides of the building exposed to noise.
8.3.3.1 The insulation necessary between adjoining rooms, both horizontally and vertically, depends upon the amount of noise created within the rooms, the amount of intruding noise and whether it is important that conversation should not be overheard between rooms. Generally a sound isolation value (Dw) of 40 dB between one room and another room in office is recommended.
8.3.3.2 The following list may be considered as broad classification of noise producing rooms and rooms requiring quiet though many offices fall into both categories. Where rooms in opposing categories are planned adjacent to each other, a sound reduction Dw of at least 45 dB should be provided between them.
Sl No. Noise Producing Rooms i) Entrance and reception halls, staircases and corridors used by the public ii) Lifts and lift halls iii) Motor and plant rooms iv) Lavatories v) Public offices vi) Canteen and kitchens vii) Office machine rooms and typing pools viii) Recreation rooms ix) Large general offices x) Cinemas and projection rooms: Sl No. Rooms Requiring Quiet Conditions i) Executive's rooms, Conference rooms and board rooms ii) Interview rooms iii) Offices for one or two persons iv) Medical officer's rooms v) Sick rooms vi) Rest rooms vii) Libraries viii) Telephoning rooms
a) Rooms requiring quiet (as listed above) on a quiet site where privacy is required Dw 45 dB
b) Rooms requiring quiet (as listed above) but on a noisy site or where a lower degree of privacy is tolerable 40 dB
c) Clerical offices in which noise does not constitute a major nuisance 30 dB
8.3.3.3 It is recommended that the minimum sound reduction index, Rw for floors should be 45 dB, and the floors should have a resilient finish.
Hotels and hostels are primarily used as dwelling units, and hotels also provide for public entertainment. The most serious risk, of course, is disturbance to sleep, and adequate care therefore needs to be taken to protect the occupants from being disturbed by outdoor and indoor noise.
Hotels near railway stations, airports, highways and those situated in highly urbanized areas are especially vulnerable to outdoor noise. The outdoor noise in many of the areas is of a high level even late at night and early in the morning. The noise could also be due to other types of activities such as building construction (pile driving, concrete mixing, etc) and due to various types of portable utility equipment, such as compressors or generators.
Insofar as indoor noise is concerned, the noise could be due to the occupants themselves, which is transmitted from one room to the other. It could also be due to public functions and late night use of restaurants located in the hotel, as also due to miscellaneous utility equipment installed for providing and maintaining the services in the hotel, such as air conditioning equipment, pumping equipment, power laundry and kitchen. Sometimes hotels equipped with standby generators are a potential source of noise. Another source which could lead to disturbance to the occupants is the plumbing system.
While it is desirable to locate the hotel, or hostel away from an area where there is a high ambient noise level, many a time these have to be located in noisy areas for public convenience. Hotels near airports and railway stations are becoming popular because they are convenient for passengers in transit. Hotels located in the commercial areas of a city are also a commercially
viable proposition and many a time this factor outweighs the other problems associated with such a location. When a reasonably quiet location is not possible, it is desirable that adequate measures be considered to provide a comfortable acoustical environment for the occupants.
Where a hotel is located in a noisy environment, the provision of sealed windows (single or double) and provision of an air conditioning system is desirable for rooms exposed to noise. The requirements for the windows would of course depend upon the level and character of noise in the area.
The general recommendations for satisfactory acoustical design of hotels and hostels are given in 9.2.2.1 to 9.2.2.7.
9.2.2.1 Hotels of all classes shall by necessity provide good protection against indoor noise. Since hotels can be considered as flats, the standards of protection recommended for flats are also applicable to hotels. Partition between guest rooms and between rooms, corridors and floors shall not be less than 230 mm brick wall plastered or equivalent ( Rw = 50 dB). The floors shall have proper impact insulation. Special attention should be paid to built-in wall cupboards as these are potential areas of sound leakage. These will not serve as sound insulating partitions and may not be relied upon to increase the insulation value of partitions against which they may be built. In fact, partitions between adjoining rooms should be continuous behind the cupboards. Use of silent type door gear and cupboard catches is also highly desirable.
9.2.2.2 Door openings on opposite sides of corridors shall be staggered and doors shall be provided with gaskets on head, sides and threshold. Intercommunicating doors should be double doors, fully gasketed. Doors should also have quiet action latches. Whenever possible, rooms should be entered through a baffle lobby. Wherever possible, corridor walls should not have ventilators unless they are double glazed and non-openable.
9.2.2.3 Corridors and staircases may have resilient floor coverings and sound absorbent ceilings are desirable unless the corridor is fully carpeted. Staircases and lift wells may be cut off from corridors by means of swing doors and, if possible, isolated from guest rooms by linen stores or similar rooms. Room service pantries on floors can also be a source of noise and may be separated from corridors by baffle lobbies, unless the rooms themselves have baffle lobbies.
9.2.2.4 Except within the same suite, bathrooms should not be planned next to bedrooms. Where this is unavoidable, internal pipe shafts with heavy walls,
unpierced on bedrooms side may be used as means of separation. It is important to choose quiet type of sanitary fittings and to design the plumbing system so as not to create noise by avoiding sharp bends, restrictions of flow, quick-action valves that might cause water hammer, etc.
9.2.2.5 Air conditioning system should be quiet in operation. Care should also be taken that the air-conditioning ducts do not lead to a cross-talk problem between rooms. Suitable acoustical lining should be provided in the ducts consistent with the fire safety requirements of the buildings.
9.2.2.6 Large hotels often have banquet halls and conference halls which are separately hired out for public and private functions. Late night restaurants and night clubs are also popular and functions in all these areas may go on well into the night. It is therefore essential that these rooms be effectively isolated from bedrooms and effective insulation from all possible noise sources is considered. Here it is not only necessary to consider the airborne sound insulation but it is also necessary to consider the question of structure-borne and impact noise transmitted from areas where there might be dancing late into the night. Floating floors may be considered for structure-borne sound isolation for dance floors and loudspeakers.
9.2.2.7 While most of the noise problems encountered in hotels are applicable to hostels, the latter are normally of more economical construction and, therefore, do not cater for special sound insulation provisions. However, as far as possible, precautions should be taken to provide comfortable conditions in hostel rooms. This is especially true for student hostels where each room is also a living room. Students might play music or have loud discussions late into the night.
This may disturb sleep or study of other students. Proper precautions should, therefore, be taken to provide satisfactory conditions.
Ventilating ducts or air transfer openings where
provided should be designed to minimise transmission of noise. For this purpose, sound attenuating devices having necessary insertion loss may be installed in these openings.
All partitions should be sealed effectively where they butt against rest of the structure. All doors and windows should be properly gasketed where a high degree of sound insulation is desired.
This requires the use of discontinuous or non-homogeneous materials in the construction of the structure.
The floor of a room immediately above the bed room or living room shall result in an impact sound pressure level ( L'nT,w ) not greater than 60 dB. Typically, a 150 mm thick concrete floor with thick carpet (12 mm) covering would satisfy this requirement.
5.2.3.6 Main staircases in blocks of flats are often highly reverberant. Some of the surfaces at least (for example, the soffits of stairs and landings) should be finished with sound absorbent materials, wherever required.
In the case of schools, the concrete floor of the room immediately above the teaching rooms shall provide an impact sound pressure level, LnT,w' not greater than 70 dB. For example, a covering of 6 mm linoleum or cork tiles on concrete floor (hollow or solid) weighing not less than 220 kg / m² will usually meet the above requirement.
16
Noise from water or heating pipes may be reduced by installing systems which operate at comparatively low pressure and velocities. Silencing pipes and specially designed flushing action reduce water closet noise at source and make structural measures easier to apply. The ventilation system should be designed so as not to create a noise problem. Silent closers should be fitted to doors.
Since the various departments or units may be planned in many ways, only general guidance on the insulation values for walls and partitions is as given below:
a) It is recommended that walls or partitions between rooms should normally have an Rw of at least 45 dB. Higher values of Rw of at least 50 dB are necessary where a noisy room is adjacent to one requiring quiet conditions. Doors should be solid with close fitting in the frames.
b) There is little insulation value in double swing doors and where these are fitted to a noisy room the opening should be planned so that it is screened from areas requiring quiet by a baffle lobby lined with absorbent material. Very high insulation values may be necessary in special cases and exceptional measures may be required.
c) Solid floors with floating finishes and resilient surfaces are necessary particularly between wards and other parts of the building. Ordinary timber board on joist floors should never be used.
d) Conduits, ventilation ducts, chases, etc, should be constructed so as not to form easy by-pass for disseminating noise about the building, and should be provided with sufficient sound insulation. Pipe ducts should be completely sealed around the pipes where they pass through walls or floors. Ducts carrying waste or water pipes should be lined with sound insulating material to prevent noise from the pipes passing through duct walls into the rooms through which they pass.
Most surfaces in hospitals should be easily cleanable, so as to prevent the build-up of bacteria which may cause cross-infection. Many sound absorbent materials of a soft nature and difficult to clean are unsuitable for use in some hospital areas and lose much of their effectiveness, if painted for hygienic reasons.
Some porous materials with very thin non-porous coverings (like mineral wool covered with thin plastic sheets) have good sound absorption and when covered with a perforated sheet metal facing can be used in most areas requiring a washable acoustical treatment. In noisy areas, such as corridors and waiting rooms, however, a wider choice of absorbents is available.
In the ward, bed curtains, window curtain, etc, add to the absorbent properties of the room and help reduce
18
reverberation in otherwise hard surfaced surroundings.
7.3.5 Sensitive areas such as operation theatres, doctors' consultation rooms, intensive care units (ICU) require special consideration against noise control. Apart from outdoor noise, a common problem is the transmission of sound between the consulting room and the waiting room. To ensure silence, a sound isolation Dw of 45 dBA, between the rooms shall be provided. If the doors are directly connected by a single communicating door it will not be possible to achieve these values of isolation Dw . To obtain 40-45 dBA insulation between communicating rooms, it is necessary to provide two doors separated by an air gap, such as a lobby or corridor.